Schneider Electric PM5100 manual Test points, Typical sources of test errors

Page 76

Chapter 10—Verifying accuracyPowerLogic™ PM5100 series user guide

3600 × (Maximum pulse frequency) 3600 × 25 Maximum Ptot = -------------------------------------------------------------------------------------- = ----------------------- = 0.009 kW

Kmax9,999,999

Test points

The meter should be tested at full and light loads and at lagging (inductive) power factors to help ensure testing over the entire range of the meter. The test amperage and voltage input rating are labeled on the meter. Refer to the installation sheet or data sheet for your meter’s nominal current, voltage and frequency specifications.

Watt-hour test points example

Watt-hour test point

Sample accuracy verification test point

 

 

Full load

100% to 200% of the nominal current, 100% of the nominal voltage and nominal

frequency at unity power factor or one (1).

 

Light load

10% of the nominal current, 100% of the nominal voltage and nominal frequency

at unity power factor or one (1).

 

Inductive load (lagging

100% of the nominal current, 100% of the nominal voltage and nominal frequency

power factor)

at 0.50 lagging power factor (current lagging voltage by 60° phase angle).

Var-hour test points example

Var-hour test point

Sample accuracy verification test point

 

 

Full load

100% to 200% of the nominal current, 100% of the nominal voltage and nominal

frequency at zero power factor (current lagging voltage by 90° phase angle).

 

Light load

10% of the nominal current, 100% of the nominal voltage and nominal frequency

at zero power factor (current lagging voltage by 90° phase angle).

 

Inductive load (lagging

100% of the nominal current, 100% of the nominal voltage and nominal frequency

power factor)

at 0.87 lagging power factor (current lagging voltage by 30° phase angle).

Typical sources of test errors

If excessive errors are observed during accuracy testing, examine your test setup and test procedures to eliminate typical sources of measurement errors:

Loose connections of voltage or current circuits, often caused by worn-out contacts or terminals. Inspect terminals of test equipment, cables, test harness and the meter under test.

Meter ambient temperature is significantly different than 23 °C (73 °F).

Floating (ungrounded) neutral voltage terminal in any configuration with unbalanced phase voltages.

Inadequate meter control power, resulting in the meter resetting during the test procedure.

Ambient light interference or sensitivity issues with the optical sensor.

Unstable power source causing energy pulsing fluctuations.

Incorrect test setup: not all phases connected to the reference device or the energy standard. All phases connected to the meter under test should also be connected to the reference meter/standard.

Moisture (condensing humidity), debris or pollution present in the meter under test.

