Chapter 10—Multi-tariff featurePowerLogic™ PM5300 series user guide

Time of day mode tariff setup (continued)

Parameter

Values

 

Description

 

 

 

 

 

Set the month that the tariff period starts,

Start Month

1 to 12

where 1 = January, 2 = February, 3 = March,

4

= April, 5 = May, 6 = June, 7 = July,

 

 

8

= August, 9 = September, 10 = October,

 

 

11 = November, 12 = December.

 

 

Set the day of the Start Month that the tariff

Start Day

1 to 31

period starts. The Start Day must be earlier

than End Day if Start Month equals End

 

 

 

 

Month.

 

 

 

 

 

The month that the tariff period ends, where

 

 

1

= January, 2 = February, 3 = March,

End Month

1 to 12

4

= April, 5 = May, 6 = June, 7 = July,

 

 

8

= August, 9 = September, 10 = October,

 

 

11 = November, 12 = December.

End Day

1 to 31

The day of the End Month that the tariff

period ends.

 

 

7.Modify each parameter as required, then press OK to set. Press or to move between parameters.

8.Press to exit, then Yes to save your changes. Repeat for the other tariffs as required. The meter checks the configuration and display a message if any tariffs have conflicting settings (i.e., overlapping tariff periods).

Configuring input mode tariffs using the front panel

When you set the tariff type to Input, the active tariff is determined by the status of the digital inputs.

Digital inputs are available for tariffs if they are not used, or if they are only associated with alarms (Normal). To make a digital input available, you must manually disconnect the conflicting association before configuring tariffs.

You cannot configure any digital input tariff if digital input 1 is not available for association. Likewise, digital input 2 must be available to select more than two tariffs. The status of the digital inputs is used to calculate the binary value of the active tariff, where off = 0 and on = 1. The calculation of the number of tariffs value can differ, depending on the number of digital inputs that can be selected (i.e., inputs that can be associated with multi-tariff).

To configure input mode tariffs using the front panel:

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to Meter > Tariff.

4.With the cursor pointing to Mode, press Edit.

5. Press or to change the setting to Input, then press OK.

NOTE: If a digital input association error prompt displays, you must exit from the tariff setup screens and remove the digital input association.

6. Navigate to Tariffs, then press Edit.

7. Press or to change the number of tariffs you want to set up. The maximum number of tariffs that you can apply is determined by the number of available digital inputs, as described in the table, “Digital input requirements for required number of tariffs” on page 86. Press OK.

8. Navigate to Inputs, then press Edit.

9. If applicable, press or to change how many digital inputs you want to use to control which tariff is selected (active). Press OK.

