Schneider Electric PM5300 manual Setting Up 1-Second Alarms

Page 67

PowerLogic™ PM5300 series user guide

Chapter 7—Alarms

Setting Up 1-Second Alarms

To set up a standard alarm:

1.Press 1-Sec. The 1-second alarm Select screen appears.

2.Press and to scroll through the list of standard 1– second alarms.

3.Press Edit to select an alarm to be configured.

4.Press Edit to select Pickup Setpoint.

5.Press + to increment the active digit through the numerals 0-9.

6.Press to enter the selected value for the active digit and move to the next digit to the left.

7.Continue until all values are selected, then press OK to enter the selected number for the pickup setpoint.

8.For power factor alarms (Lead PF, True; Lag PF, True; Lead PF, Disp; and Lag PF, Disp) press to select PU Set Point Lead/Lag, then press Edit. For other alarms, skip to Step 11.

9.Press + and - to scroll between Lead and Lag.

10.Press OK to set the pickup set point lead or lag.

11.Press and follow Steps 4 to 7 for Pickup Time Delay and Dropout Setpoint.

12.For power factor alarms, press to select DO Set Point Lead/Lag and follow Steps 10 and 11. For other alarms, proceed to Step 14.

13.Press and follow Steps 4 to 7 for Dropout Time Delay.

14.Press to select Enable, then press Edit.

15.Press + and - to scroll between Yes and No.

16.Press OK to enable or disable the alarm.

