Bard TCS22-***-003 manual Space Temp Alarm, Space Humidity Alarm

Page 38

on the screen. Press the <F1> key. Use the <Up> key to highlight the dashes next to the alarm item to be acknowledged. Press <Enter> to enter edit mode.

If you do not have authority to acknowledge alarms the dashes will not be highlighted. An Engineer authority level is required to override outputs. If you have authority to dashes will be highlighted after pressing the <F1> key.

There are five (5) actions now available, NOP = No Operation, ACK = Acknowledge the alarm, CRAM = Clear alarm ram, ACKA = Acknowledge all alarms, CAF = Clear alarm flag. Use the <Up> and <Down> keys to choose ACK to acknowledge the alarm. Once the desired action is displayed press the <Enter> key to initiate the action. If the action was accepted the screen will show an A next to the alarm type.

The display will then revert to the list item display and within 10 seconds the new action will be updated.

5.3.3.1SPACE TEMP ALARM

The space temperature alarm item will show one of four different alarm messages. A No alarm message indicates that the Zone Temperature Sensor is functioning normally. A Fault alarm message indicates that the Zone Temperature Sensor is sensing a value above 120 Fo or below -20 Fo. This probably indicates a faulty sensor. When a Space Temperature Fault alarm is detected the Zone Temperature value defaults to 74 degrees effectively shutting down heating and cooling until the sensor is replaced.

An Alarm (High) or Alarm (Low) message indicates that the sensor is sensing a temperature above or below, respectively, the High Temperature Alarm Setpoint or Low Temperature Alarm Setpoint.

The Fault alarm takes precedence over the Alarm (High) or Alarm (Low) message. If the Sensor is failed high or low the Alarm (High) or Alarm (Low) alarms will also be activated but only the Fault alarm will be displayed because this is the actual condition causing the other alarms.

These are all self-clearing alarms and will reset themselves when the alarm condition no longer exists. This is a critical alarm.

5.3.3.2SPACE HUMIDITY ALARM

The Space Humidity Alarm item will show one of four different alarm messages. A No alarm message indicates that the Zone Humidity Sensor is functioning normally. A Fault alarm message indicates that the Zone Humidity Sensor is sensing a value above 99 % RH or below 2 % RH. This probably indicates a faulty sensor. When a Space Humidity Fault alarm is detected, the Zone Humidity value defaults to 50 % RH until the sensor is replaced.

An Alarm (High) or Alarm (Low) message indicates that the sensor is sensing humidity above or below, respectively, the High Humidity Alarm Setpoint or Low Humidity Alarm Setpoint.

2100-444-003A

Page 32

Image 38 Contents
Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Additional Requirements Package ContentsShipping Damage Copyright NoticeWallmount Points to be Monitored for Each Unit GeneralBuilding Points to be Monitored Building Points to be ControlledWallmount Points to be Controlled Alarm PointsSystem Points to be Controlled Inputs Environmental Specifications Electrical SpecificationsMechanical Specifications Model NomenclatureHumidity Sensors Sensor SpecificationsTemperature Sensors Indoor and Outdoor Compressor Current SensorBlower Airflow Switch Front Cover Control Location Mounting Template Mounting WiringHigh Voltage Wiring Outdoor Temperature Sensor OTS Wiring LOW VoltageWiring Sensors Zone Temperature Sensor ZTSWiring Inputs & Outputs Wiring Telephone Line Wiring EthernetExternal Wiring Internal Wiring Power Backup System Installation Check List Wallmount Startup Checklist System Startup2 TCS22 Startup Checklist Heating Sequence Sequence of OperationCooling Sequence with Economizers FAN SequenceOccupied / Unoccupied Mode Sequence Alarm SequencePage Thermal Shock Protection Sequence Power Management SequenceDehumidification Sequence Modem SequenceDisplay & Keypad Physicals SetpointsPower Up Menu TreeBuildings Status Screen Unit Status Room Humidity Room Temperature Outdoor Temperature Outdoor HumidityOutdoor Enthalpy Free CoolingRoom Occupied YES/NO Unit #1 Compressor Unit Status ScreenUnit #1 Economizer Unit #1 HeaterUnit #1 Filter Alarms MenuUnit #1 Discharge AIR Temperature Space Temp Alarm Space Humidity AlarmUtility Power Fail 3.4 #1 Compressor Alarm3.5 #1 Filter Alarm Outdoor Humidity Alarm Fire AlarmOutdoor Temp Alarm Door AlarmSetpoints Screen Occupied Cooling Setpoint Unoccupied Cooling SetpointHigh Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint LOW Humidity Alarm SetpointFree Cooling Enthalpy Setpoint Free Cooling DRY Bulb SetpointEnthalpy Lookup Table Overrides Unit #1 Screen5.1 #1 Blower Override 5.4 #1 Heater Override 5.2 #1 Economizer Override5.3 #1 Compressor Override Continuous Blower Enables Menu Free Cooling Enthalpy Changeover DRY Bulb Temperature ChangeoverEconomizer Operation Daylight Savings TimePassword Operation Entering PasswordKeyboard Map UNIT#1 Comp OFF Room RH ClimateWatch System Software Overview InstallationSoftware Installation Hardware RequirementsMenu Bar ASI Expert / Bard ClimateWatch SoftwareScreen Overview Controller Information Area Tool BarStatus Bar Project FoldersSoftware Setup TCS CommunicationsCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page TCS Controller Information Screens Saving TCS ConfigurationLoading TCS Configuration Main Screen TAB ConditionsTime & Place Unit #1 StatusUnit #2 Status SET Point TAB Occupied Cooling SetpointOccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Unoccupied Heating SetpointLow Humidity Alarm SetPoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Enthalpy Changeover SetpointDehumidification Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Active Cooling SetpointOverride #1 TAB Stage IndicatorsActive Dehumidification Setpoint Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Unit #1 Blower Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Zone Temperature AlarmOutdoor Humidity Alarm Zone Humidity AlarmOutdoor Temperature Alarm Main Power AlarmFire Trouble Alarm Alarm LOG TAB Offsets TAB Zone Temperature OffsetOutdoor Temperature Offset Zone Humidity OffsetMISC. TAB Unit #1 Supply Air Temperature OffsetOutdoor Humidity Offset Enable Daylight Savings Time Clear Alarm Event LogEnable Economizer Operation Enable 50 hz ClockModel Serial Number Enable Zone DehumidificationModel Number SoftwareTrend TAB Dial OUT TAB Page 2100-444-003A 1 TCS22 Troubleshooting Routine MaintenanceTroubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Operation Procedure Wallmount Quick Troubleshooting Guide