Protect PV.630 Installation and Start-up

4.8Tightening Torque Values for Screw Connections

These values apply to the electrical and mechanical connections.

They do not apply to the floor attachment of the system or the indi- vidual control cabinets where the floor is subject to dynamic force.

The specified torque information for the built-in units must be ob- served.

 

Required torques of the electrical screw connections

 

 

 

 

 

 

 

 

 

Connection of devises in general

Copper-rails connections

 

 

 

 

 

 

 

 

Nominal torque [Nm]

Nominal torque [Nm]

Screw size

 

acc. N57 2205

 

acc. N57 2201

 

slotted-head

hex-head

hex-head (min)

 

 

 

 

strength class 8.8

 

 

strength class 5.8

strength class 8.8

 

 

min.

max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2,5

 

0,21 - 0,42

0,33

- 0,65

 

 

M3

 

0,37 - 0,74

0,58 - 1,2

 

 

M3,5

 

0,57 - 1,15

0,9 - 1,85

 

 

M4

 

0,85 - 1,7

1,35 - 2,7

2

2,7

M5

 

1,75 - 2,65

2,8

- 5,5

3

5,5

M6

 

2,95 - 4,4

4,7

- 9,3

5,5

9,3

M8

 

7,0 - 14,0

11,5

- 22,5

15

22,5

M10

 

 

22 – 44

30

44

M12

 

 

38 – 75

60

75

M16

 

 

90 – 180

120

180

M20

 

 

174

- 347

 

 

 

 

 

 

 

 

 

Table 1

Tightening torque values for screw connections

 

12 of 21

80000047963 BAL

Page 88
Image 88
AEG PV.630 manual Tightening Torque Values for Screw Connections