PowerLogic™ PM5300 series user guideChapter
Communications setup parameters
Parameter | Values | Description |
|
|
|
|
| The communications format used to transmit data. The |
Protocol | Modbus | protocol must be the same for all devices in a |
|
| communications loop. |
|
| Set the address for this device. The address must be |
Address | 1 to 247 | unique for each device in a communications loop. For |
|
| Jbus protocol, set the device ID to 255. |
|
| Select the speed for data transmission. The baud rate |
Baud Rate | 9600, 19200, 38400 | must be the same for all devices in a communications |
|
| loop. |
|
| Select None if the parity bit is not used. The parity |
Parity | Even, Odd, None | setting must be the same for all devices in a |
|
| communications loop. |
7. Press
to exit. Press Yes to save your changes.
Setting up Ethernet communications
The Ethernet Port setup screen allows you to assign the meter a unique IP address so you can use software to access the meter’s data or configure the meter remotely through the Ethernet port. Before configuring the Ethernet parameters, make sure you obtain your meter’s IP address information from your network administrator or IT department.
Ethernet communications setup menu tree
Maint
Reset
Setup
Meter
Comm
1.Navigate to Maint > Setup.
2.Enter the setup password (default is “0000”), then press OK.
3.Press Comm.
4.Move the cursor to point to the parameter you want to modify, then press Edit.
5.Modify the parameter as required, then press OK.
6.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.
© 2014 Schneider Electric All Rights Reserved | 37 |