Apollo IMY Alarm #2 Assignment to Input or INTEGRATOR/ Totalizer, Program Value for Alarm #2

Page 17

ALARM #2 ASSIGNMENT TO INPUT OR INTEGRATOR/ TOTALIZER

Alarm #2 may be programmed to activate on either the input or the integrator/totalizer value. If the integrator/totalizer option is not installed, this step defaults to the input.

“ASN-2” < > “INPUt”or “totAL”

PROGRAM VALUE FOR ALARM #2

The range of the alarm value is -999 to 9,999 for the input display and -99999 to 999999 for the totalizer option display.

“AL-2” < > “-999” to “9999”

PROGRAM HYSTERESIS VALUE FOR ALARM #2 (Cannot be programmed if alarm latch is programmed)

The hysteresis (deadband) value for alarm #2 may be programmed from 1 to 9,999 for the input and 1 to 999999 for the totalizer option. The value is either added to or subtracted from the alarm value depending on whether the alarm is high or low acting. (See “alarms” section for operation.)

“HyS-2” < > “1” to “9999”

ALARM #2 HIGH OR LOW ACTING

The action of alarm #2 may be programmed to activate either when the display value goes above the alarm value (high acting) or goes below it (low acting).

“Act-2” < > “HI” or “LO”

Note: Depending on options selected under Pro 3 and Pro 6, alarms, hysteresis, peak, and valley values can be monitored and/or changed when PGM. DIS. is tied to COMM. This provides a “QUICK PROGRAMMING” method for “day to day” process changes. (See QUICK PROGRAMMING SECTION for more details.)

-15-

Image 17
Contents Apollo Intelligent Meter Series Introduction Table of Contents Page Definition of Terms Safety InformationSafety Summary Theory of Operation General DescriptionBlock Diagram Programming the IMY Programming and Operating the IMYDisplay Module #2 Program Temperature Display Offset and Slope Enter Alarm Values Display Alarm ValuesReset Latched Alarms Reset PEAK/VALLEY Memory BufferEnter Offset Value Temperature Offset ValueProgram Digital Filtering Module #4 Program Digital Filter and Remote InputProgram Function of E1-CON and Optional E2-CON Cont’d Program INTEGRATOR/TOTALIZER Time Base Module #5 Program INTEGRATOR/TOTALIZERProgram Decimal Point Position for the INTEGRATOR/TOTALIZER Module #6 Program ALARM/SETPOINT Alarm #2 High or LOW Acting Alarm #2 Assignment to Input or INTEGRATOR/ TotalizerProgram Value for Alarm #2 Unit Address Number Baud RatePrint Request Function Full or Abbreviated TransmissionAnalog Output Source Module #8 Program RE-TRANSMITTED Analog OutputAnalog Output LO Display Value Analog Output HI Display ValueEnter Access Code Module #9 Service OperationsEnter Zero Reference Apply Precision ResistanceQuick Programming Operating the IMYSlope Factory ConfigurationProgramming Example Temperature Monitoring Example PEAK/VALLEY Offset and Slope Display TemperatureINTEGRATOR/TOTALIZER INTEGRATOR/TOTALIZER SET-UP INTEGRATOR/TOTALIZER ExampleBasic SET-UP 125 x 827 Alarm Timing Diagrams Alarms OptionalCommunication Format General DescriptionCommand String Examples Sending Commands to the IMYTiming Diagrams Wiring Connections Current Loop InstallationReceiving Data from the IMY Serial Terminal DescriptionsSerial Communications Examples Connecting to AN RLC PrinterProcess Controlling System RE-TRANSMITTED Analog Output Optional To 20 mA Calibration Analog Output CalibrationSelect AC Power 115/230 VAC Appendix a Installation & ConnectionsInstallation Environment EMC Installation Guidelines Power Wiring Wiring ConnectionsOpen Thermistor Detection Display Ululul Appendix B Specifications and DimensionsTo 20 mA Certifications and Compliances Safety Problem Possible Cause Remedies Appendix C Troubleshooting GuideDecimal Point Positon Appendix D Programmable FunctionsAppendix D Programmable Functions Cont’d E2-CON Appendix E Ordering InformationLimited Warranty IMY/IM-A 3/02 Drawing NO. LP0311