6.4.3.3 Unit #1 Economizer
The override status box displays the current override condition of the Unit #1 Economizer. It will read “Yes” if the output has been overridden on or off.
The output value box displays the current condition of the Unit #1 Economizer. It will read either on or off.
To override the Unit #1 Economizer on click the Output Verify Action button. Select the “Override Output ON” item and click OK. The override status box will display yes and the Output status will display ON.
To override the Unit #1 Economizer off click the Output Verify Action button. Select the “Override Output OFF” item and click OK. The override status box will display yes and the Output status will display OFF.
To clear an override, click the Output Verify Action button. Select “Clear RAM Override Flag,
6.4.3.4 Unit #1 Heater
The override status box displays the current override condition of the Unit #1 Heater. It will read “Yes” if the output has been overridden on or off.
The output value box displays the current condition of the Unit #1 Heater. It will read either ON or OFF.
To override the Unit #1 Heater on click the Output Verify Action button. Select the “Override Output ON” item and click OK. The override status box will display yes and the Output status will display ON.
To override the Unit #1 Heater off click the Output Verify Action button. Select the “Override Output OFF” item and click OK. The override status box will display yes and the Output status will display OFF.
To clear an override, click the Output Verify Action button. Select “Clear RAM Override Flag,