76

© 2014 Schneider Electric All Rights Reserved

Image 76
Contents PowerLogic PM5100 Series Power and Energy Meter Page Important Information Please notePage Ence Introduction Chapter Safety Precau TionsHardware Refer Chapter Alarms Chapter MeasurementsCalculations Chapter MID ComplianceGlossary Table of Contents PowerLogic PM5100 series user guide Power and Energy Meter Hardware Parts and AccessoriesBox Contents IntroductionIntroduction Safety Precautions Before You BeginPowerLogic PM5100 series user guide Models, Features and Options Functions and CharacteristicsPM5100 Series Models, Features and Options Functions and CharacteristicsTechnical Specifications Mechanical Characteristics Environmental CharacteristicsSafety precautions SafetyElectromagnetic Compatibility CommunicationDimension Meter mountingMounting the PM5100 Meter wiring Serial No Description SpecificationRecommended cables Make Part code DescriptionWiring Diagrams 3CT 2CTPower system Symbol DescriptionDirect connect voltage limits Current TransformerMeter setting Power system setup parameters Power system descriptionSymbol Voltage and current input wiring Voltage input protectionCurrent input protection Direct connect maximumControl power wiring CommunicationsBalanced system considerations Serial communicationsRS-485 wiring RS-485 network configurationRS-485 cable RS-485 maximum cable lengthDigital outputs Digital output connectionsPowerLogic PM5100 series user guide Hardware Reference Front panel display and meter setup LED indicatorsAlarm / energy pulsing LED modes Heartbeat / communications LEDMeter screen menus Notification iconsRelated topics Menu tree PM5100 display screen menusFront panel meter setup Meter setup screen navigationConfiguring the basic setup parameters Basic setup screenBasic setup parameters Basic setup menu treeParameter Values Description Communications setup Setting up serial communicationsSerial communications setup menu tree Communications setup parametersHMI settings Setting up the displaySetting up regional settings Display setup menu treeRegional settings menu tree Setting up the screen passwordsRegional settings setup parameters Setting the clock Lost passwordPassword setup menu tree Password setup parametersAdvanced setup Clock setup parametersAdvanced setup menu tree Parameter Format DescriptionSetting up the alarm / energy pulsing LED Advanced setup parametersAlarm / energy pulsing LED settings menu tree LED setup parameterDemand setup menu tree Output setup Demand setupPower or current demand setup parameters Alarms setup Remote Meter SetupFront panel display and meter setup Viewing Meter Data Viewing meter data from the front panelMeter data display screens Displaying data screensPower PQS Volts U-VHarm Energy EAlarm TimerUnbal MnMxUsing software to view meter data Using ION Setup to view or modify configuration dataClock Input / Output Digital output setupDigital output applications Configuring digital outputs using the front panel Alarm / energy pulsing LED setupDigital output setup menu tree Navigate to I/O configuration Energy Pulsing Input / OutputPowerLogic PM5100 series user guide About Alarms AlarmsSecond Alarms List of Standard 1-Second Over/Under Alarms AlarmUnary Alarms Alarm PrioritiesAlarm Setup Setting Up 1-Second Alarms Setting Up 1-Second Alarms Viewing Alarm Activity and History Setting Up Unary AlarmsViewing Active Alarms and Alarm Counters Viewing Unacknowledged Alarms and the Alarm History Log PowerLogic PM5100 series user guide Alarms Power factor Measurements and calculationsReal-time readings EnergyPower factor min/max convention Power factor sign conventionIEC mode Power factor minimum and maximumPower demand calculation methods Ieee modeDemand Block interval demandSynchronized demand Block interval demand exampleCurrent demand Predicted demandThermal demand Thermal demand examplePeak demand Predicted demand examplePower quality Harmonic content calculationsHarmonics overview Total Harmonic Distortion and Total Demand DistortionViewing harmonics using the front panel Displaying harmonics dataTHD and thd calculations TDD calculationViewing THD/thd using the front panel Power Quality display screenViewing TDD Example 7th to 15th harmonics for line-to-neutral voltageRelated topics Verifying accuracy Testing overviewAccuracy test requirements Reference device or energy standard Energy pulsingLocation of energy pulsing LED PM5100 Verifying accuracy test Percent error calculation Calculating total powerCalculating the number of required pulses Total power limit for alarm / energy LED Total power limit for digital outputEnergy pulsing considerations VT and CT considerationsTypical sources of test errors Test pointsWatt-hour test points example Var-hour test points exampleMeter resets Front panel meter reset screensGlobal resets Reset menu treeSingle resets Single reset optionsAlarm counter options Alarm counter Option DescriptionPowerLogic PM5100 series user guideChapter 11-Meter resets Meter resets Maintenance and Upgrades Password RecoveryPower Meter Memory Identifying the Firmware Version, Model, and Serial NumberControl Power Additional Meter Status InformationDownloading Firmware MeterTroubleshooting Heartbeat/Comms LEDPotential Problem Possible Cause Possible Solution TroubleshootingGetting Technical Support Register List Specifications relevant to MID MID ComplianceMID overview MID compliance for the meterInstallation and wiring MID ComplianceInstalling the terminal covers PM5111 default screenDefault PM5111 display screen Location of terminal coversMID-protected setup parameters Lock-protected setup parametersLock-protected setup parameters Meter firmware versionInitializing the meter Setting up the PM5111Locking or unlocking the meter Setting up lock password Irrecoverable PasswordGlossary TermsPowerLogic PM5100 series user guide Abbreviations PowerLogic PM5100 series user guide Page Schneider Electric 35, rue Joseph Monier CS