Chapter | PowerLogic™ PM5300 series user guide |
|
|
Digital output setup parameters available through ION Setup (continued)
Parameter |
| Values | Description | |
|
|
|
| |
| 1. | Over Current, Ph; |
| |
| 2. | Under Current, Ph; |
| |
| 3. | Over Current, N; |
| |
| 4. | Over Current Gnd; |
| |
| 5. | Over Voltage, |
| |
| 6. | Under Voltage, |
| |
| 7. | Over Voltage, |
| |
| 8. | Under Voltage |
| |
| 9. | Over kW; |
| |
| 10. | Over kVAR; |
| |
| 11. | Over kVA; |
| |
| 12. | Lead PF, True; |
| |
| 13. | Lag PF, True; |
| |
| 14. | Lead PF, Disp; |
| |
| 15. | Lag PF, Disp; |
| |
| 16. | Over kW Dmd, Pres; |
| |
| 17. | Over kW Dmd, Last; | Applies when Control Mode is set to Alarm. Select | |
Select Alarms | 18. | Over kW Dmd, Pred; | ||
one or more alarms to monitor. | ||||
| 19. | Over kVAR Dmd,Pres; | ||
|
| |||
| 20. | Over kVAR Dmd,Last; |
| |
| 21. | Over kVAR Dmd,Pred; |
| |
| 22. | Over kVA Dmd, Pres; |
| |
| 23. | Over kVA Dmd, Last; |
| |
| 24. | Over kVA Dmd, Pred; |
| |
| 25. | Over Frequency; |
| |
| 26. | Under Frequency; |
| |
| 27. | Over Voltage Unbal; |
| |
| 28. | Over Voltage THD; |
| |
| 29. | Phase Loss; |
| |
| 30. | Meter Powerup; |
| |
| 31. | Meter Reset; |
| |
| 32. | Meter Diagnostic; |
| |
| 33. | Phase Reversal; |
| |
| 34. | Digital Alarm S1; |
| |
| 35. | Digital Alarm S2; |
| |
|
|
|
| |
|
|
| This field displays additional information if the digital | |
Associations | — |
| output is already associated with another meter | |
|
|
| function. |
Configuring digital outputs using the front panel
You can use the front panel to configure the digital outputs.
Digital output setup menu tree
Maint
Reset
Setup
Meter
Comm
Alarm
I/O
HMI
Clock
LED
SIn D Out Relay
1.Navigate to Maint > Setup.
2.Enter the setup password (default is “0000”), then press OK.
3.Navigate to I/O > D Out.
54 | © 2014 Schneider Electric All Rights Reserved |