Schneider Electric PM5300 manual Hardware Reference, Models, Features and Options

Page 13

PowerLogic™ PM5300 series user guide

Chapter 3—Hardware Reference

Chapter 3—Hardware Reference

This section supplements the meter’s installation sheet and provides additional information about the meter’s physical characteristics and capabilities.

Models, Features and Options

Table 3 –1: PM5300 Series - Models, Features and Options

 

 

PM5300 Series

 

Features and Options

PM5310

PM5320

PM5330

PM5340

 

PM5331

PM5341

 

 

 

Installation

 

 

 

 

 

 

 

 

 

Fast installation, panel mount with integrated

display

 

 

 

 

Accuracy

Cl 0.5S

Cl 0.5S

Cl 0.5S

Cl 0.5S

Display

 

 

 

 

Backlit LCD, multilingual, bar graphs, 6 lines, 4

concurrent values

 

 

 

 

Power and energy metering

 

 

 

 

3-phase voltage, current, power, demand,

energy, frequency, power factor

 

 

 

 

Multi-tariff

4

4

4

4

Power quality analysis

 

 

 

 

THD, thd, TDD

 

 

 

 

 

Harmonics, individual (odd) up to

31st

31st

31st

31st

I/Os and relays

 

 

 

 

I/Os

2SI/2DO

2SI/2DO

2SI/2DO

2SI/2DO

Relays

0

0

2

2

Alarms and control

 

 

 

 

Alarms

35

35

35

35

Set point response time, seconds

1

1

1

1

Single and multi-condition alarms

 

 

 

 

 

Communications

 

 

 

 

Serial ports with modbus protocol

1

-

1

-

Ethernet port with Modbus TCP protocol

-

1

-

1

MID ready compliance,

 

 

PM5331

PM5341

EN50470-1/3, Annex B and Annex D

 

 

Class C

 

 

 

 

Functions and Characteristics

Table 3 –2: Functions and Characteristics

General

PM5300 Series

Use on LV and MV systems

 

 

Basic metering with THD and min/max readings

 

 

Instantaneous rms values

Current (per phase and neutral)

Voltage (total, per phase L-L and L-N)

