Protect PV.630 Operating Instructions

IGBT temperature > limit value

Initialisation

Maximum speed,

minimum time!

Minimum time elapsed

Variable speed

depending on IGBT

temperature

IGBT temperature

<limit value

Fan switched off

Figure 8

Fan control

5.2.5Parameters of Inverter Stack Fan Control

IGBT temperature limit value for switching off the fan:

If the highest IGBT temperature falls below this limit value, the fan is switched off.

IGBT temperature limits and fan speeds, x-y coordinates for determining variable speed:

The variable fan speed is determined by a linear x-y characteristic on the basis of these values.

IGBT temperature limit:

If the IGBT temperature rises above the lower limit value, the fan that was previously switched off is run at maximum speed for the minimum time.

Minimum time, maximum speed:

If the minimum time has elapsed, the fan is controlled variably us- ing the measured IGBT temperature.

5.3Insulation Monitoring and Earthing of PV Cells

5.3.1General

Insulation measurements and tests are carried out with an inte- grated isometer. This device detects and checks the insulation re- sistance.

The insulation resistance detected is compared with two limit val- ues stored in the isometer. If the insulation resistance is below one of the limit values, the unit generates a signal. If the limit value is below the other limit value, the device generates a second signal. The limit values can be modified on the isometer.

The two signals are sent to the equipment control. Signalling faults are generated from the two isometer signals (Chapter 6).