PowerLogic™ PM5300 series user guide | Chapter |
|
|
Configuring digital outputs using ION Setup
You can use ION Setup to configure the digital outputs (D1 and D2).
1.Start ION Setup.
2.Connect to your meter
3.Navigate to I/O configuration > I/O Setup.
4.Select a digital output to configure and click Edit. The setup screen for that digital output is displayed.
5.Enter a descriptive name for the digital output’s Label.
6.Configure the other setup parameters as required.
7.Click Send to save your changes.
Digital output setup parameters available through ION Setup
Parameter | Values | Description | |
|
|
| |
Label | — | Use this field to change the default label and assign a | |
descriptive name to this digital output. | |||
|
| ||
|
| This field displays how the digital output functions. | |
|
| • External: the digital output is controlled remotely | |
|
| either through software or by a PLC using | |
|
| commands sent through communications. | |
Control Mode | External, Demand Sync, | • Demand Sync: the digital output is associated | |
Alarm | with one of the demand systems. The meter | ||
|
| sends a pulse to the digital output port at the end | |
|
| of every demand interval. | |
|
| • Alarm: the digital output is associated with the | |
|
| alarm system. The meter sends a pulse to the | |
|
| digital output port when the alarm is triggered. | |
|
| • Normal: this mode applies when control mode is | |
|
| set to External or Alarm. The digital output | |
|
| remains in the ON state until an OFF command is | |
|
| sent by the computer or PLC. | |
|
| • Timed: the digital output remains ON for the | |
|
| period defined by the On Time setup register. | |
Behavior Mode | Normal, Timed, Coil Hold | • Coil Hold: this mode applies when control mode | |
is set to External or Alarm. For a unary alarm that | |||
|
| is associated with a digital output, you must set | |
|
| Behavior Mode to Coil Hold. The output turns on | |
|
| when the “energize” command is received and | |
|
| turns off when the “coil hold release” command is | |
|
| received. In the event of a control power loss, the | |
|
| output remembers and returns to the state it was | |
|
| in when control power was lost. | |
On Time (s) | 0 to 9999 | This setting defines the pulse width (ON time) in | |
seconds. | |||
|
| ||
Select Dmd System | Power, Current | Applies when Control Mode is set to Demand Sync. | |
Select the demand system to monitor. | |||
|
|
© 2014 Schneider Electric All Rights Reserved | 53 |