Liebert 3000VA Replacing the Internal Battery Pack, Maintenance, Battery Replacement Procedures

Page 32

Maintenance

6.0MAINTENANCE

This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions.

! WARNING

The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the battery pack:

Remove rings, watches and other metal objects.

Use tools with insulated handles.

Do not lay tools or other metal objects on the batteries.

If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson® representative immediately.

Do not dispose of batteries in a fire. The batteries may explode.

Handle, transport and recycle batteries in accordance with local regulations.

6.1Replacing the Internal Battery Pack

The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Refer to Table 7 for internal battery pack part numbers for Liebert GXT3 UPS:

Table 7

Replacement battery pack model numbers

 

 

 

 

 

 

 

Replacement Internal Battery

Quantity

UPS Model Number

Pack Model Number

Required

 

 

 

Liebert GXT3-700RT230

GXT3-5A48BATKIT

1

 

 

 

Liebert GXT3-1000RT230

GXT3-5A48BATKIT

1

 

 

 

Liebert GXT3-1500RT230

GXT3-7A48BATKIT

1

 

 

 

Liebert GXT3-2000RT230

GXT3-9A48BATKIT

1

 

 

 

Liebert GXT3-3000RT230

GXT3-9A72BATKIT

1

 

 

 

 

Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to obtain the part number and pricing of the appropriate replacement battery pack.

6.1.1Battery Replacement Procedures

1.Gently remove the front plastic bezel cover from the UPS.

2.Loosen and remove the six screws on the battery door, as shown in Figure 21.

3.Lay the battery door and screws aside for reassembly.

Figure 21 Removing the front plastic bezel cover and battery door

Battery Door

Screws, 6

Front Bezel

4.Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in Figure 22.

Liebert® GXT3

26

Image 32
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Maintenance TroubleshootingOperation CommunicationFigures Page Important Safety Precautions UPS Safety NotesBattery Safety Information for the Protection of the EnvironmentGlossary of Symbols Features UPS models, power ratingsModel Nominal Power Rating Available ModelsRear Panel Features Appearance and ComponentsAppearance Ventilation Slots Operation and Display PanelOperating principle diagram Major ComponentsOperating Mode Manual Bypass Mode Battery ModeBattery Recharge Mode Frequency Converter ModePreparation for Installation InstallationUnpacking and Inspection What’s IncludedMechanical Installation Tower InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverOperation and Display Panel Rotated Clockwise 90 Degrees Liebert GXT3 UPSRack Installation Pulling inner member from each bracket assemblyInstalling rear member of each bracket assembly Installing inner members Connecting to AC Mains and Loads Connecting Battery CablesSpecification of input circuit breaker Cable ConnectionConnecting Communication Cables Connecting USB Communication Cables1 On/Alarm Silence/Manual Battery Test button Control ButtonsOperation and Display Panel Standby/Manual Bypass buttonLoad Level Indicators IndicatorsLevel Indicators Battery Level Indicators UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Startup Checklist for the Liebert GXT3 Manual Battery TestStarting the UPS Manual BypassDisconnecting Input Power from the Liebert GXT3 Shut Down the Liebert GXT3Liebert MultiLink Liebert IntelliSlot Communication CardsCommunication Output voltage option, all models Configuration ProgramUSB Port Communication Any Mode Shutdown Terminal Block CommunicationLow Battery Battery Mode ShutdownOn Battery Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Replacement battery pack model numbersInternal Battery Pack Handle Pull Out with Battery Handle Battery ChargingBattery Connector Checking UPS Functions PrecautionsChecking UPS Status UPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Battery Cabinet Input Breaker External Battery ConnectorSpecifications Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSBattery run time Recharge Time See TableBattery cabinet specifications Operating temperature parametersBattery run times CabinetProduct Warranty Registration Ne t Is tTwor k Care