ALARM #2 ASSIGNMENT TO INPUT OR INTEGRATOR/ TOTALIZER
Alarm #2 may be programmed to activate on either the input or the integrator/totalizer value. If the integrator/totalizer option is not installed, this step defaults to the input.
PROGRAM VALUE FOR ALARM #2
The range of the alarm value is
PROGRAM HYSTERESIS VALUE FOR ALARM #2 (Cannot be programmed if alarm latch is programmed)
The hysteresis (deadband) value for alarm #2 may be programmed from 1 to 9,999 for the input and 1 to 999999 for the totalizer option. The value is either added to or subtracted from the alarm value depending on whether the alarm is high or low acting. (See “alarms” section for operation.)
ALARM #2 HIGH OR LOW ACTING
The action of alarm #2 may be programmed to activate either when the display value goes above the alarm value (high acting) or goes below it (low acting).
Note: Depending on options selected under Pro 3 and Pro 6, alarms, hysteresis, peak, and valley values can be monitored and/or changed when PGM. DIS. is tied to COMM. This provides a “QUICK PROGRAMMING” method for “day to day” process changes. (See QUICK PROGRAMMING SECTION for more details.)