© 2014 Schneider Electric All Rights Reserved

67

Image 67
Contents PowerLogic PM5300 Series Power and Energy Meter Page Please note Important InformationPage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Input / Output Chapter AlarmsChapter Multi-tariff feature Chapter Power qualityChapter Verifying accura Chapter Meter resetsChapter Maintenance UpgradesPowerLogic PM5300 series user guide Introduction Power and Energy Meter HardwareParts and Accessories Box ContentsPowerLogic PM5300 user guide Before You Begin Safety PrecautionsPowerLogic PM5300 series user guide Functions and Characteristics Models, Features and OptionsFunctions and Characteristics PM5300 Series Models, Features and OptionsOther Measurements Power Quality MeasurementsEnergy Values Demand ValuesElectrical Characteristics Technical SpecificationsElectromagnetic Compatibility Mechanical CharacteristicsEnvironmental Characteristics SafetyDimension Safety precautionsHuman Machine Interface Mounting the PM5300 Meter mountingMeter wiring Screw driver type M3 Serial No Description SpecificationMake Part code Description Recommended cablesWiring Diagrams Direct connect voltage limits Power systemSymbol Description Current Transformer Voltage disconnect switchMeter setting Power system setup parameters Power system descriptionSymbol Direct connect maximum Voltage and current input wiringVoltage input protection Current input protectionSerial communications Control power wiringCommunications Balanced system considerationsRS-485 maximum cable length RS-485 wiringRS-485 network configuration RS-485 cableEthernet communications Ethernet configurationEthernet wiring EthernetETHERNET SwitchSWITCH/ hub/ HUB Digital outputsStatus input connections Status inputsRelay outputs Digital output connectionsRelay output connections Heartbeat / communications LED Front panel display and meter setupLED indicators Alarm / energy pulsing LED modesMeter screen menus Notification iconsRelated topics PM5300 display screen menus Menu treeBasic setup screen Front panel meter setupMeter setup screen navigation Configuring the basic setup parametersBasic setup parameters Basic setup menu treeParameter Values Description Communication ports Communications setupSetting up serial communications Serial communications setup menu treeCommunications setup parameters Setting up Ethernet communicationsEthernet communications setup menu tree Display setup menu tree HMI settingsSetting up the display Ethernet port settingsRegional settings menu tree Setting up the screen passwordsSetting up regional settings Display setup parametersPassword setup menu tree Lost passwordPassword setup parameters Advanced setup menu tree Setting the clock Advanced setupClock setup menu tree Clock setup parametersLED setup parameter Setting up the alarm / energy pulsing LEDAdvanced setup parameters Alarm / energy pulsing LED settings menu treeDemand setup menu tree Input / output setup Demand setupPower or current demand setup parameters Alarms setup Multi-tariff setupRemote Meter Setup Displaying data screens Viewing Meter DataViewing meter data from the front panel Meter data display screensEnergy E Power PQSVolts U-V HarmMnMx AlarmHz F UnbalMaint Using ION Setup to view or modify configuration dataUsing software to view meter data TimerStatus input applications Input / OutputStatus Input, Digital Output Ports and Relay Output Ports Status input setup parameters available through ION Setup Status input setupConfiguring status inputs using ION Setup Navigate to I/O configuration I/O SetupStatus input setup menu tree Configuring status inputs using the front panelDigital output application example Digital output setupDigital output wiring example Digital output applicationsDigital output setup parameters available through ION Setup Configuring digital outputs using ION SetupDigital output setup menu tree Configuring digital outputs using the front panelOn Time s This defines the pulse width on time in seconds Parameter Values Description Relay output applications Relay output setupConfiguring relay outputs using ION Setup Relay output setup parameters available through ION SetupSet to External or Alarm. The relay output Relay output setup menu tree Configuring relay outputs using the front panelAlarm / energy pulsing LED setup Navigate to I/O configuration Energy Pulsing Disabled turns off the LED completely About Alarms AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsHow the power meter handles setpoint-driven alarms Digital AlarmsUsing an Alarm to Control a Relay and Digital Output Alarm SetupUnary Alarms Alarm PrioritiesSetting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Setting Up Digital Alarms Setting Up Digital Alarms Viewing Active Alarms and Alarm Counters Viewing Alarm Activity and HistoryViewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5300 series user guide Alarms Data Logs Data LogsDescription Number of Registers Data Type Register Number Alarm Log Storage Alarm LogMemory Allocation for Log Files Energy Power factorMeasurements and calculations Real-time readingsPower factor minimum and maximum Power factor min/max conventionPower factor sign convention IEC modeBlock interval demand Power demand calculation methodsIeee mode DemandBlock interval demand example Synchronized demandThermal demand example Current demandPredicted demand Thermal demandPredicted demand example Peak demandMulti-tariff feature example Multi-tariff featureMulti-tariff feature overview Front panel date and time format Command mode overviewTime of day mode overview Time formatTariff Type Start date End date Start time End time Example tariff configurations for a four-tariff systemConfiguration 1 four tariffs with weekdays and weekends Tariff creation methodDigital input requirements for required number of tariffs Input mode overviewConfiguration 1 2 tariff assignment using 2 digital inputs1 Configuration 2 2 tariff assignment using 2 digital inputsTime of day mode tariff setup Configuring tariffs using the front panelConfiguring time of day mode tariffs using the front panel Tariff setup menu treeConfiguring input mode tariffs using the front panel Total Harmonic Distortion and Total Demand Distortion Power qualityHarmonic content calculations Harmonics overviewTDD calculation Viewing harmonics using the front panelDisplaying harmonics data THD and thd calculationsExample 13th to 21st harmonics for line-to-neutral voltage Viewing THD/thd using the front panelPower Quality display screen Viewing TDDRelated topics Verifying accuracy Testing overviewAccuracy test requirements PM5300 Reference device or energy standardEnergy pulsing Location of energy pulsing LEDVerifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses VT and CT considerations Total power limit for alarm / energy LEDTotal power limit for digital output Energy pulsing considerationsVar-hour test points example Typical sources of test errorsTest points Watt-hour test points exampleReset menu tree Meter resetsFront panel meter reset screens Global resetsAlarm counter Option Description Single resetsSingle reset options Alarm counter optionsPowerLogic PM5300 series user guideChapter 13-Meter resets 102 Identifying the Firmware Version, Model, and Serial Number Maintenance and UpgradesPassword Recovery Power Meter MemoryMeter Control PowerAdditional Meter Status Information Downloading FirmwareHeartbeat/Comms LED Troubleshooting105 106 TroubleshootingPotential Problem Possible Cause Possible Solution Getting Technical Support Register ListMID compliance for the meter Specifications relevant to MIDMID Compliance MID overviewMID Compliance Installation and wiringLocation of terminal covers Installing the terminal coversPM5331/PM5341 default screen Default PM5331/PM5341 display screenMeter firmware version MID-protected setup parametersLock-protected setup parameters Lock-protected setup parametersInitializing the meter Setting up the PM5331/PM5341Navigate to Maint Setup Meter Lock Setting up lock passwordLocking or unlocking the meter Terms Glossary113 114 115 Abbreviations116 117 118 Page Schneider Electric 35, rue Joseph Monier CS