Chapter 13—Meter resets

PowerLogic™ PM5300 series user guide

 

 

5. Press Yes to confirm the reset or No to cancel and return to the previous screen.

Single resets

Single resets allow you to clear data only in a specific register or register type.

1.Navigate to Maint > Reset.

2.Move the cursor to point to Single Reset, then press Select.

3.Move the cursor to point to the parameter you want to reset, then press Reset. If there are additional options for the parameter, press Select, move the cursor to point to the option you want, then press Reset.

Single reset options

Parameter

 

Option

Description

 

 

 

 

Energy

Accumulated

 

Clears all accumulated energy values (kWh,

 

kVARh, kVAh).

 

 

 

 

 

 

Select which demand registers to clear

Demand

Power, Current

(power demand, current demand or input

 

 

 

metering demand).

 

Event Queue

 

Clears the alarm event queue register.

 

 

 

 

 

History Log

 

Clears the alarm history log.

 

 

 

 

Alarms

 

All Alarm Counts,

Select “Counters”, then select which counter

 

Counters

(various alarm

to clear (choose all or individual alarm

 

counters) — see the

counters listed in the “Alarm counter options”

 

 

 

 

next table

table below).

 

 

 

 

 

 

All Dig In Timers,

Select “Timers”, then select which status

 

Timers

Status Input S1,

input timer to clear (choose all or individual

Status Inputs

 

Status Input S2

status input timers).

 

All Dig In Counters,

Select “Timers”, then select which status

 

 

 

Counters

Status Input S1,

input counter to clear (choose all or individual

 

 

Status Input S2

status input counters).

 

 

All Dig Out Timers,

 

 

Timers

Digital Output D1,

Select “Timers”, then select which digital

 

Digital Output D2,

output timer to clear (choose all or individual

 

 

Relay R1,

digital output timers).

Digital Outputs

 

Relay R2

 

 

All Dig Out Counters,

 

 

 

 

 

 

Digital Output D1,

Select “Timers”, then select which digital

 

Counters

Digital Output D2,

output counter to clear (choose all or

 

 

Relay R1,

individual digital output counters).

 

 

Relay R2

 

Active Load Timer

 

 

Clears and restarts the load operation timer.

 

 

 

 

Multi-Tariff

 

 

Clears accumulated values in all tariff

 

 

register.

 

 

 

4.Enter the reset password if prompted (default is “0000”), then press OK.

5.Press Yes to confirm the reset or No to cancel and return to the previous screen.

Alarm counter options

Alarm counter

Option

Description

 

 

 

 

Over Current, Ph

 

 

 

 

Current

Under Current, Ph

Select which alarm counter register to reset from

Over Current, N

the current alarm condition counters.

 

 

 

 

 

Over Current, Gnd

 

 

 

 

 

Over Voltage, L-L

 

 

 

 

 

Under Voltage, L-L

 

 

 

 

 

Over Voltage, L-N

Select which alarm counter register to reset from

 

 

Voltage

Under Voltage, L-N

the voltage alarm condition counters.

 

 

 

Over Voltage Unbal

 

 

 

 

 

Over Voltage THD

 

 

 

 

 

Phase Loss

 

 

 

 

