Schneider Electric PM5100 manual Basic setup menu tree, Basic setup parameters

Page 33

PowerLogic™ PM5100 series user guide

Chapter 4—Front panel display and meter setup

 

 

Basic setup menu tree

Maint

Reset

Meter

Basic

 

Setup

Comm

 

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0000”), then press OK.

3.Navigate to Meter > Basic.

4.Move the cursor to point to the parameter you want to modify, then press Edit.

5.Modify the parameter as required, then press OK.

6.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

Basic setup parameters

Parameter

Values

Description

 

 

 

 

Select the power system type (power transformer) the meter is wired to.

 

 

 

 

1PH2W LN

Single-phase 2-wire line-to-neutral

 

 

 

 

1PH2W LL

Single-phase 2-wire line-to-line

 

 

 

 

1PH3W LL with N

Single-phase 3-wire line-to-line with neutral

 

 

 

 

3PH3W Dlt Ungnd

3-phase 3-wire ungrounded delta

 

 

 

 

3PH3W Dlt Crnr Gnd

3-phase 3-wire corner grounded delta

 

 

 

Power System

3PH3W Wye Ungnd

3-phase 3-wire ungrounded wye

 

 

3PH3W Wye Gnd

3-phase 3-wire grounded wye

 

 

 

 

 

3PH3W Wye Res Gnd

3-phase 3-wire resistance-grounded wye

 

 

 

 

3PH4W Opn Dlt Ctr Tp

3-phase 4-wire center-tapped open delta

 

 

 

 

3PH4W Dlt Ctr Tp

3-phase 4-wire center-tapped delta

 

 

 

 

3PH4W Wye Ungnd

3-phase 4-wire ungrounded wye

 

 

 

 

3PH4W Wye Gnd

3-phase 4-wire grounded wye

 

 

 

 

3PH4W Wye Res Gnd

3-phase 4-wire resistance-grounded wye

 

 

 

 

Select how many voltage transformers (VT) are connected to the electrical power

 

system.

 

VT Connect

Direct Con

Direct connect; no VTs used

 

2VT

2 voltage transformers

 

 

 

 

3VT

3 voltage transformers

 

 

 

VT Primary (V)

1 to 1000000

Enter the size of the VT primary, in Volts.

 

 

 

VT Secondary (V)

100, 110, 115, 120

Select the size of the VT secondary, in Volts

 

 

 

 

Define how many current transformers (CT) are connected to the meter, and

 

which terminals they are connected to.

 

I1

1 CT connected to I1 terminal

 

 

 

 

I2

1 CT connected to I2 terminal

 

 

 

CT on Terminal

I3

1 CT connected to I3 terminal

 

I1 I2

2 CT connected to I1, I2 terminals

 

 

 

 

I1 I3

2 CT connected to I1, I3 terminals

 

 

 

 

I2 I3

2 CT connected to I2, I3 terminals

 

 

 

 

I1 I2 I3

3 CT connected to I1, I2, I3 terminals

 

 

 

CT Primary (A)

1 to 32767

Enter the size of the CT primary, in Amps.

 

 

 

CT Secondary (A)

1, 5

Select the size of the CT secondary, in Amps.

 

 

 

Sys Frequency (Hz)

50, 60

Select the frequency of the electrical power

system, in Hz.

 

 

Phase Rotation

ABC, CBA

Select the phase rotation of the 3-phase system.

 

 

 

