Bard TCS22-***-003 manual Mounting, High Voltage Wiring

Page 17

3.0INSTALLATION

This section discusses mounting and wiring of the TCS22 into the building. Also included is an installation checklist to be completed by the installing contractor. See installation instructions supplied with the Bard Wall-Mount air conditioners for information on installing the air conditioners.

This controller should be installed and serviced by a qualified service technician only.

3.1Mounting

TCS22 should be mounted on a flat vertical surface four (4) to six (6) feet from the floor of the building. When choosing a suitable location take into consideration that the electrical connections can be made from the back or top of the TCS22. See Figure 3 for rear electrical entrance locations.

The TCS22 is secured to the wall with four (4) - 1/4 inch fasteners with flat washers. Hollow wall anchors or lag bolts are suitable as dictated by the wall construction. See Figure 3 for a bolt pattern layout drawing.

!WARNING

_________________________________

HAZARD OF ELECTRIC SHOCK.

ELECTRIC SHOCK CAN RESULT IN SERIOUS INJURY OR DEATH.

DISCONNECT THE REMOTE ELECTRIC POWER SUPPLIES BEFORE SERVICING.

3.2Wiring

Electrical connections can be made from the back or top of the TCS22. All wiring should exit the TCS22 in conduit. Use the supplied wire ties and cable holders to route unit low voltage, communication, and sensor wiring neatly. Avoid looping excess wire. See Figure 2 for suggested conduit connections.

Never connect or disconnect wiring from the controller with power connected to the controller or to either of the Bard Wall-Mount air- conditioners.

3.2.1HIGH VOLTAGE WIRING

IMPORTANT: High voltage wiring must not be run in the same conduit as low voltage control or sensor wiring. Failure to comply with this requirement will result in poor or no remote communication and/or in inaccurate sensor reading.

Supply power is 208/240 VAC, 50/60 Hz, 1 Phase at 3 amps minimum circuit ampacity. A 3 amp circuit breaker is supplied as part of the TCS22. This circuit breaker is for internal circuit protection only and cannot be used as a disconnect. Supply wire size should be 18 ga. or larger. Use Copper Conductors Only. All wiring must comply with the applicable sections of the National Electrical Code ( NEC) and any applicable local codes.

The TCS22 is shipped for 240 VAC operation . For 208 Volt operation change both transformer primaries in the TCS22 to the 208 volt tap. See Wiring Diagram. The acceptable operating voltage ranges for the 240 and 208 volt taps are:

Tap

Range

240

253-216

208

220-187

Connect the high voltage power supply to Terminal Block TB2. Connect ground wire to the ground connector provided. TCS22 must be grounded for proper operation. Failure to ground the controller may cause erratic controller operation and inaccurate sensor operation. See Figure 2 and the wiring diagram.

2100-444-003A

Page 11

Image 17 Contents
Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Shipping Damage Package ContentsAdditional Requirements Copyright NoticeBuilding Points to be Monitored GeneralWallmount Points to be Monitored for Each Unit Building Points to be ControlledWallmount Points to be Controlled Alarm PointsSystem Points to be Controlled Inputs Mechanical Specifications Electrical SpecificationsEnvironmental Specifications Model NomenclatureTemperature Sensors Indoor and Outdoor Sensor SpecificationsHumidity Sensors Compressor Current Sensor Blower Airflow Switch Front Cover Control Location Mounting Template Mounting WiringHigh Voltage Wiring Wiring Sensors Wiring LOW VoltageOutdoor Temperature Sensor OTS Zone Temperature Sensor ZTSWiring Inputs & Outputs Wiring Ethernet Wiring Telephone LineExternal Wiring Internal Wiring Power Backup System Installation Check List System Startup Wallmount Startup Checklist2 TCS22 Startup Checklist Cooling Sequence with Economizers Sequence of OperationHeating Sequence FAN SequenceAlarm Sequence Occupied / Unoccupied Mode SequencePage Dehumidification Sequence Power Management SequenceThermal Shock Protection Sequence Modem SequenceSetpoints Display & Keypad PhysicalsMenu Tree Power UpUnit Status Buildings Status ScreenOutdoor Temperature Room TemperatureRoom Humidity Outdoor HumidityOutdoor Enthalpy Free CoolingRoom Occupied YES/NO Unit #1 Economizer Unit Status ScreenUnit #1 Compressor Unit #1 HeaterUnit #1 Filter Alarms MenuUnit #1 Discharge AIR Temperature Space Humidity Alarm Space Temp AlarmUtility Power Fail 3.4 #1 Compressor Alarm3.5 #1 Filter Alarm Outdoor Temp Alarm Fire AlarmOutdoor Humidity Alarm Door AlarmSetpoints Screen Unoccupied Cooling Setpoint Occupied Cooling SetpointLOW Temperature Alarm Setpoint High Temperature Alarm SetpointHigh Humidity Alarm Setpoint LOW Humidity Alarm SetpointFree Cooling DRY Bulb Setpoint Free Cooling Enthalpy SetpointOverrides Unit #1 Screen Enthalpy Lookup Table5.1 #1 Blower Override 5.4 #1 Heater Override 5.2 #1 Economizer Override5.3 #1 Compressor Override Continuous Blower Enables Menu Economizer Operation DRY Bulb Temperature ChangeoverFree Cooling Enthalpy Changeover Daylight Savings TimeEntering Password Password OperationKeyboard Map UNIT#1 Comp OFF Room RH Software Installation InstallationClimateWatch System Software Overview Hardware RequirementsMenu Bar ASI Expert / Bard ClimateWatch SoftwareScreen Overview Status Bar Tool BarController Information Area Project FoldersTCS Communications Software SetupCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page TCS Controller Information Screens Saving TCS ConfigurationLoading TCS Configuration Conditions Main Screen TABTime & Place Unit #1 StatusUnit #2 Status Occupied Cooling Setpoint SET Point TABUnoccupied Cooling Setpoint High Temperature Alarm SetPointOccupied Heating Setpoint Unoccupied Heating SetpointHigh Humidity Alarm SetPoint Low Temperature Alarm SetPointLow Humidity Alarm SetPoint Enthalpy Changeover SetpointDry Bulb Changeover Setpoint Continuous Blower EnableDehumidification Setpoint Active Cooling SetpointOverride #1 TAB Stage IndicatorsActive Dehumidification Setpoint Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Unit #1 Compressor Alarm Unit #1 Filter AlarmUnit #1 Blower Alarm Zone Temperature AlarmOutdoor Temperature Alarm Zone Humidity AlarmOutdoor Humidity Alarm Main Power AlarmFire Trouble Alarm Alarm LOG TAB Outdoor Temperature Offset Zone Temperature OffsetOffsets TAB Zone Humidity OffsetMISC. TAB Unit #1 Supply Air Temperature OffsetOutdoor Humidity Offset Enable Economizer Operation Clear Alarm Event LogEnable Daylight Savings Time Enable 50 hz ClockModel Number Enable Zone DehumidificationModel Serial Number SoftwareTrend TAB Dial OUT TAB Page 2100-444-003A 1 TCS22 Troubleshooting Routine MaintenanceTroubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Wallmount Quick Troubleshooting Guide Operation Procedure