© 2014 Schneider Electric All Rights Reserved

13

Image 13
Contents PowerLogic PM5300 Series Power and Energy Meter Page Please note Important InformationPage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Multi-tariff feature Chapter AlarmsChapter Power quality Chapter Input / OutputChapter Maintenance Chapter Meter resetsUpgrades Chapter Verifying accuraPowerLogic PM5300 series user guide Parts and Accessories Power and Energy Meter HardwareBox Contents Introduction PowerLogic PM5300 user guide Before You Begin Safety PrecautionsPowerLogic PM5300 series user guide Functions and Characteristics Models, Features and OptionsPM5300 Series Models, Features and Options Functions and CharacteristicsEnergy Values Power Quality MeasurementsDemand Values Other MeasurementsElectrical Characteristics Technical SpecificationsEnvironmental Characteristics Mechanical CharacteristicsSafety Electromagnetic CompatibilityDimension Safety precautionsHuman Machine Interface Mounting the PM5300 Meter mountingMeter wiring Screw driver type M3 Serial No Description SpecificationMake Part code Description Recommended cablesWiring Diagrams Symbol Description Power systemCurrent Transformer Voltage disconnect switch Direct connect voltage limitsMeter setting Power system setup parameters Power system descriptionSymbol Voltage input protection Voltage and current input wiringCurrent input protection Direct connect maximumCommunications Control power wiringBalanced system considerations Serial communicationsRS-485 network configuration RS-485 wiringRS-485 cable RS-485 maximum cable lengthEthernet wiring EthernetETHERNET SwitchSWITCH/ hub/ HUB Ethernet configurationDigital outputs Ethernet communicationsRelay outputs Status inputsDigital output connections Status input connectionsRelay output connections LED indicators Front panel display and meter setupAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics PM5300 display screen menus Menu treeMeter setup screen navigation Front panel meter setupConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Setting up serial communications Communications setupSerial communications setup menu tree Communication portsCommunications setup parameters Setting up Ethernet communicationsEthernet communications setup menu tree Setting up the display HMI settingsEthernet port settings Display setup menu treeSetting up regional settings Setting up the screen passwordsDisplay setup parameters Regional settings menu treePassword setup menu tree Lost passwordPassword setup parameters Clock setup menu tree Setting the clock Advanced setupClock setup parameters Advanced setup menu treeAdvanced setup parameters Setting up the alarm / energy pulsing LEDAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Input / output setup Demand setupPower or current demand setup parameters Alarms setup Multi-tariff setupRemote Meter Setup Viewing meter data from the front panel Viewing Meter DataMeter data display screens Displaying data screensVolts U-V Power PQSHarm Energy EHz F AlarmUnbal MnMxUsing software to view meter data Using ION Setup to view or modify configuration dataTimer MaintStatus input applications Input / OutputStatus Input, Digital Output Ports and Relay Output Ports Configuring status inputs using ION Setup Status input setupNavigate to I/O configuration I/O Setup Status input setup parameters available through ION SetupStatus input setup menu tree Configuring status inputs using the front panelDigital output wiring example Digital output setupDigital output applications Digital output application exampleDigital output setup parameters available through ION Setup Configuring digital outputs using ION SetupDigital output setup menu tree Configuring digital outputs using the front panelOn Time s This defines the pulse width on time in seconds Parameter Values Description Configuring relay outputs using ION Setup Relay output setupRelay output setup parameters available through ION Setup Relay output applicationsSet to External or Alarm. The relay output Relay output setup menu tree Configuring relay outputs using the front panelAlarm / energy pulsing LED setup Navigate to I/O configuration Energy Pulsing Disabled turns off the LED completely About Alarms AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsHow the power meter handles setpoint-driven alarms Digital AlarmsUnary Alarms Alarm SetupAlarm Priorities Using an Alarm to Control a Relay and Digital OutputSetting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Setting Up Digital Alarms Setting Up Digital Alarms Viewing Active Alarms and Alarm Counters Viewing Alarm Activity and HistoryViewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5300 series user guide Alarms Data Logs Data LogsDescription Number of Registers Data Type Register Number Alarm Log Storage Alarm LogMemory Allocation for Log Files Measurements and calculations Power factorReal-time readings EnergyPower factor sign convention Power factor min/max conventionIEC mode Power factor minimum and maximumIeee mode Power demand calculation methodsDemand Block interval demandBlock interval demand example Synchronized demandPredicted demand Current demandThermal demand Thermal demand examplePredicted demand example Peak demandMulti-tariff feature example Multi-tariff featureMulti-tariff feature overview Time of day mode overview Command mode overviewTime format Front panel date and time formatConfiguration 1 four tariffs with weekdays and weekends Example tariff configurations for a four-tariff systemTariff creation method Tariff Type Start date End date Start time End timeConfiguration 1 2 tariff assignment using 2 digital inputs1 Input mode overviewConfiguration 2 2 tariff assignment using 2 digital inputs Digital input requirements for required number of tariffsConfiguring time of day mode tariffs using the front panel Configuring tariffs using the front panelTariff setup menu tree Time of day mode tariff setupConfiguring input mode tariffs using the front panel Harmonic content calculations Power qualityHarmonics overview Total Harmonic Distortion and Total Demand DistortionDisplaying harmonics data Viewing harmonics using the front panelTHD and thd calculations TDD calculationPower Quality display screen Viewing THD/thd using the front panelViewing TDD Example 13th to 21st harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Energy pulsing Reference device or energy standardLocation of energy pulsing LED PM5300Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for digital output Total power limit for alarm / energy LEDEnergy pulsing considerations VT and CT considerationsTest points Typical sources of test errorsWatt-hour test points example Var-hour test points exampleFront panel meter reset screens Meter resetsGlobal resets Reset menu treeSingle reset options Single resetsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5300 series user guideChapter 13-Meter resets 102 Password Recovery Maintenance and UpgradesPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberAdditional Meter Status Information Control PowerDownloading Firmware MeterHeartbeat/Comms LED Troubleshooting105 Potential Problem Possible Cause Possible Solution TroubleshootingGetting Technical Support Register List 106MID Compliance Specifications relevant to MIDMID overview MID compliance for the meterMID Compliance Installation and wiringPM5331/PM5341 default screen Installing the terminal coversDefault PM5331/PM5341 display screen Location of terminal coversLock-protected setup parameters MID-protected setup parametersLock-protected setup parameters Meter firmware versionInitializing the meter Setting up the PM5331/PM5341Navigate to Maint Setup Meter Lock Setting up lock passwordLocking or unlocking the meter Terms Glossary113 114 115 Abbreviations116 117 118 Page Schneider Electric 35, rue Joseph Monier CS