Schneider Electric PM5100 manual Verifying accuracy test

Page 73

PowerLogic™ PM5100 series user guide

Chapter 10—Verifying accuracy

 

 

Verifying accuracy test

The following are guidelines for testing the meter; your meter shop may have specific testing methods.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.

Turn off all power supplying this device before working on it.

Always use a properly rated voltage sensing device to confirm that all power is off.

Do not exceed the device’s ratings for maximum limits.

Verify the device’s power source meets the specifications for your device’s power supply.

Failure to follow these instructions will result in death or serious injury.

1.Turn off power to all test equipment. Use a properly rated voltage sensing device to confirm power is off.

2.Connect the test voltage and current source to the reference device or energy standard. Ensure all voltage inputs to the meter under test are connected in parallel and all currents inputs are connected in series.

Connecting the meter to the reference standard and test equipment

Reference device or energy standard

V1 V2 V3 VN

I1

I2

I3

 

 

 

+ -

+ -

+ -

 

 

 

Test voltage and

current source

V1 V2 V3 VN

 

I1

I2

I3

 

+ -

+ -

+ -

 

 

I1

I2

I3

 

 

+- + - + -

V1V2 V3 VN

Meter under test

3.Connect the control equipment used for counting the standard output pulses using one of these methods:

Alarm / energy LED

Align the red light sensor on the standard test bench armature over the front

panel alarm / energy LED.

 

 

 

Digital output

Connect the meter’s digital output to the standard test bench pulse counting

connections.

 

NOTE: When selecting which method to use, be aware that the Alarm / energy LED and digital outputs have different pulse rate limits. See “Energy pulsing considerations” on page 75 for details.

4.Before performing the verification test, let the test equipment power up the meter and apply voltage for at least 30 seconds. This helps stabilize the internal circuitry of the meter.

5.Set the meter’s power system to 3PH4W Wye Gnd (3-phase, 4 wire Wye with ground).

© 2014 Schneider Electric All Rights Reserved

73

Image 73
Contents PowerLogic PM5100 Series Power and Energy Meter Page Please note Important InformationPage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Measurements Chapter AlarmsCalculations Chapter MID ComplianceGlossary Table of Contents PowerLogic PM5100 series user guide Parts and Accessories Power and Energy Meter HardwareBox Contents IntroductionIntroduction Before You Begin Safety PrecautionsPowerLogic PM5100 series user guide Functions and Characteristics Models, Features and OptionsPM5100 Series Models, Features and Options Functions and CharacteristicsTechnical Specifications Environmental Characteristics Mechanical CharacteristicsSafety Safety precautionsElectromagnetic Compatibility CommunicationMeter mounting DimensionMounting the PM5100 Serial No Description Specification Meter wiringMake Part code Description Recommended cables3CT 2CT Wiring DiagramsSymbol Description Power systemDirect connect voltage limits Current TransformerMeter setting Power system setup parameters Power system descriptionSymbol Voltage input protection Voltage and current input wiringCurrent input protection Direct connect maximumCommunications Control power wiringBalanced system considerations Serial communicationsRS-485 network configuration RS-485 wiringRS-485 cable RS-485 maximum cable lengthDigital output connections Digital outputsPowerLogic PM5100 series user guide Hardware Reference LED indicators Front panel display and meter setupAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics PM5100 display screen menus Menu treeMeter setup screen navigation Front panel meter setupConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Setting up serial communications Communications setupSerial communications setup menu tree Communications setup parametersSetting up the display HMI settingsSetting up regional settings Display setup menu treeRegional settings menu tree Setting up the screen passwordsRegional settings setup parameters Lost password Setting the clockPassword setup menu tree Password setup parametersClock setup parameters Advanced setupAdvanced setup menu tree Parameter Format DescriptionAdvanced setup parameters Setting up the alarm / energy pulsing LEDAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Output setup Demand setupPower or current demand setup parameters Remote Meter Setup Alarms setupFront panel display and meter setup Viewing meter data from the front panel Viewing Meter DataMeter data display screens Displaying data screensVolts U-V Power PQSHarm Energy ETimer AlarmUnbal MnMxUsing software to view meter data Using ION Setup to view or modify configuration dataClock Input / Output Digital output setupDigital output applications Configuring digital outputs using the front panel Alarm / energy pulsing LED setupDigital output setup menu tree Navigate to I/O configuration Energy Pulsing Input / OutputPowerLogic PM5100 series user guide About Alarms AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsAlarm Priorities Unary AlarmsAlarm Setup Setting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Viewing Alarm Activity and HistoryViewing Active Alarms and Alarm Counters Viewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5100 series user guide Alarms Measurements and calculations Power factorReal-time readings EnergyPower factor sign convention Power factor min/max conventionIEC mode Power factor minimum and maximumIeee mode Power demand calculation methodsDemand Block interval demandBlock interval demand example Synchronized demandPredicted demand Current demandThermal demand Thermal demand examplePredicted demand example Peak demandHarmonic content calculations Power qualityHarmonics overview Total Harmonic Distortion and Total Demand DistortionDisplaying harmonics data Viewing harmonics using the front panelTHD and thd calculations TDD calculationPower Quality display screen Viewing THD/thd using the front panelViewing TDD Example 7th to 15th harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Energy pulsing Reference device or energy standardLocation of energy pulsing LED PM5100Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for digital output Total power limit for alarm / energy LEDEnergy pulsing considerations VT and CT considerationsTest points Typical sources of test errorsWatt-hour test points example Var-hour test points exampleFront panel meter reset screens Meter resetsGlobal resets Reset menu treeSingle reset options Single resetsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5100 series user guideChapter 11-Meter resets Meter resets Password Recovery Maintenance and UpgradesPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberAdditional Meter Status Information Control PowerDownloading Firmware MeterHeartbeat/Comms LED TroubleshootingPotential Problem Possible Cause Possible Solution TroubleshootingGetting Technical Support Register List MID Compliance Specifications relevant to MIDMID overview MID compliance for the meterMID Compliance Installation and wiringPM5111 default screen Installing the terminal coversDefault PM5111 display screen Location of terminal coversLock-protected setup parameters MID-protected setup parametersLock-protected setup parameters Meter firmware versionInitializing the meter Setting up the PM5111Locking or unlocking the meter Irrecoverable Password Setting up lock passwordTerms GlossaryPowerLogic PM5100 series user guide Abbreviations PowerLogic PM5100 series user guide Page Schneider Electric 35, rue Joseph Monier CS