Schneider Electric PM5100 manual Power quality, Harmonics overview, Harmonic content calculations

Page 67

PowerLogic™ PM5100 series user guide

Chapter 9—Power quality

 

 

Chapter 9—Power quality

This section describes the meter’s power quality features and how to access power quality data.

The meter measures voltage and current harmonics up to the 15th harmonic, and calculates Total Harmonic Distortion (THD) and Total Demand Distortion (TDD and tdd).

Harmonics overview

Harmonics are integer multiples of the fundamental frequency of the power system. Harmonics information is valuable for power quality analysis, determining properly rated transformers, maintenance and troubleshooting.

Harmonics measurements include per-phase magnitudes and angles for the fundamental and higher harmonics relative to the fundamental frequency. The meter’s power system setting defines which phases are present and determines how line-to-line or line-to-neutral voltage harmonics and current harmonics are calculated.

Harmonics data provide information to determine how non-linear loads affect the power system. For example, power system harmonics can cause current flow on the neutral conductor, increase heating in electric motors, and eventually damage connected equipment. Power conditioners or harmonic filters can be used to minimize unwanted harmonics.

Total Harmonic Distortion and Total Demand Distortion

Total Harmonic Distortion (THD) is a measure of the total per-phase voltage or current harmonic distortion present in the power system. It provides a general indication of the quality of a waveform. THD is calculated for each phase of both voltage and current.

Total Demand Distortion (TDD) is the per-phase harmonic current distortion against the full load demand of the electrical system. TDD indicates the impact of harmonic distortion in the system. For example, if your system is showing high THD values but a low demand, the impact of harmonic distortion on your system might be insignificant. However at full load, the THD value for the current harmonics is equal to TDD, so this could negatively impact your system.

The meter uses the following series of equations to calculate THD and TDD.

Harmonic content calculations

1. Calculate harmonic content (HC).

HC = (H2)2 + (H3)2 + (H4)2

HC (harmonic content) is equal to the RMS value of all the non-fundamental harmonic components in one phase of the power system.

2. Calculate the harmonic content for current (HCI).

HCI = (HI2)2 + (HI3)2 + (HI4)2

HCI (harmonic content current) is equal to the RMS value of all the non-fundamental current harmonic components (HI2…HIn) in one phase of the power system.

© 2014 Schneider Electric All Rights Reserved

67

Image 67
Contents PowerLogic PM5100 Series Power and Energy Meter Page Please note Important InformationPage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter MID Compliance Chapter AlarmsChapter Measurements CalculationsGlossary Table of Contents PowerLogic PM5100 series user guide Introduction Power and Energy Meter HardwareParts and Accessories Box ContentsIntroduction Before You Begin Safety PrecautionsPowerLogic PM5100 series user guide Functions and Characteristics Models, Features and OptionsFunctions and Characteristics PM5100 Series Models, Features and OptionsTechnical Specifications Environmental Characteristics Mechanical CharacteristicsCommunication Safety precautionsSafety Electromagnetic CompatibilityMeter mounting DimensionMounting the PM5100 Serial No Description Specification Meter wiringMake Part code Description Recommended cables3CT 2CT Wiring DiagramsCurrent Transformer Power systemSymbol Description Direct connect voltage limitsMeter setting Power system setup parameters Power system descriptionSymbol Direct connect maximum Voltage and current input wiringVoltage input protection Current input protectionSerial communications Control power wiringCommunications Balanced system considerationsRS-485 maximum cable length RS-485 wiringRS-485 network configuration RS-485 cableDigital output connections Digital outputsPowerLogic PM5100 series user guide Hardware Reference Heartbeat / communications LED Front panel display and meter setupLED indicators Alarm / energy pulsing LED modesMeter screen menus Notification iconsRelated topics PM5100 display screen menus Menu treeBasic setup screen Front panel meter setupMeter setup screen navigation Configuring the basic setup parametersBasic setup parameters Basic setup menu treeParameter Values Description Communications setup parameters Communications setupSetting up serial communications Serial communications setup menu treeDisplay setup menu tree HMI settingsSetting up the display Setting up regional settingsRegional settings menu tree Setting up the screen passwordsRegional settings setup parameters Password setup parameters Setting the clockLost password Password setup menu treeParameter Format Description Advanced setupClock setup parameters Advanced setup menu treeLED setup parameter Setting up the alarm / energy pulsing LEDAdvanced setup parameters Alarm / energy pulsing LED settings menu treeDemand setup menu tree Output setup Demand setupPower or current demand setup parameters Remote Meter Setup Alarms setupFront panel display and meter setup Displaying data screens Viewing Meter DataViewing meter data from the front panel Meter data display screensEnergy E Power PQSVolts U-V HarmMnMx AlarmTimer UnbalUsing software to view meter data Using ION Setup to view or modify configuration dataClock Input / Output Digital output setupDigital output applications Configuring digital outputs using the front panel Alarm / energy pulsing LED setupDigital output setup menu tree Navigate to I/O configuration Energy Pulsing Input / OutputPowerLogic PM5100 series user guide About Alarms AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsAlarm Priorities Unary AlarmsAlarm Setup Setting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Viewing Alarm Activity and HistoryViewing Active Alarms and Alarm Counters Viewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5100 series user guide Alarms Energy Power factorMeasurements and calculations Real-time readingsPower factor minimum and maximum Power factor min/max conventionPower factor sign convention IEC modeBlock interval demand Power demand calculation methodsIeee mode DemandBlock interval demand example Synchronized demandThermal demand example Current demandPredicted demand Thermal demandPredicted demand example Peak demandTotal Harmonic Distortion and Total Demand Distortion Power qualityHarmonic content calculations Harmonics overviewTDD calculation Viewing harmonics using the front panelDisplaying harmonics data THD and thd calculationsExample 7th to 15th harmonics for line-to-neutral voltage Viewing THD/thd using the front panelPower Quality display screen Viewing TDDRelated topics Verifying accuracy Testing overviewAccuracy test requirements PM5100 Reference device or energy standardEnergy pulsing Location of energy pulsing LEDVerifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses VT and CT considerations Total power limit for alarm / energy LEDTotal power limit for digital output Energy pulsing considerationsVar-hour test points example Typical sources of test errorsTest points Watt-hour test points exampleReset menu tree Meter resetsFront panel meter reset screens Global resetsAlarm counter Option Description Single resetsSingle reset options Alarm counter optionsPowerLogic PM5100 series user guideChapter 11-Meter resets Meter resets Identifying the Firmware Version, Model, and Serial Number Maintenance and UpgradesPassword Recovery Power Meter MemoryMeter Control PowerAdditional Meter Status Information Downloading FirmwareHeartbeat/Comms LED TroubleshootingPotential Problem Possible Cause Possible Solution TroubleshootingGetting Technical Support Register List MID compliance for the meter Specifications relevant to MIDMID Compliance MID overviewMID Compliance Installation and wiringLocation of terminal covers Installing the terminal coversPM5111 default screen Default PM5111 display screenMeter firmware version MID-protected setup parametersLock-protected setup parameters Lock-protected setup parametersInitializing the meter Setting up the PM5111Locking or unlocking the meter Irrecoverable Password Setting up lock passwordTerms GlossaryPowerLogic PM5100 series user guide Abbreviations PowerLogic PM5100 series user guide Page Schneider Electric 35, rue Joseph Monier CS