Schneider Electric E4800 manual Delta service metering, Phase B CT is optional

Page 26

PowerLogicTM EM4800 Series

930-110-01-B.00

Installation

04/2011

 

 

 

Delta service metering

 

To use the PowerLogic EM4800 meter in a Delta service, the line-to-line

 

voltage from the Delta service must be reduced to 120V line-to-line using

 

appropriate potential transformers. Metering a Delta service requires only

 

two potential transformers, and only two CTs for phase A and C. Using the

 

phase B CT is optional.

For a three-phase Delta panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to meter terminal B (black wire)

Connect earth wire to earth post using lug provided (see Figure 11)

Figure 11: PowerLogic EM4800 meter three-phase Delta service connection

2

1

9

3

 

 

4

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

7

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3) 7 J3-B to J3-N shorting wire

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

20

© 201 Schneider Electric All Rights Reserved

Image 26
Contents PowerLogicTM Series EM4800 Procedure Digital apparatus complies with Canadian ICES-003Industry Canada Class B Emission Compliance Statement  Schneider Electric All Rights Reserved Table of Contents Page PowerLogic EM4800 series System Specifications IntroductionPowerLogic EM4800 series meter specifications EnvironmentalFront Panel Display EM4800PowerLogic EM4833 and PowerLogic EM4880 internal view PowerLogic EM4805 internal view Electrical Standards Compliance Safety PrecautionsInjury Receiving InstallationPre-Installation Checklist Access to Power and Lighting Site PlanningMounting the PowerLogic EM4800 meter 10.2 cm 04/2011 Installation Shorting block detail 930-110-01-B.00 Electrical personnel Power is offWiring diagrams Inside equipmentFor a single-phase panel with the 120V variant of the meter 201 Schneider Electric All Rights Reserved 930-110-01-B.00 201 Schneider Electric All Rights Reserved 930-110-01-B.00 Delta service metering Phase B CT is optionalInstalling the Current Transformers Source Installing 5A Converters and CTs on the PowerLogic EM4880 Shows a 5A CT connected to the converter PowerLogic EM4880 5A CT connection to converter X1 CT X2 CT Installing the 5A CTs on the PowerLogic EM4805 Connect the two wiring harnesses to the PowerLogic EM4805Repeat steps 5 to 7 for remaining CTs Remove the shorting block jumperPowerLogic EM4805 CT color pair identification Connecting the Ethernet Cable Connecting the CommunicationsConnecting the Phone Line Manually Testing CommunicationsPulse Inputs Normal ModeDiagnostics Mode Display NavigationRemote Display Recording the Meter MapInstallation Record sample shown Maintenance Regulatory Compliance Graphical symbols that appear on equipment Graphical symbolsShows the graphical symbols that appear on the equipment Index PowerLogicTM EM4800 Series 930-110-01-B.00 Index 04/2011 User Notes Page 930-110-01-B.00 04/2011