change. Anyone may view the setpoint value. The dehumidification setpoint range is from 50 to 65 % RH. The default value is 50 % RH.

5.3.4.10FREE COOLING ENTHALPY SETPOINT

The Enthalpy Setpoint is used to determine if the outside air is suitable to use for cooling the structure. The default value for this point is 23.00 BTU/ lb. of dry air. Consult the Enthalpy Lookup Table to adjust this value for the specific conditions that you wish to maintain in the structure. Read down the relative humidity column under the percentage RH you wish to maintain. Read across the inside temperature row to where it intersects the RH column. Enter this value into the Enthalpy Setpoint Display. This will ensure that economizer will never bring in outside air that is too humid.

5.3.4.11FREE COOLING DRY BULB SETPOINT

The Dry Bulb Setpoint is used to determine if the outside air is suitable to use for cooling the structure. The default value for this point is 48 Fo.This will ensure that the economizer will never bring in outside air that is to warm to provide cooling.

2100-444-003A

Page 38

Image 44 Contents
Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Package Contents Shipping DamageAdditional Requirements Copyright NoticeGeneral Building Points to be MonitoredWallmount Points to be Monitored for Each Unit Building Points to be ControlledWallmount Points to be Controlled Alarm PointsSystem Points to be Controlled Inputs Electrical Specifications Mechanical SpecificationsEnvironmental Specifications Model NomenclatureSensor Specifications Temperature Sensors Indoor and OutdoorHumidity Sensors Compressor Current SensorBlower Airflow Switch Front Cover Control Location Mounting Template Mounting WiringHigh Voltage Wiring Wiring LOW Voltage Wiring SensorsOutdoor Temperature Sensor OTS Zone Temperature Sensor ZTSWiring Inputs & Outputs Wiring Telephone Line Wiring EthernetExternal Wiring Internal Wiring Power Backup System Installation Check List Wallmount Startup Checklist System Startup2 TCS22 Startup Checklist Sequence of Operation Cooling Sequence with EconomizersHeating Sequence FAN SequenceOccupied / Unoccupied Mode Sequence Alarm SequencePage Power Management Sequence Dehumidification SequenceThermal Shock Protection Sequence Modem SequenceDisplay & Keypad Physicals SetpointsPower Up Menu TreeBuildings Status Screen Unit StatusRoom Temperature Outdoor TemperatureRoom Humidity Outdoor HumidityOutdoor Enthalpy Free CoolingRoom Occupied YES/NO Unit Status Screen Unit #1 EconomizerUnit #1 Compressor Unit #1 HeaterUnit #1 Filter Alarms MenuUnit #1 Discharge AIR Temperature Space Temp Alarm Space Humidity AlarmUtility Power Fail 3.4 #1 Compressor Alarm3.5 #1 Filter Alarm Fire Alarm Outdoor Temp Alarm Outdoor Humidity Alarm Door AlarmSetpoints Screen Occupied Cooling Setpoint Unoccupied Cooling SetpointHigh Temperature Alarm Setpoint LOW Temperature Alarm SetpointHigh Humidity Alarm Setpoint LOW Humidity Alarm SetpointFree Cooling Enthalpy Setpoint Free Cooling DRY Bulb SetpointEnthalpy Lookup Table Overrides Unit #1 Screen5.1 #1 Blower Override 5.4 #1 Heater Override 5.2 #1 Economizer Override5.3 #1 Compressor Override Continuous Blower Enables Menu DRY Bulb Temperature Changeover Economizer OperationFree Cooling Enthalpy Changeover Daylight Savings TimePassword Operation Entering PasswordKeyboard Map UNIT#1 Comp OFF Room RH Installation Software InstallationClimateWatch System Software Overview Hardware RequirementsMenu Bar ASI Expert / Bard ClimateWatch SoftwareScreen Overview Tool Bar Status BarController Information Area Project FoldersSoftware Setup TCS CommunicationsCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page TCS Controller Information Screens Saving TCS ConfigurationLoading TCS Configuration Main Screen TAB ConditionsTime & Place Unit #1 StatusUnit #2 Status SET Point TAB Occupied Cooling SetpointHigh Temperature Alarm SetPoint Unoccupied Cooling SetpointOccupied Heating Setpoint Unoccupied Heating SetpointLow Temperature Alarm SetPoint High Humidity Alarm SetPointLow Humidity Alarm SetPoint Enthalpy Changeover SetpointContinuous Blower Enable Dry Bulb Changeover SetpointDehumidification Setpoint Active Cooling SetpointOverride #1 TAB Stage IndicatorsActive Dehumidification Setpoint Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Unit #1 Filter Alarm Unit #1 Compressor AlarmUnit #1 Blower Alarm Zone Temperature AlarmZone Humidity Alarm Outdoor Temperature AlarmOutdoor Humidity Alarm Main Power AlarmFire Trouble Alarm Alarm LOG TAB Zone Temperature Offset Outdoor Temperature OffsetOffsets TAB Zone Humidity OffsetMISC. TAB Unit #1 Supply Air Temperature OffsetOutdoor Humidity Offset Clear Alarm Event Log Enable Economizer OperationEnable Daylight Savings Time Enable 50 hz ClockEnable Zone Dehumidification Model NumberModel Serial Number SoftwareTrend TAB Dial OUT TAB Page 2100-444-003A 1 TCS22 Troubleshooting Routine MaintenanceTroubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Operation Procedure Wallmount Quick Troubleshooting Guide