Apollo IMY instruction manual Module #6 Program ALARM/SETPOINT

Page 16

MODULE #6 - PROGRAM ALARM/SETPOINT

If the alarm option is installed, this module is used to configure the operation of the alarms to a variety of combinations. The programmable options are HI/LO acting, auto/manual reset (latching), tracking, assignment to input or integrator/totalizer, display alarms, alarm values and hysteresis (deadband) values.

ALARM TRACKING

With alarm tracking, whenever alarm #2 is changed, alarm #1 will also change so that the offset between alarm #2 and alarm #1 remains the same. This is useful for hierarchical setpoints (pre-alarm and alarm) when one change applies to both alarm values. When programming from the front panel, tracking only occurs when PGM. DIS. is low (front panel lock-out mode, alarm #1 will not appear). Tracking will always occur if alarm #2 is modified via serial communications independent of PGM. DIS.

“trAc” < > “yES” or “NO”

DISPLAY ALARMS

If display alarms are desired, a message will flash on the display every 5-10 secs when an alarm activates. For alarm 1, the message will flash “AL1 ON” and alarm 2 will flash “AL2 ON”. This warns an operator of an alarm condition. The message will stop when the unit is no longer in an alarm condition.

“dISP” < > “yES” or “NO”

AUTO OR MANUAL RESET FOR ALARM #1

The reset action of alarm #1 may be programmed to reset automatically (unlatched) or be programmed to require a manual reset (latched), through either a remote input (E1-CON or optional E2-CON)or through the front panel. Latched alarms are usually used when an operator is required to take some action for the alarm condition.

“LAtC-1” < > “yES” or “NO”

ALARM #1 ASSIGNMENT TO INPUT OR

INTEGRATOR/TOTALIZER

Alarm #1 may be programmed to activate on either the input or the integrator/totalizer value. If the integrator/totalizer option is not installed, this step defaults to the input.

“ASN-1” < > “INPUt” or “totAL”

PROGRAM VALUE FOR ALARM #1

The range of the alarm value is -999 to 9,999 for the input display and -99999 to 999999 for the totalizer option display.

“AL-1” < > “-999” to “9999”

PROGRAM HYSTERESIS VALUE FOR ALARM #1 (Cannot be programmed if alarm latch is programmed)

The hysteresis (deadband) value for alarm #1 may be programmed from 1 to 9,999 for the input and 1 to 999999 for the totalizer option. The value is either added to or subtracted from the alarm value depending on whether the alarm is high or low acting. (See “alarm” section for operation.)

“HyS-1” < > “1” to “9999”

ALARM #1 HIGH OR LOW ACTING

The action of alarm #1 may be programmed to activate either when the display value goes above the alarm value (high acting) or goes below it (low acting).

“Act-1” < > “HI” or “LO”

AUTO OR MANUAL RESET FOR ALARM #2

The reset action of alarm #2 may be programmed to reset automatically (unlatched) or be programmed to require a manual reset (latched), through either a remote input (E1-CON or optional E2-CON)or through the front panel. Latched alarms are usually used when an operator is required to take some action for the alarm condition.

“LAtC-2” < > “yES” or “NO”

-14-

Image 16
Contents Apollo Intelligent Meter Series Introduction Table of Contents Page Safety Summary Safety InformationDefinition of Terms General Description Theory of OperationBlock Diagram Programming and Operating the IMY Programming the IMYDisplay Module #2 Program Temperature Display Offset and Slope Display Alarm Values Enter Alarm ValuesReset Latched Alarms Reset PEAK/VALLEY Memory BufferTemperature Offset Value Enter Offset ValueModule #4 Program Digital Filter and Remote Input Program Digital FilteringProgram Function of E1-CON and Optional E2-CON Cont’d Program Decimal Point Position for the INTEGRATOR/TOTALIZER Module #5 Program INTEGRATOR/TOTALIZERProgram INTEGRATOR/TOTALIZER Time Base Module #6 Program ALARM/SETPOINT Program Value for Alarm #2 Alarm #2 Assignment to Input or INTEGRATOR/ TotalizerAlarm #2 High or LOW Acting Baud Rate Unit Address NumberPrint Request Function Full or Abbreviated TransmissionModule #8 Program RE-TRANSMITTED Analog Output Analog Output SourceAnalog Output LO Display Value Analog Output HI Display ValueModule #9 Service Operations Enter Access CodeEnter Zero Reference Apply Precision ResistanceOperating the IMY Quick ProgrammingFactory Configuration SlopeProgramming Example Temperature Monitoring Example INTEGRATOR/TOTALIZER Offset and Slope Display TemperaturePEAK/VALLEY Basic SET-UP INTEGRATOR/TOTALIZER ExampleINTEGRATOR/TOTALIZER SET-UP 125 x 827 Alarms Optional Alarm Timing DiagramsGeneral Description Communication FormatSending Commands to the IMY Command String ExamplesTiming Diagrams Current Loop Installation Wiring ConnectionsReceiving Data from the IMY Serial Terminal DescriptionsConnecting to AN RLC Printer Serial Communications ExamplesProcess Controlling System RE-TRANSMITTED Analog Output Optional Analog Output Calibration To 20 mA CalibrationInstallation Environment Appendix a Installation & ConnectionsSelect AC Power 115/230 VAC EMC Installation Guidelines Wiring Connections Power WiringAppendix B Specifications and Dimensions Open Thermistor Detection Display UlululTo 20 mA Certifications and Compliances Safety Appendix C Troubleshooting Guide Problem Possible Cause RemediesAppendix D Programmable Functions Decimal Point PositonAppendix D Programmable Functions Cont’d Appendix E Ordering Information E2-CONLimited Warranty IMY/IM-A 3/02 Drawing NO. LP0311