Apollo IMY Module #9 Service Operations, Enter Access Code, Enter Zero Reference

Page 20

MODULE #9 - SERVICE OPERATIONS

The indicator has been fully calibrated at the factory. If the unit appears to be indicating incorrectly or inaccurately, refer to the troubleshooting section before attempting this procedure.

When re-calibration is required (generally every 2 years), this procedure should only be performed by qualified technicians using appropriate equipment. Resistance source accuracies of 0.01% or better are required.

The procedure consists of applying accurate signal levels to the indicator in a series of two steps. Allow a 30 minute warm-up period before starting this procedure.

Note: Once the access code has been entered, there is no exiting the program module without completing the calibration procedure.

ENTER ACCESS CODE

“Code 48” must be keyed-in prior to the calibration sequence to guard against inadvertent entries. Access code numbers other than those listed in this section should not be entered at this step. If any are entered, undefined or unpredictable operation could result.

“CodE” < > “0” to “99”

If the code number for the previous step was not recognized, the indicator returns to “Pro 0”, with no action taken. Otherwise, the calibration procedure is started.

ENTER ZERO REFERENCE

Apply 0 ohms to input by shorting Terminals 6 and 7 as shown in the drawing to the right. Allow to stabilize for 20 seconds before pressing “P”.

“StEP 1” (Press “P”)

APPLY PRECISION RESISTANCE

Connect a precision (0.01%) 5.11 K￿ resistor across

Terminals 6 and 7.

Allow to stabilize for 20 seconds before pressing “P”. “StEP 2” (Press “P”)

-18-

Indicator calibration is complete. It is recommended that calibration be checked by comparing the displayed temperature with a precision thermometer.

SERIAL HARDWARE (loop-back) DIAGNOSTICS

The internal serial communications hardware in the IMY can be tested to verify proper operation. The procedure consists of connecting the Serial Input (SI), Serial Output (SO), and

20 mA Source into a simple loop, and then entering an access code.

Connect the IMY as shown at right. Enter “Pro 9”, key-in “Code 39”, and then press “P”. If the serial communication hardware is OK, “PASS” will be displayed.

Conversely, if there is an internal problem, “FAIL” will be displayed. After the diagnostic test is complete, press “P” to return to “Pro 0”.

“CodE” < > “39”

RESTORING ALL PROGRAMMING PARAMETERS BACK TO FACTORY CONFIGURATION

All of the programming in Modules #1 through #8 can be restored back to the factory configuration by entering a specific access code (refer to the “Factory Configuration” section for the data that will be entered). The procedure consists of entering “Pro 9”, keying-in “Code 66”, then pressing “P”. The IMY responds by displaying “INItAL” for several seconds, and then returns to “Pro 0”.

Note: When this procedure is performed, all of the scaling, presets, etc. that were programmed into the IMY will be overwritten.

“CodE” < > “66”

Image 20
Contents Apollo Intelligent Meter Series Introduction Table of Contents Page Definition of Terms Safety InformationSafety Summary General Description Theory of OperationBlock Diagram Programming and Operating the IMY Programming the IMYDisplay Module #2 Program Temperature Display Offset and Slope Display Alarm Values Enter Alarm ValuesReset Latched Alarms Reset PEAK/VALLEY Memory BufferTemperature Offset Value Enter Offset ValueModule #4 Program Digital Filter and Remote Input Program Digital FilteringProgram Function of E1-CON and Optional E2-CON Cont’d Program INTEGRATOR/TOTALIZER Time Base Module #5 Program INTEGRATOR/TOTALIZERProgram Decimal Point Position for the INTEGRATOR/TOTALIZER Module #6 Program ALARM/SETPOINT Alarm #2 High or LOW Acting Alarm #2 Assignment to Input or INTEGRATOR/ Totalizer Program Value for Alarm #2 Baud Rate Unit Address NumberPrint Request Function Full or Abbreviated TransmissionModule #8 Program RE-TRANSMITTED Analog Output Analog Output SourceAnalog Output LO Display Value Analog Output HI Display ValueModule #9 Service Operations Enter Access CodeEnter Zero Reference Apply Precision ResistanceOperating the IMY Quick ProgrammingFactory Configuration SlopeProgramming Example Temperature Monitoring Example PEAK/VALLEY Offset and Slope Display TemperatureINTEGRATOR/TOTALIZER INTEGRATOR/TOTALIZER SET-UP INTEGRATOR/TOTALIZER ExampleBasic SET-UP 125 x 827 Alarms Optional Alarm Timing DiagramsGeneral Description Communication FormatSending Commands to the IMY Command String ExamplesTiming Diagrams Current Loop Installation Wiring ConnectionsReceiving Data from the IMY Serial Terminal DescriptionsConnecting to AN RLC Printer Serial Communications ExamplesProcess Controlling System RE-TRANSMITTED Analog Output Optional Analog Output Calibration To 20 mA CalibrationSelect AC Power 115/230 VAC Appendix a Installation & ConnectionsInstallation Environment EMC Installation Guidelines Wiring Connections Power WiringAppendix B Specifications and Dimensions Open Thermistor Detection Display UlululTo 20 mA Certifications and Compliances Safety Appendix C Troubleshooting Guide Problem Possible Cause RemediesAppendix D Programmable Functions Decimal Point PositonAppendix D Programmable Functions Cont’d Appendix E Ordering Information E2-CONLimited Warranty IMY/IM-A 3/02 Drawing NO. LP0311