Schneider Electric E4800 manual Installing the Current Transformers

Page 27

930-110-01-B.00

PowerLogicTM EM4800 Series

04/2011

Installation

 

 

Installing the Current Transformers

The three models of PowerLogic EM4800 meter use current transformers

 

(CTs) with different secondary outputs. The PowerLogic EM4833 meter uses

 

split-core 0.333V CTs (see Figure 12), and the PowerLogic EM4880 meter

 

uses 80mA CTs only (see Figure 13) and is typically used where accuracy is

 

important and long secondary CT wiring is required (up to 300 feet [91.44

 

meters]). The PowerLogic EM4880 meter can also use a 5A CT if a 5A

 

converter has first been installed.

 

For instructions, see “Installing the CTs on the PowerLogic EM4833 and

 

PowerLogic EM4880” on page 22, and “Installing 5A Converters and CTs on

 

the PowerLogic EM4880” on page 23.

 

The PowerLogic EM4805 uses 5A secondary CTs. For instructions, see

 

“Installing the 5A CTs on the PowerLogic EM4805” on page 27.

 

Current transformers connect to the PowerLogic EM4833 and PowerLogic

 

EM4880 meters through the 50-conductor CT cable provided with the meter.

 

Table 2 describes the CT wire pairs and the cable color scheme for each

 

meter point. You can also find this information on the inside of the meter’s

 

outer cover.

 

Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice

 

connectors to attach the CT to a specific meter wire pair. The direction of the

 

energy flow is indicated on the CT.

 

Figure 12: PowerLogic EM4833 split-core 0.333V current transformer

DANGER

2

1

3

THIS SIDE T OWARDS SO UR

CE

 

Legend:

 

1

Source

 

2

Energy flow

 

3

Load

5

4

X1

 

5

X2

 

4

 

© 2011 Schneider Electric All Rights Reserved

21

Image 27
Contents PowerLogicTM Series EM4800 Digital apparatus complies with Canadian ICES-003 ProcedureIndustry Canada Class B Emission Compliance Statement  Schneider Electric All Rights Reserved Table of Contents Page Introduction PowerLogic EM4800 series System SpecificationsEnvironmental PowerLogic EM4800 series meter specificationsEM4800 Front Panel DisplayPowerLogic EM4833 and PowerLogic EM4880 internal view PowerLogic EM4805 internal view Safety Precautions InjuryElectrical Standards Compliance Installation Pre-Installation ChecklistReceiving Site Planning Access to Power and LightingMounting the PowerLogic EM4800 meter 10.2 cm 04/2011 Installation Shorting block detail 930-110-01-B.00 Inside equipment Power is offWiring diagrams Electrical personnelFor a single-phase panel with the 120V variant of the meter 201 Schneider Electric All Rights Reserved 930-110-01-B.00 201 Schneider Electric All Rights Reserved 930-110-01-B.00 Phase B CT is optional Delta service meteringInstalling the Current Transformers Source Installing 5A Converters and CTs on the PowerLogic EM4880 Shows a 5A CT connected to the converter PowerLogic EM4880 5A CT connection to converter X1 CT X2 CT Connect the two wiring harnesses to the PowerLogic EM4805 Installing the 5A CTs on the PowerLogic EM4805Remove the shorting block jumper Repeat steps 5 to 7 for remaining CTsPowerLogic EM4805 CT color pair identification Manually Testing Communications Connecting the CommunicationsConnecting the Phone Line Connecting the Ethernet CableDisplay Navigation Normal ModeDiagnostics Mode Pulse InputsRecording the Meter Map Remote DisplayInstallation Record sample shown Maintenance Regulatory Compliance Graphical symbols Shows the graphical symbols that appear on the equipmentGraphical symbols that appear on equipment Index PowerLogicTM EM4800 Series 930-110-01-B.00 Index 04/2011 User Notes Page 930-110-01-B.00 04/2011