PowerLogicTM EM4800 Series | |
04/2011 | Installation |
|
|
Installing the Current Transformers | The three models of PowerLogic EM4800 meter use current transformers |
| (CTs) with different secondary outputs. The PowerLogic EM4833 meter uses |
| |
| uses 80mA CTs only (see Figure 13) and is typically used where accuracy is |
| important and long secondary CT wiring is required (up to 300 feet [91.44 |
| meters]). The PowerLogic EM4880 meter can also use a 5A CT if a 5A |
| converter has first been installed. |
| For instructions, see “Installing the CTs on the PowerLogic EM4833 and |
| PowerLogic EM4880” on page 22, and “Installing 5A Converters and CTs on |
| the PowerLogic EM4880” on page 23. |
| The PowerLogic EM4805 uses 5A secondary CTs. For instructions, see |
| “Installing the 5A CTs on the PowerLogic EM4805” on page 27. |
| Current transformers connect to the PowerLogic EM4833 and PowerLogic |
| EM4880 meters through the |
| Table 2 describes the CT wire pairs and the cable color scheme for each |
| meter point. You can also find this information on the inside of the meter’s |
| outer cover. |
| Each CT has an X1 (positive) and X2 (neutral) wire pair and uses |
| connectors to attach the CT to a specific meter wire pair. The direction of the |
| energy flow is indicated on the CT. |
| Figure 12: PowerLogic EM4833 |
DANGER
2
1
3
THIS SIDE T OWARDS SO UR
CE
| Legend: | |
| 1 | Source |
| 2 | Energy flow |
| 3 | Load |
5 | 4 | X1 |
| 5 | X2 |
| 4 |
|
© 2011 Schneider Electric All Rights Reserved | 21 |