The Fault alarm takes precedence over the Alarm (High) or Alarm (Low) message. If the Sensor is failed high or low the Alarm (High) or Alarm (Low) alarms will also be activated but only the Fault alarm will be displayed because this is the actual condition causing the other alarms.

These are all self-clearing alarms and will reset themselves when the alarm condition no longer exists. This is a medium priority alarm.

5.3.3.3#1 BLOWER ALARM

The Blower Fail alarm item will show one of two different alarm messages. A "No Alarm" message indicates that the blower airflow sensor contacts have closed and the blower is functioning normally. A Fault alarm message indicates that the blower airflow sensor contacts have not closed. A faulty blower motor, wheel or sensor could cause this alarm.

This alarm must be cleared before operation of the blower can resume. Use the Clr Verify Alr action in the Override menu to clear the alarm. This is a critical alarm.

5.3.3.4#1 COMPRESSOR ALARM

The Compressor Alarm item will show one of two different alarm messages. "No Alarm" message indicates that the compressor verify circuit contacts have closed and the compressor is functioning normally. A Fault alarm message indicates that the compressor verify circuit contacts have not closed. A Trip on High or Low pressure, no compressor current, failed blower, or faulty compressor current sensor could cause this alarm.

This alarm must be cleared before operation of the compressor can resume. Use the Clr Verify Alr action in the Override menu to clear the alarm. This is a critical alarm.

5.3.3.5#1 FILTER ALARM

The Filter alarm item will show one of two different alarm messages. "No Alarm" message indicates that the filter is clean enough to operate. A Fault alarm message indicates that the filter is dirty and needs replaced.

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. The filter sensor is a manually reset device and must be reset once the filter is changed to clear the alarm condition. This is a low priority alarm.

5.3.3.6UTILITY POWER FAIL

The Utility Power Fail alarm item will show one of two different alarm messages. A "None" alarm message indicates that no alarm is present and that utility power is present at the site. A "Fault" alarm message indicates that an alarm is present and the system is operating on backup power. This feature will operate only if the TCS22 is connected to an uninterruptible power supply.

This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This is a critical priority alarm.

