Protect PV.630 Operating Instructions

6.2Table of Faults

The monitoring systems listed below will cause the inverter to switch off, are self- acknowledging or signalling and are shown on the DOU with corresponding plain text:

Temperature monitoring systems

Fault/Message

Deac-

Self-

Signalling

DOU message

 

tivat-ing

acknow-led

 

 

 

 

ging

 

 

IGBT 1 stack temperature warning

 

 

X

!Equipment temperature fault!

 

 

 

 

 

IGBT 2 stack temperature warning

 

 

X

!Equipment temperature fault!

 

 

 

 

 

IGBT 1 stack temperature fault

 

X

 

#Equipment temperature fault#

 

 

 

 

 

IGBT 2 stack temperature fault

 

X

 

#Equipment temperature fault#

 

 

 

 

 

IGBT supply air undertemperature

 

 

X

!Ambient temperature fault!

 

 

 

 

 

IGBT supply air temperature

 

 

X

!Ambient temperature fault!

warning

 

 

 

 

 

 

 

 

 

IGBT supply air temperature fault

 

X

 

#Ambient temperature fault#

 

 

 

 

 

Unit exhaust air 1

 

 

X

!Equipment temperature fault!

temperature warning

 

 

 

 

 

 

 

 

 

Unit exhaust air 2

 

 

X

!Equipment temperature fault!

temperature warning

 

 

 

 

 

 

 

 

 

Unit exhaust air 1

 

X

 

#Equipment temperature fault#

temperature fault

 

 

 

 

 

 

 

 

 

Unit exhaust air 2

 

X

 

#Equipment temperature fault#

temperature fault

 

 

 

 

Equipment supply air under-

 

 

X

!Ambient temperature fault!

temperature

 

 

 

 

 

 

 

 

 

Unit supply air temperature warn-

 

 

X

!Ambient temperature fault!

ing

 

 

 

 

 

 

 

 

 

Unit supply air temperature fault

 

X

 

#Ambient temperature fault#

 

 

 

 

 

Temperature sensor fault

 

X

 

#Temperature sensor fault#

IGBT 1 stack

 

 

 

 

Temperature sensor fault

 

X

 

#Temperature sensor fault#

IGBT 2 stack

 

 

 

 

 

 

 

 

 

Temperature sensor fault

 

 

X

#Temperature sensor fault#

IGBT supply air temperature

 

 

 

 

Temperature sensor fault

 

 

X

#Temperature sensor fault#

unit exhaust air 1 temperature

 

 

 

 

 

 

 

 

 

Temperature sensor fault

 

 

X

#Temperature sensor fault#

unit exhaust air 2 temperature

 

 

 

 

 

 

 

 

 

Temperature sensor fault unit

 

 

X

#Temperature sensor fault#

supply air temperature

 

 

 

 

 

 

 

 

 

IGBT difference current deviation

 

 

X

!Difference current deviation!

 

 

 

 

 

42 of 72

8000047961 BAL

Page 46
Image 46
AEG PV.630 manual Table of Faults, Temperature monitoring systems