PowerLogicTM EM4800 Series

04/2011

Installation

 

 

For a 416Y/240V (or 380Y/220V) three-phase wye panel with the 230/240V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal B to the voltage disconnect phase B (black wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to neutral bar in the voltage disconnect panel (white wire)

Connect earth wire to earth post using lug provided

Install power supply shorting jumpers (see Figure 8)

Figure 8: PowerLogic EM4800 meter 416Y/240V three-phase wye service connection

2

3

4

5

1

8

7

9

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3)

7 Neutral (white)

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

© 201 Schneider Electric All Rights Reserved

17

Image 23
Contents PowerLogicTM Series EM4800 Digital apparatus complies with Canadian ICES-003 ProcedureIndustry Canada Class B Emission Compliance Statement  Schneider Electric All Rights Reserved Table of Contents Page Introduction PowerLogic EM4800 series System SpecificationsEnvironmental PowerLogic EM4800 series meter specificationsEM4800 Front Panel DisplayPowerLogic EM4833 and PowerLogic EM4880 internal view PowerLogic EM4805 internal view Electrical Standards Compliance Safety PrecautionsInjury Receiving InstallationPre-Installation Checklist Site Planning Access to Power and LightingMounting the PowerLogic EM4800 meter 10.2 cm 04/2011 Installation Shorting block detail 930-110-01-B.00 Inside equipment Power is off Wiring diagrams Electrical personnelFor a single-phase panel with the 120V variant of the meter 201 Schneider Electric All Rights Reserved 930-110-01-B.00 201 Schneider Electric All Rights Reserved 930-110-01-B.00 Phase B CT is optional Delta service meteringInstalling the Current Transformers Source Installing 5A Converters and CTs on the PowerLogic EM4880 Shows a 5A CT connected to the converter PowerLogic EM4880 5A CT connection to converter X1 CT X2 CT Connect the two wiring harnesses to the PowerLogic EM4805 Installing the 5A CTs on the PowerLogic EM4805Remove the shorting block jumper Repeat steps 5 to 7 for remaining CTsPowerLogic EM4805 CT color pair identification Manually Testing Communications Connecting the CommunicationsConnecting the Phone Line Connecting the Ethernet CableDisplay Navigation Normal ModeDiagnostics Mode Pulse InputsRecording the Meter Map Remote DisplayInstallation Record sample shown Maintenance Regulatory Compliance Graphical symbols that appear on equipment Graphical symbolsShows the graphical symbols that appear on the equipment Index PowerLogicTM EM4800 Series 930-110-01-B.00 Index 04/2011 User Notes Page 930-110-01-B.00 04/2011