Liebert 700VA, GXT3, 3000VA user manual Battery Mode Shutdown, On Battery, Low Battery

Page 31

Communication

5.3.2Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4.

Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and mounted at remote location.

NOTE

Remote Power Off will be performed by NO contact.

A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS. The connection to the Liebert GXT3 for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the mains power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

5.3.3On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

5.3.4Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

NOTE

The rated values for the dry contacts for the On Battery and Low Battery signals are:

Rated Voltage: 30V (AC or DC)

Rated Current: 300mA

25

Liebert® GXT3

Image 31
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Communication MaintenanceTroubleshooting OperationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols Available Models FeaturesUPS models, power ratings Model Nominal Power RatingVentilation Slots Operation and Display Panel Rear Panel FeaturesAppearance and Components AppearanceMajor Components Operating principle diagramOperating Mode Frequency Converter Mode Manual Bypass ModeBattery Mode Battery Recharge ModeWhat’s Included Preparation for InstallationInstallation Unpacking and InspectionFront Plastic Bezel Cover Mechanical InstallationTower Installation Connectors Spacers Support BasesLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Cable Connection Connecting to AC Mains and LoadsConnecting Battery Cables Specification of input circuit breakerConnecting USB Communication Cables Connecting Communication CablesStandby/Manual Bypass button 1 On/Alarm Silence/Manual Battery Test buttonControl Buttons Operation and Display PanelLevel Indicators Battery Level Indicators IndicatorsLoad Level Indicators UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Manual Bypass Startup Checklist for the Liebert GXT3Manual Battery Test Starting the UPSShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Communication Liebert IntelliSlot Communication CardsLiebert MultiLink USB Port Communication Configuration ProgramOutput voltage option, all models Terminal Block Communication Any Mode ShutdownOn Battery Battery Mode ShutdownLow Battery Replacement battery pack model numbers Replacing the Internal Battery PackMaintenance Battery Replacement ProceduresBattery Connector Battery ChargingInternal Battery Pack Handle Pull Out with Battery Handle Checking UPS Status PrecautionsChecking UPS Functions Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsCondition Alarm Audible AlarmAudible alarm description Troubleshooting tableEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Care Ne tIs t Twor k