Divar Installation Manual Hardware setup
EN
External I/O connection
Alarm inputs and outputs are supplied via a
13 | 1 |
25 | 14 |
Connecting the Inputs
Each (alarm) input line can be switched by a relay contact from devices such as pressure pads, passive
Connecting the Alarm Outputs
The four alarm output relays respond to input alarms and triggers. You can configure the alarm outputs as N/O or N/C in the menu system. The relays are active for the duration of the driving event. Connect the application to the alarm output relays (resistive loads only). Do not exceed 30 Vac, 40Vdc, 500 mA (continuous) or 10VA on an alarm output relay's contacts. The contacts must not be used at AC line voltages.
Specifications
1A | R |
| 3A |
| ||||
E |
|
| ||||||
1B |
| 3B |
| |||||
L |
|
| ||||||
2A |
| 4A |
| |||||
A |
|
| ||||||
2B | Y |
| 4B |
| ||||
|
| GND |
|
|
| |||
|
|
|
| |||||
1 |
|
| IN | 9 |
| |||
2 |
|
| 10 |
| ||||
|
| GND |
|
| ||||
|
|
|
|
Alarm input impedence: Input voltage range: Input voltage treshold:
Switching current (resistive): Carrying power:
Switching voltage (resistive):
Internal
10VA max
30 Vac / 40 Vdc max
3 |
| IN | 11 | ||
4 |
|
| 12 | ||
|
| GND |
|
| |
|
|
| |||
5 |
| IN | 13 | ||
6 |
| 14 | |||
|
| ||||
|
| GND |
| ||
|
|
| |||
7 |
| IN | 15 | ||
8 |
|
| 16 |
Panel view
External I/O - 25-pole D-type socket
Signal name: | Pin no. | Description |
Alarm_in_1 | 1 | Alarm input 1 |
|
|
|
Alarm_in_2 | 2 | Alarm input 2 |
|
|
|
Alarm_in_3 | 3 | Alarm input 3 |
|
|
|
Alarm_in_4 | 4 | Alarm input 4 |
|
|
|
Alarm_in_5 | 5 | Alarm input 5 |
|
|
|
Bosch Security Systems