Bard TCS22-***-003 5.2 #1 Economizer Override, 5.3 #1 Compressor Override, 5.4 #1 Heater Override

Page 47

This list item uses the Clr Verify Alr, O/R On, O/R Off, and Clr O/R actions. The Clr Verify Alr action clears a blower failure alarm in the alarm object. In the event of a unit #1 blower failure alarm, the output of the controller will be disabled until the problem is corrected and the alarm is cleared. Once the problem is corrected use the Clr Verify Alr action to re-enable normal operation of the output.

Any alarm of the Unit #1 Blower must be cleared before an override is accepted. Once overridden the output will remain overridden until the Clr O/R action is sent to the output or power is interrupted to the controller. Entering the O/R On action will turn on the blower output to unit #1 and it will remain on until cleared. Entering the O/R Off action will disable the output to the unit #1 blower and it will remain disabled until cleared. Use the Clr O/R to cancel an override action and resume normal operation.

A supervisor authority level is needed to use this item.

5.3.5.2 #1 ECONOMIZER OVERRIDE

This list item uses the Clr Verify Alr, O/R On, O/R Off, and Clr O/R actions. The Clr Verify Alr has no effect on this item.

Entering the O/R On action will turn on the economizer output to unit #1 and it will remain on until cleared. Entering the O/R Off action will disable the output to the unit #1 economizer and it will remain disabled until cleared. Once overridden the output will remain overridden until the Clr O/R action is sent to the output or power is interrupted to the controller Use the Clr O/R to cancel an override action and resume normal operation.

A supervisor authority level is needed to use this item.

5.3.5.3 #1 COMPRESSOR OVERRIDE

This list item uses the Clr Verify Alr, O/R On, O/R Off, and Clr O/R actions. The Clr Verify Alr action clears a compressor failure alarm in the alarm object. In the event of a unit #1 compressor failure alarm, the output of the controller will be disabled until the problem is corrected and the alarm is cleared. Once the problem is corrected use the Clr Verify Alr action to re-enable normal operation of the output.

Any alarm of the Unit #1 compressor must be cleared before an override is accepted. Once overridden the output will remain overridden until the Clr O/R action is sent to the output or power is interrupted to the controller. Entering the O/R On action will turn on the compressor output to unit #1 and it will remain on until cleared. Entering the O/R Off action will disable the output to the unit #1 compressor and it will remain disabled until cleared. Use the Clr O/R to cancel an override action and resume normal operation. A supervisor authority level is needed to use this item.

5.3.5.4 #1 HEATER OVERRIDE

This list item uses the Clr Verify Alr, O/R On, O/R Off, and Clr O/R actions. The Clr Verify Alr has no effect on this item.

