Chapter 10—Verifying accuracy

 

 

Where:

EM = energy measured by the meter under test

ES = energy measured by the reference device or energy standard.

NOTE: If accuracy verification reveals inaccuracies in your meter, they may be caused by typical sources of test errors. If there are no sources of test errors present, please contact your local Schneider Electric representative.

Energy pulsing considerations

The meter’s alarm / energy LED and digital outputs are capable of energy pulsing within the following limits:

Energy pulsing limits

Description

Alarm / energy LED

 

Digital output

 

 

 

 

Maximum pulse frequency

50 Hz

 

25 Hz

 

 

 

 

Minimum pulse constant

1 pulse per k_h

 

 

 

Maximum pulse constant

9,999,999 pulses per k_h

 

 

 

 

The pulse rate depends on the voltage, current and PF of the input signal source, the number of phases, and the VT and CT ratios.

If Ptot is the instantaneous power (in kW) and K is the pulse constant (in pulses per k_h), then the pulse period is:

Pulse period (in seconds) =

3600

=

1

K-------------------× Ptot

Pulse--------------------------------------------------frequency (Hz)

VT and CT considerations

The test points are always taken at the secondary side, regardless of whether VTs or CTs are used. Ptot is derived from the values of the voltage and current inputs at the secondary side, and takes into account the VT and CT ratios.

If VTs and CTs are used, you must include their primary and secondary ratings in the equation. For example, in a balanced 3-phase Wye system with VTs and CTs:

Ptot = 3 × VLN ×

---------------------------------VT primary

× I ×

----------------------------------CT primary

× PF ×

------------------1 kW

 

VT secondary

 

CT secondary

 

1000 W

Total power limit for alarm / energy LED

Given the maximum pulse constant (Kmax) you can enter is 9,999,999 pulses per kWh, and the maximum pulse frequency for the alarm / energy LED is 83 Hz, the maximum total power (Max Ptot) the alarm / energy LED’s energy pulsing circuitry can handle is

29.88 Watts:

3600 × (Maximum pulse frequency) 3600 × 83

Maximum Ptot = -------------------------------------------------------------------------------------- = ----------------------- = 0.02988 kW

Kmax9,999,999

Total power limit for digital output

Given the maximum pulse constant (Kmax) you can enter is 9,999,999 pulses per kWh, and the maximum pulse frequency for the digital output is 25 Hz, the maximum total power (Max Ptot) the digital input’s energy pulsing circuitry can handle is 9 Watts:

