AEG PV.630 manual Single Operation, Change of status to separate operation

Models: PV.630

1 128
Download 128 pages 35.18 Kb
Page 41
Image 41

Protect PV.630 Operating Instructions

Figure 10 Linked operation in partner operating mode

Change of status to separate operation:

If capacity utilisation in the inverter which is switched on rises above a certain value, once a delay has elapsed, the two inverters are switched to separate operation.

First, the inverter which is switched on is switched off. Then, the tie switch is opened. Once the tie switch is open, both inverters are switched on.

Change of status to linked operation in the event of a fault: In the event of a deactivating or self-acknowledging fault in the in- verter which is switched on, the system switches to linked opera- tion.

The inverter which is switched off is switched on. The faulty invert- er is shut down due to the fault.

5.5.2Single Operation

Both inverters are switched on and are feeding power into the mains. The tie switch is open.

This operating mode is active when insolation levels are high.

Figure 11 Single operation in partner operating mode

Change of status to linked operation:

If the capacity utilisation of the two inverters falls below a certain value, the system switches to linked operation once a set delay has elapsed.

The MPP tracker is switched off in both inverters and an attempt is made to regulate the two inverters to a uniform DC voltage. When the DC voltages are approximately identical, the tie switch is closed and one inverter is switched off. If the DC voltages cannot be regulated to the same value in a certain time, the two MPP trackers switch back on. Once a delay has elapsed, the MPP trackers are switched back off again and the next attempt to match the DC voltage is started.

Change of status to linked operation in the event of a fault:

In the event of a deactivating or self-acknowledging fault in one in- verter, the two inverters are switched to linked operation. First, the inverter which is not affected by the fault is also switched off.

8000047961 BAL

37 of 72

Page 41
Image 41
AEG PV.630 manual Single Operation, Change of status to separate operation, Change of status to linked operation