Bard TCS22-***-003 manual Free Cooling, Room Occupied YES/NO, Outdoor Enthalpy

Page 35

Setpoint will be 70o the same as the fixed Dehumidification Heating Setpoint.

5.3.1.7 FREE COOLING

ON / OFF

This display item indicates whether outside conditions are suitable to allow the use of outside air to provide free cooling inside the structure. The controller calculates the either outside temperature or enthalpy from the Outdoor Temperature and Outdoor Humidity and compares this value with the Free Cooling Setpoint. The Free cooling setpoint can be either a dry bulb temperature or enthalpy. This is user selectable. If outdoor temperature or enthalpy, whichever the user has selected, is less than the Free cooling setpoint then Free Cooling is ON. If the temperature or enthalpy of the outside air is more than the Free Cooling Setpoint then Free Cooling is Off.

5.3.1.8 ROOM OCCUPIED YES/NO

This display indicates the status of the After-hours Occupancy Override Button. If the display shows "NO", the controller is in the unoccupied mode and the unoccupied setpoints prevail. If the display shows "YES", the controller is in the occupied mode and the occupied setpoints prevail. Depressing the Occupancy Override Switch on the Zone Temperature Sensor for one second triggers the Occupied mode for two (2) hours.

5.3.1.9 OUTDOOR ENTHALPY

This outdoor enthalpy displays the calculated outdoor air enthalpy. The outdoor enthalpy is calculated from the outdoor temperature and outdoor humidity sensors and is used to determine wether the air is suitable for free cooling or not.

2100-444-003A

Page 29

Image 35 Contents
Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Copyright Notice Package ContentsShipping Damage Additional RequirementsBuilding Points to be Controlled GeneralBuilding Points to be Monitored Wallmount Points to be Monitored for Each UnitWallmount Points to be Controlled Alarm PointsSystem Points to be Controlled Inputs Model Nomenclature Electrical SpecificationsMechanical Specifications Environmental SpecificationsCompressor Current Sensor Sensor SpecificationsTemperature Sensors Indoor and Outdoor Humidity SensorsBlower Airflow Switch Front Cover Control Location Mounting Template Mounting WiringHigh Voltage Wiring Zone Temperature Sensor ZTS Wiring LOW VoltageWiring Sensors Outdoor Temperature Sensor OTSWiring Inputs & Outputs Wiring Ethernet Wiring Telephone LineExternal Wiring Internal Wiring Power Backup System Installation Check List System Startup Wallmount Startup Checklist2 TCS22 Startup Checklist FAN Sequence Sequence of OperationCooling Sequence with Economizers Heating SequenceAlarm Sequence Occupied / Unoccupied Mode SequencePage Modem Sequence Power Management SequenceDehumidification Sequence Thermal Shock Protection Sequence Setpoints Display & Keypad PhysicalsMenu Tree Power UpUnit Status Buildings Status ScreenOutdoor Humidity Room TemperatureOutdoor Temperature Room HumidityOutdoor Enthalpy Free CoolingRoom Occupied YES/NO Unit #1 Heater Unit Status ScreenUnit #1 Economizer Unit #1 CompressorUnit #1 Filter Alarms MenuUnit #1 Discharge AIR Temperature Space Humidity Alarm Space Temp AlarmUtility Power Fail 3.4 #1 Compressor Alarm3.5 #1 Filter Alarm Door Alarm Fire AlarmOutdoor Temp Alarm Outdoor Humidity AlarmSetpoints Screen Unoccupied Cooling Setpoint Occupied Cooling SetpointLOW Humidity Alarm Setpoint High Temperature Alarm SetpointLOW Temperature Alarm Setpoint High Humidity Alarm SetpointFree Cooling DRY Bulb Setpoint Free Cooling Enthalpy SetpointOverrides Unit #1 Screen Enthalpy Lookup Table5.1 #1 Blower Override 5.4 #1 Heater Override 5.2 #1 Economizer Override5.3 #1 Compressor Override Continuous Blower Enables Menu Daylight Savings Time DRY Bulb Temperature ChangeoverEconomizer Operation Free Cooling Enthalpy ChangeoverEntering Password Password OperationKeyboard Map UNIT#1 Comp OFF Room RH Hardware Requirements InstallationSoftware Installation ClimateWatch System Software OverviewMenu Bar ASI Expert / Bard ClimateWatch SoftwareScreen Overview Project Folders Tool BarStatus Bar Controller Information AreaTCS Communications Software SetupCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page TCS Controller Information Screens Saving TCS ConfigurationLoading TCS Configuration Conditions Main Screen TABTime & Place Unit #1 StatusUnit #2 Status Occupied Cooling Setpoint SET Point TABUnoccupied Heating Setpoint High Temperature Alarm SetPointUnoccupied Cooling Setpoint Occupied Heating SetpointEnthalpy Changeover Setpoint Low Temperature Alarm SetPointHigh Humidity Alarm SetPoint Low Humidity Alarm SetPointActive Cooling Setpoint Continuous Blower EnableDry Bulb Changeover Setpoint Dehumidification SetpointOverride #1 TAB Stage IndicatorsActive Dehumidification Setpoint Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Zone Temperature Alarm Unit #1 Filter AlarmUnit #1 Compressor Alarm Unit #1 Blower AlarmMain Power Alarm Zone Humidity AlarmOutdoor Temperature Alarm Outdoor Humidity AlarmFire Trouble Alarm Alarm LOG TAB Zone Humidity Offset Zone Temperature OffsetOutdoor Temperature Offset Offsets TABMISC. TAB Unit #1 Supply Air Temperature OffsetOutdoor Humidity Offset Enable 50 hz Clock Clear Alarm Event LogEnable Economizer Operation Enable Daylight Savings TimeSoftware Enable Zone DehumidificationModel Number Model Serial NumberTrend TAB Dial OUT TAB Page 2100-444-003A 1 TCS22 Troubleshooting Routine MaintenanceTroubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Wallmount Quick Troubleshooting Guide Operation Procedure