10. Press to exit, then Yes to save your changes.

88

© 2014 Schneider Electric All Rights Reserved

Image 88
Contents PowerLogic PM5300 Series Power and Energy Meter Page Important Information Please notePage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Alarms Chapter Multi-tariff featureChapter Power quality Chapter Input / OutputChapter Meter resets Chapter MaintenanceUpgrades Chapter Verifying accuraPowerLogic PM5300 series user guide Power and Energy Meter Hardware Parts and AccessoriesBox Contents IntroductionPowerLogic PM5300 user guide Safety Precautions Before You BeginPowerLogic PM5300 series user guide Models, Features and Options Functions and CharacteristicsPM5300 Series Models, Features and Options Functions and CharacteristicsPower Quality Measurements Energy ValuesDemand Values Other MeasurementsTechnical Specifications Electrical CharacteristicsMechanical Characteristics Environmental CharacteristicsSafety Electromagnetic CompatibilityDimension Safety precautionsHuman Machine Interface Meter mounting Mounting the PM5300Meter wiring Serial No Description Specification Screw driver type M3Recommended cables Make Part code DescriptionWiring Diagrams Power system Symbol DescriptionCurrent Transformer Voltage disconnect switch Direct connect voltage limitsMeter setting Power system setup parameters Power system descriptionSymbol Voltage and current input wiring Voltage input protectionCurrent input protection Direct connect maximumControl power wiring CommunicationsBalanced system considerations Serial communicationsRS-485 wiring RS-485 network configurationRS-485 cable RS-485 maximum cable lengthEthernet configuration Ethernet wiring EthernetETHERNET SwitchSWITCH/ hub/ HUBDigital outputs Ethernet communicationsStatus inputs Relay outputsDigital output connections Status input connectionsRelay output connections Front panel display and meter setup LED indicatorsAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics Menu tree PM5300 display screen menusFront panel meter setup Meter setup screen navigationConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Communications setup Setting up serial communicationsSerial communications setup menu tree Communication portsCommunications setup parameters Setting up Ethernet communicationsEthernet communications setup menu tree HMI settings Setting up the displayEthernet port settings Display setup menu treeSetting up the screen passwords Setting up regional settingsDisplay setup parameters Regional settings menu treePassword setup menu tree Lost passwordPassword setup parameters Setting the clock Advanced setup Clock setup menu treeClock setup parameters Advanced setup menu treeSetting up the alarm / energy pulsing LED Advanced setup parametersAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Input / output setup Demand setupPower or current demand setup parameters Alarms setup Multi-tariff setupRemote Meter Setup Viewing Meter Data Viewing meter data from the front panelMeter data display screens Displaying data screensPower PQS Volts U-VHarm Energy EAlarm Hz FUnbal MnMxUsing ION Setup to view or modify configuration data Using software to view meter dataTimer MaintStatus input applications Input / OutputStatus Input, Digital Output Ports and Relay Output Ports Status input setup Configuring status inputs using ION SetupNavigate to I/O configuration I/O Setup Status input setup parameters available through ION SetupConfiguring status inputs using the front panel Status input setup menu treeDigital output setup Digital output wiring exampleDigital output applications Digital output application exampleConfiguring digital outputs using ION Setup Digital output setup parameters available through ION SetupConfiguring digital outputs using the front panel Digital output setup menu treeOn Time s This defines the pulse width on time in seconds Parameter Values Description Relay output setup Configuring relay outputs using ION SetupRelay output setup parameters available through ION Setup Relay output applicationsSet to External or Alarm. The relay output Configuring relay outputs using the front panel Relay output setup menu treeAlarm / energy pulsing LED setup Navigate to I/O configuration Energy Pulsing Disabled turns off the LED completely About Alarms AlarmsSecond Alarms List of Standard 1-Second Over/Under Alarms AlarmDigital Alarms How the power meter handles setpoint-driven alarmsAlarm Setup Unary AlarmsAlarm Priorities Using an Alarm to Control a Relay and Digital OutputSetting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Setting Up Digital Alarms Setting Up Digital Alarms Viewing Alarm Activity and History Viewing Active Alarms and Alarm CountersViewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5300 series user guide Alarms Data Logs Data LogsDescription Number of Registers Data Type Register Number Alarm Log Storage Alarm LogMemory Allocation for Log Files Power factor Measurements and calculationsReal-time readings EnergyPower factor min/max convention Power factor sign conventionIEC mode Power factor minimum and maximumPower demand calculation methods Ieee modeDemand Block interval demandSynchronized demand Block interval demand exampleCurrent demand Predicted demandThermal demand Thermal demand examplePeak demand Predicted demand exampleMulti-tariff feature example Multi-tariff featureMulti-tariff feature overview Command mode overview Time of day mode overviewTime format Front panel date and time format Example tariff configurations for a four-tariff system Configuration 1 four tariffs with weekdays and weekends Tariff creation method Tariff Type Start date End date Start time End timeInput mode overview Configuration 1 2 tariff assignment using 2 digital inputs1Configuration 2 2 tariff assignment using 2 digital inputs Digital input requirements for required number of tariffsConfiguring tariffs using the front panel Configuring time of day mode tariffs using the front panelTariff setup menu tree Time of day mode tariff setupConfiguring input mode tariffs using the front panel Power quality Harmonic content calculationsHarmonics overview Total Harmonic Distortion and Total Demand DistortionViewing harmonics using the front panel Displaying harmonics dataTHD and thd calculations TDD calculationViewing THD/thd using the front panel Power Quality display screenViewing TDD Example 13th to 21st harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Reference device or energy standard Energy pulsingLocation of energy pulsing LED PM5300Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for alarm / energy LED Total power limit for digital outputEnergy pulsing considerations VT and CT considerationsTypical sources of test errors Test pointsWatt-hour test points example Var-hour test points exampleMeter resets Front panel meter reset screensGlobal resets Reset menu treeSingle resets Single reset optionsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5300 series user guideChapter 13-Meter resets 102 Maintenance and Upgrades Password RecoveryPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberControl Power Additional Meter Status InformationDownloading Firmware MeterHeartbeat/Comms LED Troubleshooting105 Troubleshooting Potential Problem Possible Cause Possible SolutionGetting Technical Support Register List 106Specifications relevant to MID MID ComplianceMID overview MID compliance for the meterInstallation and wiring MID ComplianceInstalling the terminal covers PM5331/PM5341 default screenDefault PM5331/PM5341 display screen Location of terminal coversMID-protected setup parameters Lock-protected setup parametersLock-protected setup parameters Meter firmware versionSetting up the PM5331/PM5341 Initializing the meterNavigate to Maint Setup Meter Lock Setting up lock passwordLocking or unlocking the meter Terms Glossary113 114 Abbreviations 115116 117 118 Page Schneider Electric 35, rue Joseph Monier CS