Protect PV.630 Operating Instructions

CAN I/O monitoring systems

Fault/Message

Deac-

Self-

Signalling

DOU message

 

tivat-ing

acknow-led

 

 

 

 

ging

 

 

Feedback signal

 

 

X

Q4.x: !Switch feedback fault!

DC load interrupter switch Q4.1

 

 

 

 

 

 

 

 

 

Switch position Q4.1

 

 

X

Q4.x: Switch open

 

 

 

 

 

Feedback signal

 

 

X

K21: !Switch feedback fault!

K21 earthing PV cells

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

!Miniature circuit breaker tripped!

F21 earthing circuit breaker

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

!Overvoltage protection tripped!

F81 surge voltage arrester DC

 

 

 

 

input

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

!Insulation monitor warning!

insulation monitor level 1

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

!Insulation monitor alarm!

insulation monitor level 2

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

F83/84: !Miniature circuit breaker

F83/F84 surge voltage arrester AC

 

 

 

tripped!

anti-condensation heater

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

F60: !Miniature circuit breaker

F60 auxiliary power supply mains 2

 

 

 

tripped!

 

 

 

 

 

Monitoring

 

 

X

F61: !Miniature circuit breaker

F61 independent power supply

 

 

 

tripped!

mains 1

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

Q26: Switch open

Q26 AC mains disconnector

 

 

 

 

 

 

 

 

 

Monitoring

 

 

X

!Unit cabinet door open!

unit cabinet door

 

 

 

 

 

 

 

 

 

Monitoring communication CAN

 

 

X

!Communication fault with I/O

I/O AC cabinet

 

 

 

control!

 

 

 

 

 

Monitoring communication CAN

 

 

X

!Communication fault with I/O

I/O DC cabinet

 

 

 

control!

 

 

 

 

 

Monitoring

X

 

 

#I/O parameter error#

CAN I/O parameters

 

 

 

 

 

 

 

 

 

8000047961 BAL

43 of 72

Page 47
Image 47
AEG PV.630 manual Can I/O monitoring systems Fault/Message