2100-444-003A

Page 33

Image 39
Contents Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Copyright Notice Package ContentsShipping Damage Additional RequirementsBuilding Points to be Controlled GeneralBuilding Points to be Monitored Wallmount Points to be Monitored for Each UnitAlarm Points System Points to be ControlledWallmount Points to be Controlled Inputs Model Nomenclature Electrical SpecificationsMechanical Specifications Environmental SpecificationsCompressor Current Sensor Sensor SpecificationsTemperature Sensors Indoor and Outdoor Humidity SensorsBlower Airflow Switch Front Cover Control Location Mounting Template Wiring High Voltage WiringMounting Zone Temperature Sensor ZTS Wiring LOW VoltageWiring Sensors Outdoor Temperature Sensor OTSWiring Inputs & Outputs Wiring Ethernet Wiring Telephone LineExternal Wiring Internal Wiring Power Backup System Installation Check List System Startup Wallmount Startup Checklist2 TCS22 Startup Checklist FAN Sequence Sequence of OperationCooling Sequence with Economizers Heating SequenceAlarm Sequence Occupied / Unoccupied Mode SequencePage Modem Sequence Power Management SequenceDehumidification Sequence Thermal Shock Protection SequenceSetpoints Display & Keypad PhysicalsMenu Tree Power UpUnit Status Buildings Status ScreenOutdoor Humidity Room TemperatureOutdoor Temperature Room HumidityFree Cooling Room Occupied YES/NOOutdoor Enthalpy Unit #1 Heater Unit Status ScreenUnit #1 Economizer Unit #1 CompressorAlarms Menu Unit #1 Discharge AIR TemperatureUnit #1 Filter Space Humidity Alarm Space Temp Alarm3.4 #1 Compressor Alarm 3.5 #1 Filter AlarmUtility Power Fail Door Alarm Fire AlarmOutdoor Temp Alarm Outdoor Humidity AlarmSetpoints Screen Unoccupied Cooling Setpoint Occupied Cooling SetpointLOW Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint High Humidity Alarm SetpointFree Cooling DRY Bulb Setpoint Free Cooling Enthalpy SetpointOverrides Unit #1 Screen Enthalpy Lookup Table5.1 #1 Blower Override 5.2 #1 Economizer Override 5.3 #1 Compressor Override5.4 #1 Heater Override Continuous Blower Enables Menu Daylight Savings Time DRY Bulb Temperature ChangeoverEconomizer Operation Free Cooling Enthalpy ChangeoverEntering Password Password OperationKeyboard Map UNIT#1 Comp OFF Room RH Hardware Requirements InstallationSoftware Installation ClimateWatch System Software OverviewASI Expert / Bard ClimateWatch Software Screen OverviewMenu Bar Project Folders Tool BarStatus Bar Controller Information AreaTCS Communications Software SetupCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page Saving TCS Configuration Loading TCS ConfigurationTCS Controller Information Screens Conditions Main Screen TABUnit #1 Status Unit #2 StatusTime & Place Occupied Cooling Setpoint SET Point TABUnoccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Occupied Heating SetpointEnthalpy Changeover Setpoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Low Humidity Alarm SetPointActive Cooling Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Dehumidification SetpointStage Indicators Active Dehumidification SetpointOverride #1 TAB Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Zone Temperature Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Unit #1 Blower AlarmMain Power Alarm Zone Humidity AlarmOutdoor Temperature Alarm Outdoor Humidity AlarmFire Trouble Alarm Alarm LOG TAB Zone Humidity Offset Zone Temperature OffsetOutdoor Temperature Offset Offsets TABUnit #1 Supply Air Temperature Offset Outdoor Humidity OffsetMISC. TAB Enable 50 hz Clock Clear Alarm Event LogEnable Economizer Operation Enable Daylight Savings TimeSoftware Enable Zone DehumidificationModel Number Model Serial NumberTrend TAB Dial OUT TAB Page 2100-444-003A Routine Maintenance Troubleshooting1 TCS22 Troubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Wallmount Quick Troubleshooting Guide Operation Procedure

TCS22-***-003 specifications

The Bard TCS22-***-003 is a cutting-edge technological marvel designed for modern thermal management solutions. This unit is revered in the HVAC industry for its innovative features and energy-efficient operation, making it a popular choice among both commercial and residential users.

One of the main features of the Bard TCS22-***-003 is its advanced climate control capabilities. Equipped with state-of-the-art sensors, the unit provides precise temperature regulation, ensuring optimal comfort in interior spaces. The system's intelligence allows it to adapt to varying weather conditions, maintaining consistent indoor temperatures even during extreme external fluctuations.

The Bard TCS22-***-003 also sports a robust energy efficiency rating, setting it apart from traditional heating and cooling systems. With the integration of variable speed technology, the unit optimizes energy usage by adjusting its output based on the current load. This not only reduces energy consumption but also results in lowered utility bills, promoting sustainability and eco-friendly living.

Another notable characteristic is its whisper-quiet operation. Noise reduction has been a focal point in the design of the TCS22-***-003, allowing it to function below typical sound levels associated with conventional HVAC systems. This is particularly beneficial for residential applications where noise pollution can disrupt daily activities.

The unit is built with durability in mind, featuring a weatherproof construction that can withstand various environmental conditions. Its exterior casing prevents moisture infiltration, while corrosion-resistant materials enhance its longevity. As a result, maintenance needs are minimized, further establishing the Bard TCS22-***-003 as a cost-effective solution in the long run.

In addition, the Bard TCS22-***-003 integrates smart technology, enabling users to control the system remotely using mobile devices or smart home automation systems. This level of convenience allows for personalized heating and cooling settings tailored to individual preferences and schedules.

Overall, the Bard TCS22-***-003 is a standout in the HVAC market due to its blend of efficiency, performance, and user-friendly features. Whether for a home or a commercial establishment, this innovative system offers reliable and sustainable climate control solutions that cater to the needs of today's environmentally conscious consumers.