ADC AD-410 service manual If the Opposite Side is not LEVEL, the Dryer will not Tilt

Page 87

3)24 VAC Transformer

The 24 VAC transformer consists of fuse 1 (F1) and fuse 2 (F2) which is the primary fusing for the transformer. For the proper rating of these fuses refer to the specific electric diagram. The transformer is located in the right hand electrical cabinet.

Dryer models with an optional Sprinkler System have an energizing stop relay which will disable the dryer functions (shut the dryer down) in the event of a fire. IF THE SPRINKLER SYSTEM IS NOT ENERGIZED (POWERED) THE DRYER WILL NOT OPERATE. The Energizing Stop Push Button is located on the front right electrical panel. On 2-Door models this Energizing Stop Push Button is located on the right rear side of the electrical panel (when viewed from the rear).

On dryer models manufactured for 208 volt or 240 volt electric service, the step down voltage for the Phase 5 microprocessor controller (computer) and the Programmable Logic Controller (PLC) is supplied from the primary side of the 24 VAC transformer. On dryers that are manufactured for 380 volts and higher, there is an additional secondary 240 VAC on the transformer that is used to supply the voltage required to operate the Phase 5 microprocessor controller (computer) and the Programmable Logic Controller (PLC) through fuse 4 (F4), (and fuse 5 [F5] for low voltage applications).

4)24 VAC Control Circuit

The secondary side of the 24 VAC transformer supplies 24 VAC to various control circuits through fuse 3 (F3) and a 20-amp fuse or an 8-amp fuse (fuse amperage [rating] is dependent on the voltage that the dryer was manufactured with).

The first circuit is the control voltage on/off. Control voltage ( 24 VAC) goes through the "Master Off" (normally closed) switch and supplies voltage to the "Master On" (normally open) switch. When the "Master On" switch is momentarily engaged, the master control relay (MCR) engages. This closes the MCR-A contactor (which is in parallel with the "Master On" switch) which will keep the MCR enabled. If the power is interrupted or the "Master Off" switch is pressed the MCR will disengage. The MCR-B contactor supplies power to the rest of the 24 VAC circuits.

For dryers manufactured with Automatic Doors - the purpose of the supply air is to relieve pressure

on the automatic door pistons when an emergency stop is engaged.

5)Safety Circuits

The following circuit branches are to verify various safeties, if ALL conditions are met ...

a)The first two (2) items are the Auxiliary Contact located on the blower (squirrel cage fan) motor and the Tumbler (basket) Motor Overload. If either of these devices trip, it will open up the safety circuit thereby preventing the dryer from operating.

b)Dryer Level Switches circuit branch ...

(1)On 1-way tilt models, this switch is in series with the dry enable.

(2)On 2-way tilt models ...one (1) pole of each of the two (2) level switches (LS1-A and LS2-A) are in series with the dryer level relay and the other pole is in series with the opposite piston.

IF THE OPPOSITE SIDE IS NOT LEVEL, THE DRYER WILL NOT TILT.

8 3

Image 87
Contents American Dryer Corporation Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Troubleshooting AD-410 Reference Guide Base Section AD-410 Machine Operational Summary AD-410 Operator CONTROLS/INDICATORSControl Power On END of Cycle / Heater Fault Indicator / AIR JET AIR JET AD-410 Machine Operation Troubleshooting InformationLoad Tilted Unload TiltedDRY GAS Pressure If Both AIR Flow Switches are not Open AT this TimeImportant Information System Ladder Diagram ONE 1 Burner will not Ignite AT the Beginning of a CycleONE 1 Burner will not Ignite During a Drying Cycle Optional Sprinkler Control Signals Solenoid ControlLint Drawer / Guard Status Page What to do if YOU Smell GAS Explosion could ResultNational Electric Code ANSI/NFPA no -LATEST Edition StandardsCleaning Suggested Cleaning ScheduleLiquids Monthly Lubrication Days After Installation and Every 6 Months Thereafter AdjustmentsGas Dimensions AD-410 with Inlet AIR Adapter Enclosure / AIR Supply / Exhaust Requirements Installation RequirementsElectrical Requirements and GAS Requirements Operational Service Check ProcedureDirect Spart Ignition DSI System COMPONENTS/FUNCTIONS Heat Section24 VAC Direct Spark Ignition DSI Module Repairable ADC Direct Spark Ignition DSI Operation Flow Chart Manometer Troubleshooting the Direct Spark Ignition DSI SystemMAN0677 Page If not, refer to the Second Visual Check on First Visual Check Second Visual Check Third Visual Check Are no Retries Leaks with a Flame Continuously Page Page Create a Potential Safety Hazard Page General Overview Steam Coil System OperationPage Page Page Page Sprinkler System Description Require any adjustment Page Page Supplies Before Servicing the Dryer MAN3169 Tilting System Description Page Tilting Pistons Page Page Page Page AIR JET Assembly Page Blower Squirrel Cage Fan Motor Assembly Leave enough movement for V-belt adjustment Page Important do not Overtighten V-BELTS Important do not Overtighten V-BELTS Page Page Filter and Regulator Assembly Door Systems Page Page Page Page Allow a full 72 hours for the silicone to cure Page Control and Electrical System Page Button does not Disable the High Voltage to the Dryer If the Opposite Side is not LEVEL, the Dryer will not Tilt ºC + Page Page Page Page Page Page MAN3405 Page Page Page Tumbler Basket System Important do not Over Tighten Turnbuckle Install new V-belts Tighten turnbuckle For Gear Reducer removal refer to Section d on page 99 Page Do not tighten 101 102 103 Troubleshooting Drive motor is not operating does not start Impellor fan motor is not operating does not start 107 108 Dryer operates but is taking too long to dry Excessive noise and vibration Dryer will not level from a tilt position Procedure for Functional Check Replacement Components 113 ADC450414 1- 05/27/99-25