100

© 2014 Schneider Electric All Rights Reserved

Image 100
Contents PowerLogic PM5300 Series Power and Energy Meter Page Important Information Please notePage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Alarms Chapter Multi-tariff featureChapter Power quality Chapter Input / OutputChapter Meter resets Chapter MaintenanceUpgrades Chapter Verifying accuraPowerLogic PM5300 series user guide Power and Energy Meter Hardware Parts and AccessoriesBox Contents IntroductionPowerLogic PM5300 user guide Safety Precautions Before You BeginPowerLogic PM5300 series user guide Models, Features and Options Functions and CharacteristicsPM5300 Series Models, Features and Options Functions and CharacteristicsPower Quality Measurements Energy ValuesDemand Values Other MeasurementsTechnical Specifications Electrical CharacteristicsMechanical Characteristics Environmental CharacteristicsSafety Electromagnetic CompatibilityDimension Safety precautionsHuman Machine Interface Meter mounting Mounting the PM5300Meter wiring Serial No Description Specification Screw driver type M3Recommended cables Make Part code DescriptionWiring Diagrams Power system Symbol DescriptionCurrent Transformer Voltage disconnect switch Direct connect voltage limitsMeter setting Power system setup parameters Power system descriptionSymbol Voltage and current input wiring Voltage input protectionCurrent input protection Direct connect maximumControl power wiring CommunicationsBalanced system considerations Serial communicationsRS-485 wiring RS-485 network configurationRS-485 cable RS-485 maximum cable lengthEthernet configuration Ethernet wiring EthernetETHERNET SwitchSWITCH/ hub/ HUBDigital outputs Ethernet communicationsStatus inputs Relay outputsDigital output connections Status input connectionsRelay output connections Front panel display and meter setup LED indicatorsAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics Menu tree PM5300 display screen menusFront panel meter setup Meter setup screen navigationConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Communications setup Setting up serial communicationsSerial communications setup menu tree Communication portsCommunications setup parameters Setting up Ethernet communicationsEthernet communications setup menu tree HMI settings Setting up the displayEthernet port settings Display setup menu treeSetting up the screen passwords Setting up regional settingsDisplay setup parameters Regional settings menu treePassword setup menu tree Lost passwordPassword setup parameters Setting the clock Advanced setup Clock setup menu treeClock setup parameters Advanced setup menu treeSetting up the alarm / energy pulsing LED Advanced setup parametersAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Input / output setup Demand setupPower or current demand setup parameters Alarms setup Multi-tariff setupRemote Meter Setup Viewing Meter Data Viewing meter data from the front panelMeter data display screens Displaying data screensPower PQS Volts U-VHarm Energy EAlarm Hz FUnbal MnMxUsing ION Setup to view or modify configuration data Using software to view meter dataTimer MaintStatus input applications Input / OutputStatus Input, Digital Output Ports and Relay Output Ports Status input setup Configuring status inputs using ION SetupNavigate to I/O configuration I/O Setup Status input setup parameters available through ION SetupConfiguring status inputs using the front panel Status input setup menu treeDigital output setup Digital output wiring exampleDigital output applications Digital output application exampleConfiguring digital outputs using ION Setup Digital output setup parameters available through ION SetupConfiguring digital outputs using the front panel Digital output setup menu treeOn Time s This defines the pulse width on time in seconds Parameter Values Description Relay output setup Configuring relay outputs using ION SetupRelay output setup parameters available through ION Setup Relay output applicationsSet to External or Alarm. The relay output Configuring relay outputs using the front panel Relay output setup menu treeAlarm / energy pulsing LED setup Navigate to I/O configuration Energy Pulsing Disabled turns off the LED completely About Alarms AlarmsSecond Alarms List of Standard 1-Second Over/Under Alarms AlarmDigital Alarms How the power meter handles setpoint-driven alarmsAlarm Setup Unary AlarmsAlarm Priorities Using an Alarm to Control a Relay and Digital OutputSetting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Setting Up Digital Alarms Setting Up Digital Alarms Viewing Alarm Activity and History Viewing Active Alarms and Alarm CountersViewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5300 series user guide Alarms Data Logs Data LogsDescription Number of Registers Data Type Register Number Alarm Log Storage Alarm LogMemory Allocation for Log Files Power factor Measurements and calculationsReal-time readings EnergyPower factor min/max convention Power factor sign conventionIEC mode Power factor minimum and maximumPower demand calculation methods Ieee modeDemand Block interval demandSynchronized demand Block interval demand exampleCurrent demand Predicted demandThermal demand Thermal demand examplePeak demand Predicted demand exampleMulti-tariff feature example Multi-tariff featureMulti-tariff feature overview Command mode overview Time of day mode overviewTime format Front panel date and time formatExample tariff configurations for a four-tariff system Configuration 1 four tariffs with weekdays and weekendsTariff creation method Tariff Type Start date End date Start time End timeInput mode overview Configuration 1 2 tariff assignment using 2 digital inputs1Configuration 2 2 tariff assignment using 2 digital inputs Digital input requirements for required number of tariffsConfiguring tariffs using the front panel Configuring time of day mode tariffs using the front panelTariff setup menu tree Time of day mode tariff setupConfiguring input mode tariffs using the front panel Power quality Harmonic content calculationsHarmonics overview Total Harmonic Distortion and Total Demand DistortionViewing harmonics using the front panel Displaying harmonics dataTHD and thd calculations TDD calculationViewing THD/thd using the front panel Power Quality display screenViewing TDD Example 13th to 21st harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Reference device or energy standard Energy pulsingLocation of energy pulsing LED PM5300Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for alarm / energy LED Total power limit for digital output Energy pulsing considerations VT and CT considerationsTypical sources of test errors Test pointsWatt-hour test points example Var-hour test points exampleMeter resets Front panel meter reset screensGlobal resets Reset menu treeSingle resets Single reset optionsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5300 series user guideChapter 13-Meter resets 102 Maintenance and Upgrades Password RecoveryPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberControl Power Additional Meter Status InformationDownloading Firmware MeterHeartbeat/Comms LED Troubleshooting105 Troubleshooting Potential Problem Possible Cause Possible SolutionGetting Technical Support Register List 106Specifications relevant to MID MID ComplianceMID overview MID compliance for the meterInstallation and wiring MID ComplianceInstalling the terminal covers PM5331/PM5341 default screenDefault PM5331/PM5341 display screen Location of terminal coversMID-protected setup parameters Lock-protected setup parametersLock-protected setup parameters Meter firmware versionSetting up the PM5331/PM5341 Initializing the meterNavigate to Maint Setup Meter Lock Setting up lock passwordLocking or unlocking the meter Terms Glossary113 114 Abbreviations 115116 117 118 Page Schneider Electric 35, rue Joseph Monier CS