TROUBLESHOOTING

Solutions

Begin the troubleshooting process by referring to the error messages on the LCD Display and/or the Status LEDs on the control board. Use pages 36-40 to identify the Troubleshooting Reference # (TS Ref#) then reference the table below.

TS Ref#

CHECK

Page Ref#

1

Check that the high voltage power supplied to “EMI Board” is within range.

 

 

100V-120V or 200V-240V

pg 18

2

Remove and check EMI Fuse for continuity.

pg 3, 18

3

Check that the “Voltage Selector”, on the EMI Board, is set according to the high

 

 

 

voltage power supply. 115VAC or 230VAC

pg 3, 18

4

Check that the “AC POWER” switch is turned ON

pg 3, 18,

 

 

36, 37

 

 

 

5

Check that the Power Harness is connected to the control board.

pg 4, 18

6

Check that the limit circuits are Normally Closed (N.C.). Check the limit switch.

pg 20-21

 

 

 

7

Check Motor Fuse on the control board.

pg 4

8

Check that the operator is not in Manual Release mode

pg 3, 11

 

 

 

9

Check the Status LEDs and LCD Display to determine if the control board is

pg 24, 26,

 

receiving an input from any external devices or if the “ODS” has been triggered.

36-38

 

 

 

10Remove the external devices from the control board to determine if the control pg 29-32, board is responding to an input or problem with the external device or wiring. 36-37

11

Check the “ODS” setting on the control board.

pg 8, 12,

 

 

26

12

Check that the gate can be moved manually with low resistance throughout its

 

 

full range of motion.

pg 8, 17

 

 

 

13

Check the limit position.

pg 20-21

14

Not applicable to this model

pg 4

 

 

15

Check that the EMI cable is properly connected to the “EMI” connection at the

 

 

 

VFlex control board and at the EMI Board.

pg 4

16

Check the LCD Display for Error Messages

pg 40

17

Not applicable to this model

 

 

18

Check 4 Amp fuse on the control board

pg 4

19Manually adjust any setting on the Control Board to clear all wireless override settings

20 Check for 24VAC out from the Toroidal Transformer and Power Harness

pg 3, 18

21 Check the EMI Cable and contacts between the EMI Board and the VFlex Board pg 2, 4

?The Control Board or EMI board may be damaged. Call Viking Technical Support for further assistance

VIKING TECHNICAL SUPPORT 1.800.908.0884

4 1

 

 

Image 43
Contents Instructions Viking F-1 Swing Gate Operator Vehicular Gate Operator Revision F1NXMN10.D October Description Parts DiagramOperator References Control Board References Limit Setup ButtonsTable of Contents Important Safety Instructions Important Safety InformationImportant Installation Instructions Important Installation Instructions General Safety Precautions MaintenanceUL325 Gate Operator Classifications Install the gate operator only whenGlossary Secondary Entrapment Protection Photo Beam non-contact sensor InstallationTo resume normal operation Edge Sensor contact sensor InstallationWhen manual operation is required Manual ReleaseManual Reset for the Audible Alarm Audible Alarm Reset Switch InstallationLocate Control Buttons SpecificationsSingle Phase 50Hz / 60Hz Alternative Power 24VAC / VDC 60VA or SolarConcrete Pad Option Gate Operator InstallationRequired ADD-ON PART# VA-F1PS Post Mounting OptionTechnical Tips Operator and Arm Geometry Operator PositioningStep Tips for proper ground installation Electrical InstallationHigh Voltage Supply Option Solar Supply Option Low Voltage Supply OptionAt the Limit Cam & Holder assembly Limits Setup1a 1b Limits Setup Two Wire Communication MASTER/SLAVE SetupCable Requirements Required ADD-ON Choose option a or B Wireless Communication OptionsObstruction Detection Sensor Initial SettingsTimer Hold Open Timer ODSFail Safe Mode Control Board SetupAuto Open Power Failure Option Last Open Power Failure OptionFlashing Overload When the Obstruction Sensor detects an obstruction it willObstruction Sensor Primary Entrapment Protection ODS Obstruction Detection SensorTo set the heater to turn on at the Close Limit Viking Lock ModeUse the LCD Display to activate this feature Viking HeaterThis page Left Blank Intentionally Check for proper operation Accessory ConnectionsRe-Open Photo Beam vehicular Safety COM +Open-Stop-Close Radio Receiver TypicalOpen Only ATG Anti-Tailgate Anti-Tailgate, Open Commands & Guard StationOpen Commands Guard StationViking Loop Rack Guidelines for Loop Installation Accessory ConnectionsMagnetic Lock, Lock Solenoid Power for the LocksMagnetic Lock Lock Solenoid Barrier Arm B-12 Synchronization Option Synchronization with B-12LED References TroubleshootingTroubleshooting LCD Display References LCD MSG MeaningTroubleshooting Error Messages Check SolutionsPower Connections Access Control ConnectionsTechnical TIP Viking uses Appendix aRelays In General GeneralCommon Radio Receivers Connections Batteries & Fuse Appendix CSolar Applications PanelsViking Expansion Products Viking Konnect Diagnostic Tool On-site remoteViking Konnect Master/Slave Kit Secure and reliable OUR Continuous Commitment to Excellence Standard Features