Protect PV.630 Installation and Start-up

5.1

External Connections

 

 

 

 

 

 

 

 

Establish the connections in accordance with the circuit

 

 

i

diagram provided. The mains connection line for the inde-

 

 

pendent power supply must be protected by the circuit

 

 

breaker specified in the technical data sheet. See the cir-

 

 

cuit diagram and the technical data sheet for possible

 

 

 

connection cross-sections.

 

 

 

 

DANGER

System not installed correctly!

Risk to life due to electric shock.

Only trained and qualified skilled personnel who are authorised to install medium-voltage systems may con- nect such equipment.

Wear personal protective equipment.

Power terminals

-X41:1L+, 1L-

DC connection

Maximum 185 mm²

to

 

 

-X41:8L+, 8L-

 

 

 

 

 

-X3:U, V, W

Mains connection

Maximum 3x150 mm²/phase

 

 

 

PE

Earth connection

Maximum 2x120 mm²

 

 

 

X6:1, 2

Partner master

Maximum 4x95 mm²/pole

 

 

 

X6:3, 4

Partner slave

Maximum 4x95 mm²/pole

 

 

 

Control/Monitoring terminals

 

-E1:1, PE, 2

Auxiliary power supply 2-phase 230 VAC

 

 

-X13:U, N, PE

230 V output ±20% maximum 400 VA

 

 

 

-X26:1, 2, 3, 4

Input Q26 external

 

 

 

-X33:1, 2

Signals (NC contact of S1, system stop)

 

 

 

-A12-X3, X4, X5

Remote signalling

 

 

 

 

-A13-X3, X4

Remote signalling

 

 

 

-A20-X3:1, 2, 3

Partner mode (optional)

 

 

 

Designated cable:

See cable diagram

14 of 21

80000047963 BAL

Page 90
Image 90
AEG PV.630 manual External Connections, System not installed correctly, Power terminals, Control/Monitoring terminals