Schneider Electric PM5300 manual Mechanical Characteristics, Environmental Characteristics, Safety

Page 16

PowerLogic™ PM5300 series user guide

Chapter 3—Hardware Reference

 

from 1 to 9,999,999 pulses per k_h (k_h = kWh,

Meter constant

kVARh or kVAh depending on the energy

 

parameter selected)

Pulse width for Digital Output

50% duty cycle

Pulse frequency for Digital Output

25 Hz max.

Leakage current

0.03 micro Amps

Isolation

5 kV rms

Optical outputs

 

Pulse width (LED)

200 μs

Pulse frequency

50 Hz. max.

Meter constant

from 1 to 9,999,999 pulses per k_h

Status Inputs

 

ON Voltage

18.5 to 36 V DC

OFF Voltage

0 to 4 V DC

Input Resistance

110 k Ω

Maximum Frequency

2 Hz (T ON min = T OFF min = 250 ms)

Response Time

20 ms

Opto Isolation

5 kV rms

Whetting output

24 V DC/ 8mA max

Input Burden

2 mA @ 24 V DC

Mechanical Characteristics

 

 

 

Product weight

430 g

IP degree of protection (IEC 60529)

IP52 front display, IP30 meter body

Dimensions W x H x D [protrusion from cabinet]

96 x 96 x 72mm (depth of meter from housing

mounting flange) [13mm]

 

Mounting position

Vertical

Panel thickness

6 mm maximum

Environmental Characteristics

 

 

 

Operating temperature

 

Meter

-25 °C to +70 °C

Display (Display functions to -25º with reduced

-25 °C to +70 °C

performance)

 

Storage temp.

-40 °C to +85 °C

Humidity range

5 to 95 % RH at 50 °C (non-condensing)

Pollution degree

2

Altitude

2000 m CAT III / 3000 m CAT II

For indoor use only

 

Electromagnetic Compatibility 3

 

Electrostatic discharge

IEC 61000-4-2

Immunity to radiated fields

IEC 61000-4-3

Immunity to fast transients

IEC 61000-4-4

Immunity to surge

IEC 61000-4-5

Conducted immunity 150kHz to 80MHz

IEC 61000-4-6

Immunity to magnetic fields

IEC 61000-4-8

Immunity to voltage dips

IEC 61000-4-11

Radiated emissions

FCC part 15, EN 55022 Class B

Conducted emissions

FCC part 15, EN 55022 Class B

Safety

 

 

 

Europe

CE, as per IEC 61010-1 (3rd Edition), IEC 62052-

11 & IEC61557-121

U.S. and Canada

cULus as per UL61010-1 (3rd Edition)

CAN/CSA-C22.2 No. 61010-1 (3rd Edition)

 

Measurement category (Voltage and Current inputs)

CAT III up to 400 V L-N / 690 V L-L

Dielectric

As per IEC/UL 61010-1 (3rd Edition)

Protective Class

II, Double insulated for user accessible parts

Communication

 

 

 

 

2-Wire, 9600,19200 or 38400 baud, Parity - Even,

RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS

Odd, None, 1 stop bit if parity Odd or Even, 2 stop

 

bits if None; (Optional)

Ethernet port: 10/100 Mbps; Modbus TCP/IP

1 (Optional)

Firmware and language file update

Meter firmware update via the communication

ports

 