7. Press to exit. Press Yes to save your changes.

© 2014 Schneider Electric All Rights Reserved

33

Image 33
Contents PowerLogic PM5100 Series Power and Energy Meter Page Please note Important InformationPage Introduction Chapter Safety Precau Tions EnceHardware Refer Chapter Measurements Chapter AlarmsCalculations Chapter MID ComplianceGlossary Table of Contents PowerLogic PM5100 series user guide Parts and Accessories Power and Energy Meter HardwareBox Contents IntroductionIntroduction Before You Begin Safety PrecautionsPowerLogic PM5100 series user guide Functions and Characteristics Models, Features and OptionsPM5100 Series Models, Features and Options Functions and CharacteristicsTechnical Specifications Environmental Characteristics Mechanical CharacteristicsSafety Safety precautionsElectromagnetic Compatibility CommunicationMeter mounting DimensionMounting the PM5100 Serial No Description Specification Meter wiringMake Part code Description Recommended cables3CT 2CT Wiring DiagramsSymbol Description Power systemDirect connect voltage limits Current TransformerPower system setup parameters Power system description Meter settingSymbol Voltage input protection Voltage and current input wiringCurrent input protection Direct connect maximumCommunications Control power wiringBalanced system considerations Serial communicationsRS-485 network configuration RS-485 wiringRS-485 cable RS-485 maximum cable lengthDigital output connections Digital outputsPowerLogic PM5100 series user guide Hardware Reference LED indicators Front panel display and meter setupAlarm / energy pulsing LED modes Heartbeat / communications LEDNotification icons Meter screen menusRelated topics PM5100 display screen menus Menu treeMeter setup screen navigation Front panel meter setupConfiguring the basic setup parameters Basic setup screenBasic setup menu tree Basic setup parametersParameter Values Description Setting up serial communications Communications setupSerial communications setup menu tree Communications setup parametersSetting up the display HMI settingsSetting up regional settings Display setup menu treeSetting up the screen passwords Regional settings menu treeRegional settings setup parameters Lost password Setting the clockPassword setup menu tree Password setup parametersClock setup parameters Advanced setupAdvanced setup menu tree Parameter Format DescriptionAdvanced setup parameters Setting up the alarm / energy pulsing LEDAlarm / energy pulsing LED settings menu tree LED setup parameterOutput setup Demand setup Demand setup menu treePower or current demand setup parameters Remote Meter Setup Alarms setupFront panel display and meter setup Viewing meter data from the front panel Viewing Meter DataMeter data display screens Displaying data screensVolts U-V Power PQSHarm Energy ETimer AlarmUnbal MnMxUsing ION Setup to view or modify configuration data Using software to view meter dataClock Digital output setup Input / OutputDigital output applications Alarm / energy pulsing LED setup Configuring digital outputs using the front panelDigital output setup menu tree Navigate to I/O configuration Energy Pulsing Input / OutputPowerLogic PM5100 series user guide Alarms About AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsAlarm Priorities Unary AlarmsAlarm Setup Setting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Viewing Alarm Activity and HistoryViewing Active Alarms and Alarm Counters Viewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5100 series user guide Alarms Measurements and calculations Power factorReal-time readings EnergyPower factor sign convention Power factor min/max conventionIEC mode Power factor minimum and maximumIeee mode Power demand calculation methodsDemand Block interval demandBlock interval demand example Synchronized demandPredicted demand Current demandThermal demand Thermal demand examplePredicted demand example Peak demandHarmonic content calculations Power qualityHarmonics overview Total Harmonic Distortion and Total Demand DistortionDisplaying harmonics data Viewing harmonics using the front panelTHD and thd calculations TDD calculationPower Quality display screen Viewing THD/thd using the front panelViewing TDD Example 7th to 15th harmonics for line-to-neutral voltageRelated topics Testing overview Verifying accuracyAccuracy test requirements Energy pulsing Reference device or energy standardLocation of energy pulsing LED PM5100Verifying accuracy test Calculating total power Percent error calculationCalculating the number of required pulses Total power limit for digital output Total power limit for alarm / energy LEDEnergy pulsing considerations VT and CT considerationsTest points Typical sources of test errorsWatt-hour test points example Var-hour test points exampleFront panel meter reset screens Meter resetsGlobal resets Reset menu treeSingle reset options Single resetsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5100 series user guideChapter 11-Meter resets Meter resets Password Recovery Maintenance and UpgradesPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberAdditional Meter Status Information Control PowerDownloading Firmware MeterHeartbeat/Comms LED TroubleshootingTroubleshooting Potential Problem Possible Cause Possible SolutionGetting Technical Support Register List MID Compliance Specifications relevant to MIDMID overview MID compliance for the meterMID Compliance Installation and wiringPM5111 default screen Installing the terminal coversDefault PM5111 display screen Location of terminal coversLock-protected setup parameters MID-protected setup parametersLock-protected setup parameters Meter firmware versionSetting up the PM5111 Initializing the meterLocking or unlocking the meter Irrecoverable Password Setting up lock passwordTerms GlossaryPowerLogic PM5100 series user guide Abbreviations PowerLogic PM5100 series user guide Page Schneider Electric 35, rue Joseph Monier CS