4.2.10 SETPOINTS

The default setpoint for all points are listed below. All setpoints are user changeable within the ranges listed.

Occupied Heating Setpoint

Default

70.0 Fo

Range

 

60.0 - 70.0 Fo

Unoccupied Heating Setpoint

Default

68.0

Fo

Range

55.0

- 70.0 Fo

Occupied Cooling Setpoint

Default

75.0

Fo

Range

72.0

- 80.0 Fo

Unoccupied Cooling Setpoint

Default

80.0

Fo

Range

72.0

- 85.0 Fo

High Temperature Alarm Setpoint

Default

90.0

Fo

Range

80.0

- 100.0 Fo

Low Temperature Alarm Setpoint

Default

56.0

Fo

Range

45.0

- 67.0 Fo

High Humidity Alarm Setpoint

Default

60 % RH

Range

55 % - 85 %

RH

 

 

 

 

 

 

Low Humidity Alarm Setpoint

Default

20 % RH

Range

5 % - 35 %

RH

 

 

 

 

 

 

Changeover Hours

Default

24 Hrs

 

Range

24 - 168 Hrs

Enthalpy / Free Cooling Setpoint

Default

23.0 Btu/lb

Range

5.00

– 40.00

Btu/lb

 

 

 

 

 

 

Drybulb / Free Cooling Setpoint

Default

48.0

Fo

Range

40.0

- 80.0 Fo

Dehumidification Setpoint

Default

50 % RH

Range

50 % - 70 %

RH

 

 

 

 

 

 

Dehumidification Heating Setpoint

Default

70.0

Fo

Range

Fixed, Not

adjustable

 

 

 

 

 

 

Dehumidification Cooling Setpoint

Default

73.0

Fo

Range

Fixed, Not

adjustable

 

 

 

 

 

 

5.0DISPLAY & KEYPAD OPERATION (DAK)

The display and keypad (DAK) is used to monitor and change parameters in the controller. If DAK is needed it must be ordered as part of the TCS22. It cannot be ordered separately at a later date.

5.1Display & Keypad Physicals

The display and keypad (DAK) consists of a 4 line by 20 character backlit LCD display, 13 key keypad and 5 indicating LEDs.

All messages displayed on the DAK are uploaded from the 7040 controller at power up. The LCD display uses a simple page menu system to display all functions.

The keypad consists of keys labeled <F1 >, <F2>, <F3>, <F4>, <//>, <Left>, <Up>, <Down>, <Right>,and <Enter>. The specific function of these keys is preprogrammed and not user configurable.

The <?>, <>, and <I> keys are not programmed and serve no function in this application..

In general the keys have the following functions. The <Up>, <Left>, <Down>, <Right> keys are used to navigate through the 7 screens, increment or decrement values, and choose which digit or letter to change. The <Enter > Key is used to select a choice or accept the changes. The < F1 > key is used to enter change mode to change setpoints, passwords, or lead/ lag units. The function of each of the keys depends on were you are in the menu tree. The <F2> key is used to enter passwords. The <//> key

