PowerLogic™ PM5300 series user guide | Chapter |
|
|
Configuring status inputs using the front panel
You can use the front panel to configure the status inputs.
Status input setup menu tree
Maint
Reset
Setup
Meter
Comm
Alarm
I/O
HMI
Clock
LED
SIn D Out Relay
1.Navigate to Maint > Setup.
2.Enter the setup password (default is “0”), then press OK.
3.Navigate to I/O > S In.
4.Move the cursor to point to the status input you want to set up, then press Edit.
5.Move the cursor to point to the parameter you want to modify, then press Edit.
NOTE: If Edit is not displayed, it means the parameter is either
6.Modify the parameter as required, then press OK.
Status input setup parameters available through the front panel
Parameter | Values | Description | |
|
|
| |
Label | — | This can be modified only through software. Use this | |
field to assign names to the status inputs (S1 and S2). | |||
|
| ||
|
| Debounce is the time delay that compensates for | |
Debounce Time | 0 to 1000 | mechanical contact bounce. Use this field to set how | |
(ms) | long (in milliseconds) the external signal must remain in | ||
| |||
|
| a certain state to be considered a valid state change. | |
|
|
| |
|
| This field displays how the status input functions. | |
Control Mode | Normal | Normal: the status input is not associated with another | |
|
| meter function. The meter counts and records the | |
|
| number of incoming pulses normally. |
7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.
8.Press to exit. Press Yes to save your changes.
Related topics
See “Technical Specifications” on page 15 for electrical characteristics and limits for the status inputs.