16

© 2014 Schneider Electric All Rights Reserved

Image 16
Contents PowerLogic PM5300 Series Power and Energy Meter Page Important Information Please notePage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Alarms Chapter Multi-tariff featureChapter Power quality Chapter Input / OutputChapter Meter resets Chapter MaintenanceUpgrades Chapter Verifying accuraPowerLogic PM5300 series user guide Power and Energy Meter Hardware Parts and AccessoriesBox Contents IntroductionPowerLogic PM5300 user guide Safety Precautions Before You BeginPowerLogic PM5300 series user guide Models, Features and Options Functions and CharacteristicsPM5300 Series Models, Features and Options Functions and CharacteristicsPower Quality Measurements Energy ValuesDemand Values Other MeasurementsTechnical Specifications Electrical CharacteristicsMechanical Characteristics Environmental CharacteristicsSafety Electromagnetic CompatibilityDimension Safety precautionsHuman Machine Interface Meter mounting Mounting the PM5300Meter wiring Serial No Description Specification Screw driver type M3Recommended cables Make Part code DescriptionWiring Diagrams Power system Symbol DescriptionCurrent Transformer Voltage disconnect switch Direct connect voltage limitsMeter setting Power system setup parameters Power system descriptionSymbol Voltage and current input wiring Voltage input protectionCurrent input protection Direct connect maximumControl power wiring CommunicationsBalanced system considerations Serial communicationsRS-485 wiring RS-485 network configurationRS-485 cable RS-485 maximum cable lengthEthernet configuration Ethernet wiring EthernetETHERNET SwitchSWITCH/ hub/ HUBDigital outputs Ethernet communicationsStatus inputs Relay outputsDigital output connections Status input connectionsRelay output connections Front panel display and meter setup LED indicatorsAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics Menu tree PM5300 display screen menusFront panel meter setup Meter setup screen navigationConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Communications setup Setting up serial communicationsSerial communications setup menu tree Communication portsCommunications setup parameters Setting up Ethernet communicationsEthernet communications setup menu tree HMI settings Setting up the displayEthernet port settings Display setup menu treeSetting up the screen passwords Setting up regional settingsDisplay setup parameters Regional settings menu treePassword setup menu tree Lost passwordPassword setup parameters Setting the clock Advanced setup Clock setup menu treeClock setup parameters Advanced setup menu treeSetting up the alarm / energy pulsing LED Advanced setup parametersAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Input / output setup Demand setupPower or current demand setup parameters Alarms setup Multi-tariff setupRemote Meter Setup Viewing Meter Data Viewing meter data from the front panelMeter data display screens Displaying data screensPower PQS Volts U-VHarm Energy EAlarm Hz FUnbal MnMxUsing ION Setup to view or modify configuration data Using software to view meter dataTimer MaintStatus input applications Input / OutputStatus Input, Digital Output Ports and Relay Output Ports Status input setup Configuring status inputs using ION SetupNavigate to I/O configuration I/O Setup Status input setup parameters available through ION SetupConfiguring status inputs using the front panel Status input setup menu treeDigital output setup Digital output wiring exampleDigital output applications Digital output application exampleConfiguring digital outputs using ION Setup Digital output setup parameters available through ION SetupConfiguring digital outputs using the front panel Digital output setup menu treeOn Time s This defines the pulse width on time in seconds Parameter Values Description Relay output setup Configuring relay outputs using ION SetupRelay output setup parameters available through ION Setup Relay output applicationsSet to External or Alarm. The relay output Configuring relay outputs using the front panel Relay output setup menu treeAlarm / energy pulsing LED setup Navigate to I/O configuration Energy Pulsing Disabled turns off the LED completely About Alarms AlarmsSecond Alarms List of Standard 1-Second Over/Under Alarms AlarmDigital Alarms How the power meter handles setpoint-driven alarmsAlarm Setup Unary AlarmsAlarm Priorities Using an Alarm to Control a Relay and Digital OutputSetting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Setting Up Digital Alarms Setting Up Digital Alarms Viewing Alarm Activity and History Viewing Active Alarms and Alarm CountersViewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5300 series user guide Alarms Data Logs Data LogsDescription Number of Registers Data Type Register Number Alarm Log Storage Alarm LogMemory Allocation for Log Files Power factor Measurements and calculationsReal-time readings EnergyPower factor min/max convention Power factor sign conventionIEC mode Power factor minimum and maximumPower demand calculation methods Ieee modeDemand Block interval demandSynchronized demand Block interval demand exampleCurrent demand Predicted demandThermal demand Thermal demand examplePeak demand Predicted demand exampleMulti-tariff feature example Multi-tariff featureMulti-tariff feature overview Command mode overview Time of day mode overviewTime format Front panel date and time formatExample tariff configurations for a four-tariff system Configuration 1 four tariffs with weekdays and weekendsTariff creation method Tariff Type Start date End date Start time End timeInput mode overview Configuration 1 2 tariff assignment using 2 digital inputs1Configuration 2 2 tariff assignment using 2 digital inputs Digital input requirements for required number of tariffsConfiguring tariffs using the front panel Configuring time of day mode tariffs using the front panelTariff setup menu tree Time of day mode tariff setupConfiguring input mode tariffs using the front panel Power quality Harmonic content calculationsHarmonics overview Total Harmonic Distortion and Total Demand DistortionViewing harmonics using the front panel Displaying harmonics dataTHD and thd calculations TDD calculationViewing THD/thd using the front panel Power Quality display screenViewing TDD Example 13th to 21st harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Reference device or energy standard Energy pulsingLocation of energy pulsing LED PM5300Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for alarm / energy LED Total power limit for digital outputEnergy pulsing considerations VT and CT considerationsTypical sources of test errors Test pointsWatt-hour test points example Var-hour test points exampleMeter resets Front panel meter reset screensGlobal resets Reset menu treeSingle resets Single reset optionsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5300 series user guideChapter 13-Meter resets 102 Maintenance and Upgrades Password RecoveryPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberControl Power Additional Meter Status InformationDownloading Firmware MeterHeartbeat/Comms LED Troubleshooting105 Troubleshooting Potential Problem Possible Cause Possible SolutionGetting Technical Support Register List 106Specifications relevant to MID MID ComplianceMID overview MID compliance for the meterInstallation and wiring MID ComplianceInstalling the terminal covers PM5331/PM5341 default screenDefault PM5331/PM5341 display screen Location of terminal coversMID-protected setup parameters Lock-protected setup parametersLock-protected setup parameters Meter firmware versionSetting up the PM5331/PM5341 Initializing the meterNavigate to Maint Setup Meter Lock Setting up lock passwordLocking or unlocking the meter Terms Glossary113 114 Abbreviations 115116 117 118 Page Schneider Electric 35, rue Joseph Monier CS