2100-444-003A

Page 41

Image 47
Contents Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Copyright Notice Package ContentsShipping Damage Additional RequirementsBuilding Points to be Controlled GeneralBuilding Points to be Monitored Wallmount Points to be Monitored for Each UnitWallmount Points to be Controlled Alarm PointsSystem Points to be Controlled Inputs Model Nomenclature Electrical SpecificationsMechanical Specifications Environmental SpecificationsCompressor Current Sensor Sensor SpecificationsTemperature Sensors Indoor and Outdoor Humidity SensorsBlower Airflow Switch Front Cover Control Location Mounting Template Mounting WiringHigh Voltage Wiring Zone Temperature Sensor ZTS Wiring LOW VoltageWiring Sensors Outdoor Temperature Sensor OTSWiring Inputs & Outputs Wiring Ethernet Wiring Telephone LineExternal Wiring Internal Wiring Power Backup System Installation Check List System Startup Wallmount Startup Checklist2 TCS22 Startup Checklist FAN Sequence Sequence of OperationCooling Sequence with Economizers Heating SequenceAlarm Sequence Occupied / Unoccupied Mode SequencePage Modem Sequence Power Management SequenceDehumidification Sequence Thermal Shock Protection SequenceSetpoints Display & Keypad PhysicalsMenu Tree Power UpUnit Status Buildings Status ScreenOutdoor Humidity Room TemperatureOutdoor Temperature Room HumidityOutdoor Enthalpy Free CoolingRoom Occupied YES/NO Unit #1 Heater Unit Status ScreenUnit #1 Economizer Unit #1 CompressorUnit #1 Filter Alarms MenuUnit #1 Discharge AIR Temperature Space Humidity Alarm Space Temp AlarmUtility Power Fail 3.4 #1 Compressor Alarm3.5 #1 Filter Alarm Door Alarm Fire AlarmOutdoor Temp Alarm Outdoor Humidity AlarmSetpoints Screen Unoccupied Cooling Setpoint Occupied Cooling SetpointLOW Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint High Humidity Alarm SetpointFree Cooling DRY Bulb Setpoint Free Cooling Enthalpy SetpointOverrides Unit #1 Screen Enthalpy Lookup Table5.1 #1 Blower Override 5.4 #1 Heater Override 5.2 #1 Economizer Override5.3 #1 Compressor Override Continuous Blower Enables Menu Daylight Savings Time DRY Bulb Temperature ChangeoverEconomizer Operation Free Cooling Enthalpy ChangeoverEntering Password Password OperationKeyboard Map UNIT#1 Comp OFF Room RH Hardware Requirements InstallationSoftware Installation ClimateWatch System Software OverviewMenu Bar ASI Expert / Bard ClimateWatch SoftwareScreen Overview Project Folders Tool BarStatus Bar Controller Information AreaTCS Communications Software SetupCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page TCS Controller Information Screens Saving TCS ConfigurationLoading TCS Configuration Conditions Main Screen TABTime & Place Unit #1 StatusUnit #2 Status Occupied Cooling Setpoint SET Point TABUnoccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Occupied Heating SetpointEnthalpy Changeover Setpoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Low Humidity Alarm SetPointActive Cooling Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Dehumidification SetpointOverride #1 TAB Stage IndicatorsActive Dehumidification Setpoint Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Zone Temperature Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Unit #1 Blower AlarmMain Power Alarm Zone Humidity AlarmOutdoor Temperature Alarm Outdoor Humidity AlarmFire Trouble Alarm Alarm LOG TAB Zone Humidity Offset Zone Temperature OffsetOutdoor Temperature Offset Offsets TABMISC. TAB Unit #1 Supply Air Temperature OffsetOutdoor Humidity Offset Enable 50 hz Clock Clear Alarm Event LogEnable Economizer Operation Enable Daylight Savings TimeSoftware Enable Zone DehumidificationModel Number Model Serial NumberTrend TAB Dial OUT TAB Page 2100-444-003A 1 TCS22 Troubleshooting Routine MaintenanceTroubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Wallmount Quick Troubleshooting Guide Operation Procedure

TCS22-***-003 specifications

The Bard TCS22-***-003 is a cutting-edge technological marvel designed for modern thermal management solutions. This unit is revered in the HVAC industry for its innovative features and energy-efficient operation, making it a popular choice among both commercial and residential users.

One of the main features of the Bard TCS22-***-003 is its advanced climate control capabilities. Equipped with state-of-the-art sensors, the unit provides precise temperature regulation, ensuring optimal comfort in interior spaces. The system's intelligence allows it to adapt to varying weather conditions, maintaining consistent indoor temperatures even during extreme external fluctuations.

The Bard TCS22-***-003 also sports a robust energy efficiency rating, setting it apart from traditional heating and cooling systems. With the integration of variable speed technology, the unit optimizes energy usage by adjusting its output based on the current load. This not only reduces energy consumption but also results in lowered utility bills, promoting sustainability and eco-friendly living.

Another notable characteristic is its whisper-quiet operation. Noise reduction has been a focal point in the design of the TCS22-***-003, allowing it to function below typical sound levels associated with conventional HVAC systems. This is particularly beneficial for residential applications where noise pollution can disrupt daily activities.

The unit is built with durability in mind, featuring a weatherproof construction that can withstand various environmental conditions. Its exterior casing prevents moisture infiltration, while corrosion-resistant materials enhance its longevity. As a result, maintenance needs are minimized, further establishing the Bard TCS22-***-003 as a cost-effective solution in the long run.

In addition, the Bard TCS22-***-003 integrates smart technology, enabling users to control the system remotely using mobile devices or smart home automation systems. This level of convenience allows for personalized heating and cooling settings tailored to individual preferences and schedules.

Overall, the Bard TCS22-***-003 is a standout in the HVAC market due to its blend of efficiency, performance, and user-friendly features. Whether for a home or a commercial establishment, this innovative system offers reliable and sustainable climate control solutions that cater to the needs of today's environmentally conscious consumers.