525 Programmable Motion Controller

Figure 13 Differential Input Configuration

Feedback Current

Feedback current (+) and Feedback current (-) are inputs to allow the 525 PMC to monitor the motor current via the voltage proportional to current output on the external drive amplifier. This analog input is scaled at +/-5VDC = continuous current and +/-10VDC = peak current. Fault times range from 4-10 seconds at slightly greater than continuous current to 2-4 seconds at peak current. This is a high impedance input which is referenced to logic ground. Scaling of this input is programmable.

Inputs 1 & 2:

Inputs 1 & 2 allow for external drive's fault indications to be sent to the 525 PMC. A fault on Input 1 will produce a "9" on the display of the 525 PMC and a fault on Input 2 will produce a "11". Polarity of these inputs is programmable. If one or both of these inputs are not used they should have their polarity set at (-) with the "Setup Menu" of PCX (see PCX 6.X manual) or with serial commands. Typical input configuration is shown in 14.

Figure 14 Input Polarity

Drive Enable Outputs

The drive enable outputs allow the 525 PMC to disable the external drive during power up, a bridge inhibit or a fault condition. The output is provided with both normally on and normally off outputs. To utilize the normally on output connect between drive enable (+) and normally on drive enable (-). Consequently, to utilize the normally off output connect between drive enable (+) and normally off drive enable (-). The (+) indicates the collector of an optical isolator while the (-) indicates the emitter.

12

Image 20
Contents Programmable Motion Controller Installation Programmable Motion Controller Programmable Motion Controller Disclaimer Introduction Product OverviewCommand Signals External Drive InterfaceIndexing Mode Pulse ModeAnalog Mode Operating ModesProgrammable Motion Controller Installation Overview SafetyAC Input Line GroundingElectrical Noise System Grounding illustrationShielding Wiring LayoutMagnetic Coil Noise Selecting An Enclosure Enclosure SizeEncoder Feedback Encoder Model SDC-15-1, 1024 Line DensityEncoder Sine Wave Signals Encoder, Model SDC-25-1, 1024 Line DensityEncoder Square Wave Signals Encoder Signal QualityEncoder Feedback Cables Model SDC-15-1 Encoder ConnectionsSignal Discriptions Encoder input signalsExternal Drive Connections To The 525 PMC Encoder +5VDC supplyCommand + and Command Output Command Output PolaritySignal Path ShieldInputs 1 Drive Enable OutputsFeedback Current Drive Enable Outputs Drive Reset OutputsMinimum System Configuration Minimum System ConfigurationControl Control Interface Command DeviceOperating Modes Mode Selection Dip Switches/Mode Selection Factory Defaults ShownPulse Mode Pulse ModeCommand Connector Circuit Example Of Sinking/Sourcing Connections Analog Mode Velocity or Torque Analog Velocity/Torque ModeCommand Input Circuit Multi-Drop Configuration Serial InterfaceSerial a Serial BDip Switch Settings Multi-Drop ConnectionDip Switches Factory Defaults Shown Dip Switch Function Descriptions Serial CablesTIX-XXX & TIA-XXX Wiring Diagrams 525 PMC To IBM Serial Port Input Output Interface O NomenclatureInput and Output Wiring, Sinking and Sourcing Input and Output FunctionsInstallation of Application Modules PCM Modules I/O ConnectionsO Connections IOM-1 And PCM Modules Overview Fault PolaritySetting the Fault Input Polarity Fault Input Setup Fault System CalibrationSetting the System Calibration System Calibration Calibrate VelocitySystem Calibration Encoder Lines System Calibration Index Number System Calibration Position Loop Gain System Calibration Adjustment Range Programmable Motion Controller Specifications Mounting Information Mounting Information