Bard TCS22-***-003 manual Alarms TAB

Page 76

6.4.4 ALARMS TAB

The Alarms Tab will switch to the screen containing the Alarm information from the Controller. The Alarm screen will allow the user to check the alarm status of the Zone Temperature, Zone Humidity, Outdoor Temperature, Outdoor Humidity, Main Power, Door Alarm, Fire Alarm and Fire Trouble.

Blower, Compressor, and Filter alarms of the conditioning units can also be monitored.

Several alarms can be enabled or disabled by checking the alarm enable check box. Do not disable an alarm that is in alarm. Doing so will lock the alarm on and it will not be able to be cleared or acknowledged until the alarm is re-enabled.

All alarms can be acknowledged. Acknowledging an alarm resets the shelter alarm output to normally open so that any new alarm will re-close the output and signify a new alarm. Most alarms are self-clearing alarms. Once the condition that caused the alarm is corrected or goes away the alarm resets.

The compressor and blower alarms are not self clearing alarms and must be manually cleared from the Override screen . These are the verify alarms.

An alarm can also be used to initiate a dial-out alarm call to a pager or printer. Clicking the Dial- out enable check box enables dial-out alarms. The dial-out phone numbers are maintained under the Dial Out tab.

2100-444-003A

Page 70

Image 76 Contents
Operations Manual Table Of Contents Operation Unit Status Screen PC Software Operation Table of Figures and Tables Package Contents Shipping DamageAdditional Requirements Copyright NoticeGeneral Building Points to be MonitoredWallmount Points to be Monitored for Each Unit Building Points to be ControlledSystem Points to be Controlled Alarm PointsWallmount Points to be Controlled Inputs Electrical Specifications Mechanical SpecificationsEnvironmental Specifications Model NomenclatureSensor Specifications Temperature Sensors Indoor and OutdoorHumidity Sensors Compressor Current SensorBlower Airflow Switch Front Cover Control Location Mounting Template High Voltage Wiring WiringMounting Wiring LOW Voltage Wiring SensorsOutdoor Temperature Sensor OTS Zone Temperature Sensor ZTSWiring Inputs & Outputs Wiring Telephone Line Wiring EthernetExternal Wiring Internal Wiring Power Backup System Installation Check List Wallmount Startup Checklist System Startup2 TCS22 Startup Checklist Sequence of Operation Cooling Sequence with EconomizersHeating Sequence FAN SequenceOccupied / Unoccupied Mode Sequence Alarm SequencePage Power Management Sequence Dehumidification SequenceThermal Shock Protection Sequence Modem SequenceDisplay & Keypad Physicals SetpointsPower Up Menu TreeBuildings Status Screen Unit StatusRoom Temperature Outdoor TemperatureRoom Humidity Outdoor HumidityRoom Occupied YES/NO Free CoolingOutdoor Enthalpy Unit Status Screen Unit #1 EconomizerUnit #1 Compressor Unit #1 HeaterUnit #1 Discharge AIR Temperature Alarms MenuUnit #1 Filter Space Temp Alarm Space Humidity Alarm3.5 #1 Filter Alarm 3.4 #1 Compressor AlarmUtility Power Fail Fire Alarm Outdoor Temp AlarmOutdoor Humidity Alarm Door AlarmSetpoints Screen Occupied Cooling Setpoint Unoccupied Cooling SetpointHigh Temperature Alarm Setpoint LOW Temperature Alarm SetpointHigh Humidity Alarm Setpoint LOW Humidity Alarm SetpointFree Cooling Enthalpy Setpoint Free Cooling DRY Bulb SetpointEnthalpy Lookup Table Overrides Unit #1 Screen5.1 #1 Blower Override 5.3 #1 Compressor Override 5.2 #1 Economizer Override5.4 #1 Heater Override Continuous Blower Enables Menu DRY Bulb Temperature Changeover Economizer OperationFree Cooling Enthalpy Changeover Daylight Savings TimePassword Operation Entering PasswordKeyboard Map UNIT#1 Comp OFF Room RH Installation Software InstallationClimateWatch System Software Overview Hardware RequirementsScreen Overview ASI Expert / Bard ClimateWatch SoftwareMenu Bar Tool Bar Status BarController Information Area Project FoldersSoftware Setup TCS CommunicationsCreating a New Project & Establishing Communications Direct Connection Remote Connection Page Downloading Controller Information Page Page Loading TCS Configuration Saving TCS ConfigurationTCS Controller Information Screens Main Screen TAB ConditionsUnit #2 Status Unit #1 StatusTime & Place SET Point TAB Occupied Cooling SetpointHigh Temperature Alarm SetPoint Unoccupied Cooling SetpointOccupied Heating Setpoint Unoccupied Heating SetpointLow Temperature Alarm SetPoint High Humidity Alarm SetPointLow Humidity Alarm SetPoint Enthalpy Changeover SetpointContinuous Blower Enable Dry Bulb Changeover SetpointDehumidification Setpoint Active Cooling Setpoint Active Dehumidification Setpoint Stage Indicators Override #1 TAB Page Unit #1 Compressor Unit #1 Economizer Alarms TAB Unit #1 Filter Alarm Unit #1 Compressor AlarmUnit #1 Blower Alarm Zone Temperature AlarmZone Humidity Alarm Outdoor Temperature AlarmOutdoor Humidity Alarm Main Power AlarmFire Trouble Alarm Alarm LOG TAB Zone Temperature Offset Outdoor Temperature OffsetOffsets TAB Zone Humidity OffsetOutdoor Humidity Offset Unit #1 Supply Air Temperature OffsetMISC. TAB Clear Alarm Event Log Enable Economizer OperationEnable Daylight Savings Time Enable 50 hz ClockEnable Zone Dehumidification Model NumberModel Serial Number SoftwareTrend TAB Dial OUT TAB Page 2100-444-003A Troubleshooting Routine Maintenance1 TCS22 Troubleshooting To F on the terminal strip on controller Will correspond with the Humidity Page Humidity Sensor Output Thermistor Resistance Vs. Temperature Table Operation Procedure Wallmount Quick Troubleshooting Guide