Protect PV.630 Installation and Start-up

The required air is drawn in through the control cabinet doors and the ventilation slots at the base, and let out through the roof or the back panel.

 

2700

 

 

 

2

 

 

07

 

 

 

02

 

 

 

 

 

 

1

 

1

 

 

1

11,5

600

75

1500

1200

 

 

 

 

600

 

660

 

625

 

925

 

 

 

Figure 1 Air vents on the system (1=supply air, 2=exhaust air)

Additional installation site requirements:

-

-

-

It must be free from conductive dust

It must be free from corrosive acid vapours

The maximum system supply air temperature must not be exceeded

- The air vents on the system must not be obstructed, includ- ing by the structural conditions or features of the installation site.

CAUTION

Risk of injury due to rotating fans!

The fans of the INV control cabinet are freely accessible.

Never reach into rotating fans.

When setting up any system, ensure that the fans can- not be touched.

6 of 21

80000047963 BAL

Page 82
Image 82
AEG PV.630 manual Air vents on the system 1=supply air, 2=exhaust air