Bard TCS22-***-003 manual Occupied Cooling Setpoint, Unoccupied Cooling Setpoint

Page 42

SETPOINTS

F1 = EDIT MODE

ENTER TO EDIT

Occ. Cooling SP

75.00F Unocc. Clg. SP

80.00F

Occ. Heating SP

70.00F Unocc. Htg. SP

68.00F

Hi Temp Alarm SP

87.00F

Lo Temp Alarm SP

56.00F

Hi Humidity SP

80.0RH

Low Humidity SP

20.0RH Dehum. Setpoint

60.0RH

FC Enth Setpoint

23.00BTU/LB FC DB Setpoint

48.00F

5.3.4.1OCCUPIED COOLING SETPOINT

The occupied cooling setpoint requires an authority level of Supervisor or higher to change.

Anyone may view the setpoint value. The Occupied Cooling Setpoint Range is from 72.0 to 80.0 Fo. The default value is 75.0 Fo

5.3.4.2 UNOCCUPIED COOLING SETPOINT

The unoccupied cooling setpoint requires an authority level of Supervisor or higher to change. Anyone may view the setpoint value. The Unoccupied Cooling Setpoint Range is from 72.0 to 85.0 Fo. The default value is 80.0 Fo

2100-444-003A

Page 36

Image 42
Contents Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Additional Requirements Package ContentsShipping Damage Copyright NoticeWallmount Points to be Monitored for Each Unit GeneralBuilding Points to be Monitored Building Points to be ControlledAlarm Points System Points to be ControlledWallmount Points to be Controlled Inputs Environmental Specifications Electrical SpecificationsMechanical Specifications Model NomenclatureHumidity Sensors Sensor SpecificationsTemperature Sensors Indoor and Outdoor Compressor Current SensorBlower Airflow Switch Front Cover Control Location Mounting Template Wiring High Voltage WiringMounting Outdoor Temperature Sensor OTS Wiring LOW VoltageWiring Sensors Zone Temperature Sensor ZTSWiring Inputs & Outputs Wiring Telephone Line Wiring EthernetExternal Wiring Internal Wiring Power Backup System Installation Check List Wallmount Startup Checklist System Startup2 TCS22 Startup Checklist Heating Sequence Sequence of OperationCooling Sequence with Economizers FAN SequenceOccupied / Unoccupied Mode Sequence Alarm SequencePage Thermal Shock Protection Sequence Power Management SequenceDehumidification Sequence Modem SequenceDisplay & Keypad Physicals SetpointsPower Up Menu TreeBuildings Status Screen Unit StatusRoom Humidity Room TemperatureOutdoor Temperature Outdoor HumidityFree Cooling Room Occupied YES/NOOutdoor Enthalpy Unit #1 Compressor Unit Status ScreenUnit #1 Economizer Unit #1 HeaterAlarms Menu Unit #1 Discharge AIR TemperatureUnit #1 Filter Space Temp Alarm Space Humidity Alarm3.4 #1 Compressor Alarm 3.5 #1 Filter AlarmUtility Power Fail Outdoor Humidity Alarm Fire AlarmOutdoor Temp Alarm Door AlarmSetpoints Screen Occupied Cooling Setpoint Unoccupied Cooling SetpointHigh Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint LOW Humidity Alarm SetpointFree Cooling Enthalpy Setpoint Free Cooling DRY Bulb SetpointEnthalpy Lookup Table Overrides Unit #1 Screen5.1 #1 Blower Override 5.2 #1 Economizer Override 5.3 #1 Compressor Override5.4 #1 Heater Override Continuous Blower Enables Menu Free Cooling Enthalpy Changeover DRY Bulb Temperature ChangeoverEconomizer Operation Daylight Savings TimePassword Operation Entering PasswordKeyboard Map UNIT#1 Comp OFF Room RH ClimateWatch System Software Overview InstallationSoftware Installation Hardware RequirementsASI Expert / Bard ClimateWatch Software Screen OverviewMenu Bar Controller Information Area Tool BarStatus Bar Project FoldersSoftware Setup TCS CommunicationsCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page Saving TCS Configuration Loading TCS ConfigurationTCS Controller Information Screens Main Screen TAB ConditionsUnit #1 Status Unit #2 StatusTime & Place SET Point TAB Occupied Cooling SetpointOccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Unoccupied Heating SetpointLow Humidity Alarm SetPoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Enthalpy Changeover SetpointDehumidification Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Active Cooling SetpointStage Indicators Active Dehumidification SetpointOverride #1 TAB Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Unit #1 Blower Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Zone Temperature AlarmOutdoor Humidity Alarm Zone Humidity AlarmOutdoor Temperature Alarm Main Power AlarmFire Trouble Alarm Alarm LOG TAB Offsets TAB Zone Temperature OffsetOutdoor Temperature Offset Zone Humidity OffsetUnit #1 Supply Air Temperature Offset Outdoor Humidity OffsetMISC. TAB Enable Daylight Savings Time Clear Alarm Event LogEnable Economizer Operation Enable 50 hz ClockModel Serial Number Enable Zone DehumidificationModel Number SoftwareTrend TAB Dial OUT TAB Page 2100-444-003A Routine Maintenance Troubleshooting1 TCS22 Troubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Operation Procedure Wallmount Quick Troubleshooting Guide

TCS22-***-003 specifications

The Bard TCS22-***-003 is a cutting-edge technological marvel designed for modern thermal management solutions. This unit is revered in the HVAC industry for its innovative features and energy-efficient operation, making it a popular choice among both commercial and residential users.

One of the main features of the Bard TCS22-***-003 is its advanced climate control capabilities. Equipped with state-of-the-art sensors, the unit provides precise temperature regulation, ensuring optimal comfort in interior spaces. The system's intelligence allows it to adapt to varying weather conditions, maintaining consistent indoor temperatures even during extreme external fluctuations.

The Bard TCS22-***-003 also sports a robust energy efficiency rating, setting it apart from traditional heating and cooling systems. With the integration of variable speed technology, the unit optimizes energy usage by adjusting its output based on the current load. This not only reduces energy consumption but also results in lowered utility bills, promoting sustainability and eco-friendly living.

Another notable characteristic is its whisper-quiet operation. Noise reduction has been a focal point in the design of the TCS22-***-003, allowing it to function below typical sound levels associated with conventional HVAC systems. This is particularly beneficial for residential applications where noise pollution can disrupt daily activities.

The unit is built with durability in mind, featuring a weatherproof construction that can withstand various environmental conditions. Its exterior casing prevents moisture infiltration, while corrosion-resistant materials enhance its longevity. As a result, maintenance needs are minimized, further establishing the Bard TCS22-***-003 as a cost-effective solution in the long run.

In addition, the Bard TCS22-***-003 integrates smart technology, enabling users to control the system remotely using mobile devices or smart home automation systems. This level of convenience allows for personalized heating and cooling settings tailored to individual preferences and schedules.

Overall, the Bard TCS22-***-003 is a standout in the HVAC market due to its blend of efficiency, performance, and user-friendly features. Whether for a home or a commercial establishment, this innovative system offers reliable and sustainable climate control solutions that cater to the needs of today's environmentally conscious consumers.