Protect PV.630 Operating Instructions

Kabel/Cable

19,5

9,5

12

Figure 17

Shield connection

7.1.4Configuration

The communication interface does not have to be configured in or- der to connect the PV inverter to the data logger system of the AEG “PV.LoG”. Once the bus cable has been installed and the system has been powered up, the configuration settings are made fully automatically.

If you are using a different/in-house monitoring system, you can adjust the transmission parameters and the slave address of the Modbus interface to suit your requirements via port 1 (X2). We would be happy to provide you with the Modbus unit profile on re- quest.

7.1.4.1 Configuration Preparations

You will need a 1:1 data line and a PC.

For this configuration, you must connect the PC to the MultiCom interface (X2) via the data line and start a terminal program, e.g. Hyperterminal, on the PC.

Setting the terminal program:

Data transmission:

COMx, 9600 baud/8 data bits/1 stop bit

No parity/no protocol

Terminal emulation: VT100

You can then start the configuration by pressing the “S1” button on the MultiCom interface. Ensure that no communication has taken place via interfaces X2/X5 for at least 10 seconds before doing so.

Initiation of the configuration is displayed by the two LEDs flashing on the MultiCom interface and the following display on the termi- nal:

“PRESS <CR> FOR CONFIGURATION WHILE LED IS FLASHING”

The configuration starts provided you press the <ENTER> key (<CR>) within 30 seconds. The configuration main menu opens: