Nordyne AND M5S, SERIES M1B Control Module Status Indicators M1M Series, Red LED Indicator Status

Page 29

 

Control Module Status Indicators - M1M Series

Red LED Indicator

Status

 

 

Steady ON

Control OK

 

 

Steady OFF

No power

 

 

Rapid fl ash

False fl ame or internal control fault

 

 

One fl ash

Limit switch is open

 

 

Two fl ashes

Pressure switch is open

 

 

Three fl ashes

Pressure switch is stuck closed

 

 

Four fl ashes

Lockout due to failed ignition

 

 

Five fl ashes

L1 neutral reversed or L1 voltage not present on L1

 

 

Flame Status - A Yellow LED labeled “Flame” is provided to indicate fl ame status. When fl ame is sensed, the fl ame LED is lit. If fl ame sense is weak, yellow LED will fl ash.

 

Control Module Status Indicator - M1B

 

 

Red LED Indicator

Status

 

 

One fl ash

The control is in lock-out because the inducer centrifugal switch is or

was stuck closed.

 

 

 

Two fl ashes

The control is in lockout because the signal was not received by the

control that the inducer centrifugal switch had closed within the time.

 

 

 

 

The control is in lockout because a failed ignition attempt, a gas valve

Three fl ashes

error, or a false fl ame sensed during the warm up period. If false fl ame

has been sensed, the control will return to normal operation, and repeat

 

 

ignition sequence when the false fl ame is not present.

 

 

Four fl ashes

The control is in lockout due to a failure within the control board

 

 

Control Module Status Indicator - M5S Series

The LED indicator(s) on the oil primary control provides lockout, recycle and cad cell indications.

Honeywell R7184 Control

Green LED Indicator

Status

 

 

On

Cad cell is sensing flame (could be fl ame or stray light)

 

 

Off

Cad cell is not sensing flame

 

 

Flashing - 1/2 sec. on, 1/2 sec. off

Lockout/Restricted Lockout

 

 

Flashing - 2 sec. on, 2 sec. off

Recycle

 

 

Beckett 7505 Control

LED Indicator Color

On Continuously

Flashing

 

 

 

Red

Restricted (hard) lockout

Soft lockout

 

 

 

Green

Cad cell is sensing fl ame -

Recycle

(could be fl ame or stray light)

 

 

 

 

 

Yellow

Pump prime mode or reset

N/A

button currently held for 15+ sec.

 

 

 

Table 9. Control Module Status Indicators

29

Image 29
Contents For installation Installation InstructionsStanding Pilot Models Direct Ignition Models Oil Gun Models Homeowner Information Installer Information InformationReturn Air Connections Supply Air Connections Requirements and Codes Safety InformationGeneral Installation Gas Piping and Gas Pipe Pressure TestingSafety Combustion and Ventilation AirALL Models Closet Alcove General InformationMinimum Clearances Applications AssemblyUnit Location BlowerReturn Air Connections Circulating AIR RequirementsGas piping is not run in or through the return duct system Supply Air ConnectionsDetermine which duct connector to use from Furnace InstallationGeneral Information Requirements and CodesDuct Connector Sizes Standard Duct Connector Installation Cut-Out Dimensions for Standard Duct ConnectorsInstalling The Furnace Duct Connector TabsRequired ceiling and roof cut-out openings see Roof Jack InstallationRoof Jack Selection Application NotesSlant Deck Flashings Roof Jack Series If Roof Pitch is Slant Deck FactorInstallation of Transit-Mode Venting System Installing The Roof JackConnect fl ue pipe to fl ue collar of furnace. See Figure Secure fl ashing with appropriate fastenersElectrical Information Line Voltage WiringWire Heating Heating/Cooling Low Voltage WiringThermostat Wire Gauge Thermostat Length Unit to T’STATImportant Notes Fuel Supply and PipingFuel line Hook-Up Oil Tank and Piping InstallationConversion to Propane LP Gas Leak CheckFuel Oil Type Honeywell Gas Valve High Altitude ConversionStanding Pilot Valve Lighting Instructions Standing Pilot ModelsOperating Instructions for Direct Ignition Models M1M Replace the furnace doorPilot Flame Standing Pilot Only Burner AdjustmentsFor oil, shut off all valves Replace the furnace door Combustion Air Factory Combustion Air SettingsElectrode Setting Oil Gun Only Standing Pilot Operating SequenceStanding Pilot w/Induced Draft Blowers M1M Models with Direct IgnitionFurnace Controls & Functions Direct Ignition Furnaces Including Gas Gun M1B Series see , TroubleshootingStanding Pilot Models Page Optional Accessories Burner will not start and the LED indicator isCad Cell Resistance when Sensing flame Cad cell is operational, replace the primary controlRed LED Indicator Status Control Module Status Indicators M1M SeriesControl Module Status Indicator M1B Control Module Status Indicator M5S SeriesInstaller Information MaintenanceAdditional Oil Furnace Maintenance Clean or replace the oil fi lter element at the oil tankM1GB Burner Direct Blower TonsM1MC Manifold Pressure Natural Gas 3.5 w.cOrifi ce Size Nat. Gas Orifi ce Size LP Equivalent Orifice Sizes for High Altitude InstallationsOutput Mbtuh Orifi ce Size Nat. GasGas Flow Rates Cubic Feet per Hour GAS InformationModels Wiring DiagramsM1GH 077, 090 Models M1GB 056, 070 Models Gas AtmosphericWiring Diagram Steady OFF No power Blinking Wiring Diagram Installation Address Installation / Performance Check List