© 2014 Schneider Electric All Rights Reserved

75

Image 75
Contents PowerLogic PM5100 Series Power and Energy Meter Page Please note Important InformationPage Introduction Chapter Safety Precau Tions EnceHardware Refer Chapter MID Compliance Chapter AlarmsChapter Measurements CalculationsGlossary Table of Contents PowerLogic PM5100 series user guide Introduction Power and Energy Meter HardwareParts and Accessories Box ContentsIntroduction Before You Begin Safety PrecautionsPowerLogic PM5100 series user guide Functions and Characteristics Models, Features and OptionsFunctions and Characteristics PM5100 Series Models, Features and OptionsTechnical Specifications Environmental Characteristics Mechanical CharacteristicsCommunication Safety precautionsSafety Electromagnetic CompatibilityMeter mounting DimensionMounting the PM5100 Serial No Description Specification Meter wiringMake Part code Description Recommended cables3CT 2CT Wiring DiagramsCurrent Transformer Power systemSymbol Description Direct connect voltage limitsPower system setup parameters Power system description Meter settingSymbol Direct connect maximum Voltage and current input wiringVoltage input protection Current input protectionSerial communications Control power wiringCommunications Balanced system considerationsRS-485 maximum cable length RS-485 wiringRS-485 network configuration RS-485 cableDigital output connections Digital outputsPowerLogic PM5100 series user guide Hardware Reference Heartbeat / communications LED Front panel display and meter setupLED indicators Alarm / energy pulsing LED modesNotification icons Meter screen menusRelated topics PM5100 display screen menus Menu treeBasic setup screen Front panel meter setupMeter setup screen navigation Configuring the basic setup parametersBasic setup menu tree Basic setup parametersParameter Values Description Communications setup parameters Communications setupSetting up serial communications Serial communications setup menu treeDisplay setup menu tree HMI settingsSetting up the display Setting up regional settingsSetting up the screen passwords Regional settings menu treeRegional settings setup parameters Password setup parameters Setting the clockLost password Password setup menu treeParameter Format Description Advanced setupClock setup parameters Advanced setup menu treeLED setup parameter Setting up the alarm / energy pulsing LEDAdvanced setup parameters Alarm / energy pulsing LED settings menu treeOutput setup Demand setup Demand setup menu treePower or current demand setup parameters Remote Meter Setup Alarms setupFront panel display and meter setup Displaying data screens Viewing Meter DataViewing meter data from the front panel Meter data display screensEnergy E Power PQSVolts U-V HarmMnMx AlarmTimer UnbalUsing ION Setup to view or modify configuration data Using software to view meter dataClock Digital output setup Input / OutputDigital output applications Alarm / energy pulsing LED setup Configuring digital outputs using the front panelDigital output setup menu tree Navigate to I/O configuration Energy Pulsing Input / OutputPowerLogic PM5100 series user guide Alarms About AlarmsSecond Alarms Alarm List of Standard 1-Second Over/Under AlarmsAlarm Priorities Unary AlarmsAlarm Setup Setting Up 1-Second Alarms Setting Up 1-Second Alarms Setting Up Unary Alarms Viewing Alarm Activity and HistoryViewing Active Alarms and Alarm Counters Viewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5100 series user guide Alarms Energy Power factorMeasurements and calculations Real-time readingsPower factor minimum and maximum Power factor min/max conventionPower factor sign convention IEC modeBlock interval demand Power demand calculation methodsIeee mode DemandBlock interval demand example Synchronized demandThermal demand example Current demandPredicted demand Thermal demandPredicted demand example Peak demandTotal Harmonic Distortion and Total Demand Distortion Power qualityHarmonic content calculations Harmonics overviewTDD calculation Viewing harmonics using the front panelDisplaying harmonics data THD and thd calculationsExample 7th to 15th harmonics for line-to-neutral voltage Viewing THD/thd using the front panelPower Quality display screen Viewing TDDRelated topics Testing overview Verifying accuracyAccuracy test requirements PM5100 Reference device or energy standardEnergy pulsing Location of energy pulsing LEDVerifying accuracy test Calculating total power Percent error calculationCalculating the number of required pulses VT and CT considerations Total power limit for alarm / energy LEDTotal power limit for digital output Energy pulsing considerationsVar-hour test points example Typical sources of test errorsTest points Watt-hour test points exampleReset menu tree Meter resetsFront panel meter reset screens Global resetsAlarm counter Option Description Single resetsSingle reset options Alarm counter optionsPowerLogic PM5100 series user guideChapter 11-Meter resets Meter resets Identifying the Firmware Version, Model, and Serial Number Maintenance and UpgradesPassword Recovery Power Meter MemoryMeter Control PowerAdditional Meter Status Information Downloading FirmwareHeartbeat/Comms LED TroubleshootingTroubleshooting Potential Problem Possible Cause Possible SolutionGetting Technical Support Register List MID compliance for the meter Specifications relevant to MIDMID Compliance MID overviewMID Compliance Installation and wiringLocation of terminal covers Installing the terminal coversPM5111 default screen Default PM5111 display screenMeter firmware version MID-protected setup parametersLock-protected setup parameters Lock-protected setup parametersSetting up the PM5111 Initializing the meterLocking or unlocking the meter Irrecoverable Password Setting up lock passwordTerms GlossaryPowerLogic PM5100 series user guide Abbreviations PowerLogic PM5100 series user guide Page Schneider Electric 35, rue Joseph Monier CS