Nordyne SERIES M1B Applications, Unit Location, Assembly, Blower, Tons, Wheel, 10 x, 11 x

Page 6

6" (152 mm)

Top Clearance

0" Side Clearance to Furnace Cabinet

Removable access panel should be installed above furnace door frame to access roof jack

18"

 

(457

mm)

Nearest

 

 

Wall or

 

 

Partition

Applications

M1 Series gas and M5 Series oil furnaces are listed direct vent (sealed combustion), downfl ow heating appliances for manufactured (mobile) homes, recreational vehicles, and for use in residential/modular/commercial construction. The furnace must be located so that venting can be properly achieved.

Air conditioning may be added to structures with M1/M5 series furnaces using air conditioning or conventional units. This Installation Instruction manual includes special requirements for incorporation of air conditioning equipment to the M1/M5 series of furnaces.SeeTabel 12 (page 32).

Figure 1. Alcove Installation

6" (152 mm)

Top Clearance

0" Side Clearance to Furnace Cabinet

Provide min. 235 sq. in. (1516 cm 2 )

open free area in

front or side wall

or

In closet door

located at top, center

or bottom

(152

6"

mm)

 

Multi-speed blower assemblies shown in Table 2, have been certifi ed for fi eld installation in M1/ M5 Series furnaces.

Unit Location

• The furnace shall be appropriately located to

the supply and return air distribution system

(See Page 7). Sides and back of the furnace

may be enclosed by wall framing.See Minimum

Clearances (page 2) and Figures 1- 3.

• The furnace installation is only intended for

free air return through the furnace door louvers.

DO NOT connect a ducted return air system

CLOSET DOOR

Figure 2. Closet Installation

directly to the furnace. Improper installation

may create a hazard and damage equipment,

as well as void all warranties.

• Furnace may be installed on combustible

flooring when using NORDYNE Duct

6" (152 mm)

Top Clearance

0" Side Clearance to Furnace Cabinet

Provide min. 250 sq. in. (1613 cm 2) open free area in front or side wall

or

in closet

door

a fully louvered door may be used

(25

1"

mm)

 

CLOSET DOOR

Connectors. See pages 9 & 10.

• When installed in a residential garage, the

furnace must be positioned so the burners and

the source of the ignition are located no less

than 18 inches above the fl oor and protected

from physical damage by vehicles.

“A”- 56"

Figure 3. Special 1” Clearance

 

Blower / Motor

 

Part

Assembly

A/C Capacity

No.

Blower

Motor

(Tons)

 

Wheel

(Hp)

 

903773

10 x 8

1/4

2, 2½ & 3

903413

11 x 8

1/2

2, 2½, 3 & 4

903890

11 x 8

3/4

2, 2½, 3, 4 & 5

Table 2. Blower Assemblies

“A” Model

 

w/o Coil

“B”- 76"

Cabinet

“B” Model

 

w/Coil

 

Cabinet

 

23 3/4"

19 3/4"

Figure 4. Overall Dimensions

6

Image 6
Contents Installation Instructions For installationHomeowner Information Installer Information Information Return Air Connections Supply Air ConnectionsStanding Pilot Models Direct Ignition Models Oil Gun Models Safety Information Requirements and CodesSafety Gas Piping and Gas Pipe Pressure TestingGeneral Installation Combustion and Ventilation AirGeneral Information Minimum ClearancesALL Models Closet Alcove Unit Location AssemblyApplications BlowerGas piping is not run in or through the return duct system Circulating AIR RequirementsReturn Air Connections Supply Air ConnectionsGeneral Information Furnace InstallationDetermine which duct connector to use from Requirements and CodesCut-Out Dimensions for Standard Duct Connectors Duct Connector Sizes Standard Duct Connector InstallationDuct Connector Tabs Installing The FurnaceRoof Jack Selection Roof Jack InstallationRequired ceiling and roof cut-out openings see Application NotesRoof Jack Series If Roof Pitch is Slant Deck Factor Slant Deck FlashingsConnect fl ue pipe to fl ue collar of furnace. See Figure Installing The Roof JackInstallation of Transit-Mode Venting System Secure fl ashing with appropriate fastenersLine Voltage Wiring Electrical InformationThermostat Wire Gauge Low Voltage WiringWire Heating Heating/Cooling Thermostat Length Unit to T’STATFuel Supply and Piping Important NotesOil Tank and Piping Installation Fuel line Hook-UpLeak Check Fuel Oil TypeConversion to Propane LP Gas High Altitude Conversion Honeywell Gas ValveLighting Instructions Standing Pilot Models Standing Pilot ValveReplace the furnace door Operating Instructions for Direct Ignition Models M1MBurner Adjustments For oil, shut off all valves Replace the furnace doorPilot Flame Standing Pilot Only Factory Combustion Air Settings Electrode Setting Oil Gun OnlyCombustion Air Standing Pilot w/Induced Draft Blowers Operating SequenceStanding Pilot M1M Models with Direct IgnitionFurnace Controls & Functions Troubleshooting Standing Pilot ModelsDirect Ignition Furnaces Including Gas Gun M1B Series see , Page Cad Cell Resistance when Sensing flame Burner will not start and the LED indicator isOptional Accessories Cad cell is operational, replace the primary controlControl Module Status Indicator M1B Control Module Status Indicators M1M SeriesRed LED Indicator Status Control Module Status Indicator M5S SeriesAdditional Oil Furnace Maintenance MaintenanceInstaller Information Clean or replace the oil fi lter element at the oil tankM1MC Burner Direct Blower TonsM1GB Manifold Pressure Natural Gas 3.5 w.cOutput Mbtuh Equivalent Orifice Sizes for High Altitude InstallationsOrifi ce Size Nat. Gas Orifi ce Size LP Orifi ce Size Nat. GasGAS Information Gas Flow Rates Cubic Feet per HourWiring Diagrams ModelsM1GH 077, 090 Models Gas Atmospheric M1GB 056, 070 ModelsWiring Diagram Steady OFF No power Blinking Wiring Diagram Installation / Performance Check List Installation Address