5.3.2 Unit Status Screen
Authority Level Required to Make Changes - Does not apply. No changes can be made from this
screen.
The Unit Status screen displays the following information about both
Unit #1 Economizer | On/Off |
Unit #1 Compressor | On/Off |
Unit #1 Heater | On/Off |
Unit #1 Blower | On/Off |
Unit #1 Filter | Clean/Dirty |
Unit #1 Discharge Air Temperature | Value DegF |
UNIT STATUS
UNIT#1 ECON. | OFF |
UNIT#1 COMP. | OFF |
UNIT#1 HEAT | ON |
UNIT#1 BLOWER | OFF |
UNIT#1FILTER | CLEAN |
U#1 SUPPLY AIR | 90.24 |
Pressing the <Up> or <Down> key will scroll up or down respectively through the above screen showing four lines at a time.
5.3.2.1 UNIT #1 ECONOMIZER
This display item will show "Off" if the unit #1 economizer output of the controller is not energized. This display item will show "On" if the unit #1 economizer output of the controller is energized.
5.3.2.2 UNIT #1 COMPRESSOR
This display item will show "Off" if the unit #1 compressor output of the controller is not energized. This display item will show "On" if the unit #1 compressor output of the controller is energized.
5.3.2.3 UNIT #1 HEATER
This display item will show "Off" if the unit #1 heater output of the controller is not energized. This display item will show "On" if the unit #1 heater output of the controller is energized.
5.3.2.4 UNIT #1 BLOWER
This display item will show "Off" if the unit #1 blower output of the controller is not energized. This display item will show "On" if the unit #1 blower output of the controller is energized.
Page 30