Schneider Electric E4800 manual Delta service metering, Phase B CT is optional

Page 26

PowerLogicTM EM4800 Series

930-110-01-B.00

Installation

04/2011

 

 

 

Delta service metering

 

To use the PowerLogic EM4800 meter in a Delta service, the line-to-line

 

voltage from the Delta service must be reduced to 120V line-to-line using

 

appropriate potential transformers. Metering a Delta service requires only

 

two potential transformers, and only two CTs for phase A and C. Using the

 

phase B CT is optional.

For a three-phase Delta panel with the 120V variant of the meter:

Connect meter terminal A to the voltage disconnect phase A (red wire)

Connect meter terminal C to the voltage disconnect phase C (blue wire)

Connect meter neutral terminal to meter terminal B (black wire)

Connect earth wire to earth post using lug provided (see Figure 11)

Figure 11: PowerLogic EM4800 meter three-phase Delta service connection

2

1

9

3

 

 

4

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

7

6

Legend:

1BX cable

2 Earth

3 Phase C (blue)

4 Phase B (black)

5 Shorting jumper

6 Sense voltage terminal block (J3) 7 J3-B to J3-N shorting wire

8 Phase A (red)

9 0.75-inch (1.9-cm) strain relief

20

© 201 Schneider Electric All Rights Reserved

Image 26
Contents PowerLogicTM Series EM4800 Procedure Digital apparatus complies with Canadian ICES-003Industry Canada Class B Emission Compliance Statement  Schneider Electric All Rights Reserved Table of Contents Page PowerLogic EM4800 series System Specifications IntroductionPowerLogic EM4800 series meter specifications EnvironmentalFront Panel Display EM4800PowerLogic EM4833 and PowerLogic EM4880 internal view PowerLogic EM4805 internal view Electrical Standards Compliance Safety PrecautionsInjury Receiving InstallationPre-Installation Checklist Access to Power and Lighting Site PlanningMounting the PowerLogic EM4800 meter 10.2 cm 04/2011 Installation Shorting block detail 930-110-01-B.00 Electrical personnel Power is offWiring diagrams Inside equipmentFor a single-phase panel with the 120V variant of the meter 201 Schneider Electric All Rights Reserved 930-110-01-B.00 201 Schneider Electric All Rights Reserved 930-110-01-B.00 Delta service metering Phase B CT is optionalInstalling the Current Transformers Source Installing 5A Converters and CTs on the PowerLogic EM4880 Shows a 5A CT connected to the converter PowerLogic EM4880 5A CT connection to converter X1 CT X2 CT Installing the 5A CTs on the PowerLogic EM4805 Connect the two wiring harnesses to the PowerLogic EM4805Repeat steps 5 to 7 for remaining CTs Remove the shorting block jumperPowerLogic EM4805 CT color pair identification Connecting the Ethernet Cable Connecting the CommunicationsConnecting the Phone Line Manually Testing CommunicationsPulse Inputs Normal ModeDiagnostics Mode Display NavigationRemote Display Recording the Meter MapInstallation Record sample shown Maintenance Regulatory Compliance Graphical symbols that appear on equipment Graphical symbolsShows the graphical symbols that appear on the equipment Index PowerLogicTM EM4800 Series 930-110-01-B.00 Index 04/2011 User Notes Page 930-110-01-B.00 04/2011
Related manuals
Manual 30 pages 57.56 Kb

E4800 specifications

Schneider Electric's E4800 is a robust solution designed for comprehensive energy management, combining advanced features, innovative technologies, and user-friendly characteristics that cater to the needs of various industries. This device primarily focuses on enhancing efficiency in energy consumption and optimizing operational performance.

One of the standout features of the E4800 is its ability to monitor and manage energy consumption in real-time. This capability allows businesses to identify energy usage patterns, track costs, and gain insights into where energy can be saved. The real-time data analysis supports decision-making, enabling organizations to implement energy-saving strategies effectively.

The E4800 is equipped with an intuitive user interface that simplifies navigation and data interpretation. Users can access detailed analytics and reporting tools that provide visibility into energy performance metrics. This user-friendly aspect ensures that both technical and non-technical staff can utilize the system, fostering a culture of energy efficiency across the organization.

Additionally, Schneider Electric has integrated advanced communication technologies into the E4800. It supports various communication protocols such as Modbus, BACnet, and Ethernet, enabling seamless integration with existing systems and infrastructure. This versatility ensures that organizations can leverage their current investments in technology while upgrading to more advanced energy management solutions.

The E4800 is also designed with scalability in mind. Organizations can easily expand their energy management capabilities as their needs grow. Whether managing a single facility or a multi-site operation, the E4800 can adapt to varying requirements without significant overhauls or disruptions.

Another noteworthy characteristic is its compliance with global standards for energy management and sustainability. By utilizing the E4800, companies can demonstrate their commitment to environmental responsibility and adherence to regulations, which is increasingly important in today’s business landscape.

Lastly, Schneider Electric's E4800 comes with robust support services, ensuring that users can access assistance whenever needed. This commitment to customer service solidifies its position as a reliable solution for energy management.

In summary, Schneider Electric's E4800 offers a comprehensive suite of features designed for effective energy management, leveraging real-time analytics, versatile communication technologies, scalability, compliance with global standards, and excellent customer support, making it an ideal choice for businesses aiming to enhance their energy efficiency and sustainability.