2100-444-003A

Page 25

Image 31
Contents Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Copyright Notice Package ContentsShipping Damage Additional RequirementsBuilding Points to be Controlled GeneralBuilding Points to be Monitored Wallmount Points to be Monitored for Each UnitSystem Points to be Controlled Alarm PointsWallmount Points to be Controlled Inputs Model Nomenclature Electrical SpecificationsMechanical Specifications Environmental SpecificationsCompressor Current Sensor Sensor SpecificationsTemperature Sensors Indoor and Outdoor Humidity SensorsBlower Airflow Switch Front Cover Control Location Mounting Template High Voltage Wiring WiringMounting Zone Temperature Sensor ZTS Wiring LOW VoltageWiring Sensors Outdoor Temperature Sensor OTSWiring Inputs & Outputs Wiring Ethernet Wiring Telephone LineExternal Wiring Internal Wiring Power Backup System Installation Check List System Startup Wallmount Startup Checklist2 TCS22 Startup Checklist FAN Sequence Sequence of OperationCooling Sequence with Economizers Heating SequenceAlarm Sequence Occupied / Unoccupied Mode SequencePage Modem Sequence Power Management SequenceDehumidification Sequence Thermal Shock Protection SequenceSetpoints Display & Keypad PhysicalsMenu Tree Power UpUnit Status Buildings Status ScreenOutdoor Humidity Room TemperatureOutdoor Temperature Room HumidityRoom Occupied YES/NO Free CoolingOutdoor Enthalpy Unit #1 Heater Unit Status ScreenUnit #1 Economizer Unit #1 CompressorUnit #1 Discharge AIR Temperature Alarms MenuUnit #1 Filter Space Humidity Alarm Space Temp Alarm3.5 #1 Filter Alarm 3.4 #1 Compressor AlarmUtility Power Fail Door Alarm Fire AlarmOutdoor Temp Alarm Outdoor Humidity AlarmSetpoints Screen Unoccupied Cooling Setpoint Occupied Cooling SetpointLOW Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint High Humidity Alarm SetpointFree Cooling DRY Bulb Setpoint Free Cooling Enthalpy SetpointOverrides Unit #1 Screen Enthalpy Lookup Table5.1 #1 Blower Override 5.3 #1 Compressor Override 5.2 #1 Economizer Override5.4 #1 Heater Override Continuous Blower Enables Menu Daylight Savings Time DRY Bulb Temperature ChangeoverEconomizer Operation Free Cooling Enthalpy ChangeoverEntering Password Password OperationKeyboard Map UNIT#1 Comp OFF Room RH Hardware Requirements InstallationSoftware Installation ClimateWatch System Software OverviewScreen Overview ASI Expert / Bard ClimateWatch SoftwareMenu Bar Project Folders Tool BarStatus Bar Controller Information AreaTCS Communications Software SetupCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page Loading TCS Configuration Saving TCS ConfigurationTCS Controller Information Screens Conditions Main Screen TABUnit #2 Status Unit #1 StatusTime & Place Occupied Cooling Setpoint SET Point TABUnoccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Occupied Heating SetpointEnthalpy Changeover Setpoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Low Humidity Alarm SetPointActive Cooling Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Dehumidification SetpointActive Dehumidification Setpoint Stage IndicatorsOverride #1 TAB Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Zone Temperature Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Unit #1 Blower AlarmMain Power Alarm Zone Humidity AlarmOutdoor Temperature Alarm Outdoor Humidity AlarmFire Trouble Alarm Alarm LOG TAB Zone Humidity Offset Zone Temperature OffsetOutdoor Temperature Offset Offsets TABOutdoor Humidity Offset Unit #1 Supply Air Temperature OffsetMISC. TAB Enable 50 hz Clock Clear Alarm Event LogEnable Economizer Operation Enable Daylight Savings TimeSoftware Enable Zone DehumidificationModel Number Model Serial NumberTrend TAB Dial OUT TAB Page 2100-444-003A Troubleshooting Routine Maintenance1 TCS22 Troubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Wallmount Quick Troubleshooting Guide Operation Procedure

TCS22-***-003 specifications

The Bard TCS22-***-003 is a cutting-edge technological marvel designed for modern thermal management solutions. This unit is revered in the HVAC industry for its innovative features and energy-efficient operation, making it a popular choice among both commercial and residential users.

One of the main features of the Bard TCS22-***-003 is its advanced climate control capabilities. Equipped with state-of-the-art sensors, the unit provides precise temperature regulation, ensuring optimal comfort in interior spaces. The system's intelligence allows it to adapt to varying weather conditions, maintaining consistent indoor temperatures even during extreme external fluctuations.

The Bard TCS22-***-003 also sports a robust energy efficiency rating, setting it apart from traditional heating and cooling systems. With the integration of variable speed technology, the unit optimizes energy usage by adjusting its output based on the current load. This not only reduces energy consumption but also results in lowered utility bills, promoting sustainability and eco-friendly living.

Another notable characteristic is its whisper-quiet operation. Noise reduction has been a focal point in the design of the TCS22-***-003, allowing it to function below typical sound levels associated with conventional HVAC systems. This is particularly beneficial for residential applications where noise pollution can disrupt daily activities.

The unit is built with durability in mind, featuring a weatherproof construction that can withstand various environmental conditions. Its exterior casing prevents moisture infiltration, while corrosion-resistant materials enhance its longevity. As a result, maintenance needs are minimized, further establishing the Bard TCS22-***-003 as a cost-effective solution in the long run.

In addition, the Bard TCS22-***-003 integrates smart technology, enabling users to control the system remotely using mobile devices or smart home automation systems. This level of convenience allows for personalized heating and cooling settings tailored to individual preferences and schedules.

Overall, the Bard TCS22-***-003 is a standout in the HVAC market due to its blend of efficiency, performance, and user-friendly features. Whether for a home or a commercial establishment, this innovative system offers reliable and sustainable climate control solutions that cater to the needs of today's environmentally conscious consumers.