120 VAC Is Available At AMP Plug - Ignitor Does Not Heat Up

1.Disconnect power to the furnace.

2.Disconnect AMP plug to the ignitor, and check ignitor resistance with an ohm meter. Set on RX1 scale.

Normal reading should be 40 - 75 ohms.

If above or below this rating at room tem- perature change ignitor.

3.Check for continuity from ignitor receptacle to burner.

Main Flame Ignites - Burner Locks Out

Ignition control is not properly grounded.

Defective ignition control.

Improper polarity of 120 volt power supply.

Ignitor has hairline crack.

Improper gas pressure or burner air adjustment is not allowing fl ame to contact ignitor tip for fl ame rectifi cation.

Misaligned ignitor does not allow fl ame to contact ignitor tip for fl ame rectifi cation.

Burner Short Cycling - Thermostat Calls for Heat, Limit Switches Closed

Check for polarity.

Check ground.

Check fl ue.

Check combustion air.

Check gas pressure.

Check orifi ce.

Check the position of ignitor, a normal reading should be 40-75 ohms.

24 Volts Supplied To Gas Valve During Ignition - No Main Gas Flow

Gas valve may be defective. Replace if necessary.

Gas piping may be plugged. Check for adequate gas supply to gas valve at union.

Burner Operates - Insuffi cient Heat

Check thermostat for proper setting and location. Thermostat should not be located where it will be affected by another heat source.

Check for clean fi lter and proper air fl ow.

Check burner for proper gas fi ring rate.

Be sure unit is not undersized for its thermal load.

Check thermostat anticipator. The nominal setting is 0.4.

Burner Flame Without Motor Running

Gas valve stuck open, check gas valve for proper operation (replace if necessary) and inspect heat exchanger.

Check for 115 volts to the combustion blower motor; replace if necessary.

If no power to combustion blower then check wiring and control module;replace if necessary.

Circulation Air Blower Will Not Operate Even Though The Burner Does Operate

Check thermostat G connection.

Check wiring to motor.

Check for a defective motor.

Oil Gun - Honeywell R7184 or Beckett 7505 Controls Only - M5S Series.

Burner does not start with a call for heat.

Check the electrical supply to furnace.

Verify the furnace door switch is in the ON position.

Check for line voltage (115 VAC) at the oil primary control.

Check indicator LED with burner off, no call for heat (no fl ame). See Table 9 (page 29).

-If green LED indicator is on, the cad cell is seeing stray light or the cad cell of controller is defective.

-If green LED indicator is off, go immediately to step 5.

-If LED indicator is fl ashing (red or green on Beckett 7505 control), refer to the next step 1 below - Reset primary control.

Jumper T to T terminals on primary control.

-If burner starts, check thermostat or limit wiring connections.

-If burner does not start, turn off power.Check all wiring connections.

-If burner does not start, replace primary control.

Burner starts and then locks out on safety with Honeywell R7184 LED indicator fl ashing

½second on, ½ second off. For Beckett 7505 control, the red LED will fl ash.

1.Reset primary control: To reset the control from (soft) lockout, the button needs only to be pressed and released. If the R7184 control is in restricted mode, press and hold the button for 45 seconds - until the LED fl ashes once. If the 7505 control is in restricted mode, press and hold the button in for 15 seconds until the red turns off and the yellow LED turns on.

NOTE: Restricted Lockout: If the control locks out three times in a row without a complete heat cycle between attempts, the lockout becomes a restricted (hard) lockout.

2.If the LED indicator stops fl ashing and the ignition remains off, the primary control could be defective. If line voltage is present at the igniter terminals, and there is no ignition, the igniter is likely defective and needs to be replaced.

3.If the stops fl ashing, burner turns on, but the control locks out again, check the cad cell. If

27

Image 27
Contents For installation Installation InstructionsHomeowner Information Installer Information Information Return Air Connections Supply Air ConnectionsStanding Pilot Models Direct Ignition Models Oil Gun Models Requirements and Codes Safety InformationCombustion and Ventilation Air Gas Piping and Gas Pipe Pressure TestingGeneral Installation SafetyGeneral Information Minimum ClearancesALL Models Closet Alcove Blower AssemblyApplications Unit LocationSupply Air Connections Circulating AIR RequirementsReturn Air Connections Gas piping is not run in or through the return duct systemRequirements and Codes Furnace InstallationDetermine which duct connector to use from General InformationDuct Connector Sizes Standard Duct Connector Installation Cut-Out Dimensions for Standard Duct ConnectorsInstalling The Furnace Duct Connector TabsApplication Notes Roof Jack InstallationRequired ceiling and roof cut-out openings see Roof Jack SelectionSlant Deck Flashings Roof Jack Series If Roof Pitch is Slant Deck FactorSecure fl ashing with appropriate fasteners Installing The Roof JackInstallation of Transit-Mode Venting System Connect fl ue pipe to fl ue collar of furnace. See FigureElectrical Information Line Voltage WiringThermostat Length Unit to T’STAT Low Voltage WiringWire Heating Heating/Cooling Thermostat Wire GaugeImportant Notes Fuel Supply and PipingFuel line Hook-Up Oil Tank and Piping InstallationLeak Check Fuel Oil TypeConversion to Propane LP Gas Honeywell Gas Valve High Altitude ConversionStanding Pilot Valve Lighting Instructions Standing Pilot ModelsOperating Instructions for Direct Ignition Models M1M Replace the furnace doorBurner Adjustments For oil, shut off all valves Replace the furnace doorPilot Flame Standing Pilot Only Factory Combustion Air Settings Electrode Setting Oil Gun OnlyCombustion Air M1M Models with Direct Ignition Operating SequenceStanding Pilot Standing Pilot w/Induced Draft BlowersFurnace Controls & Functions Troubleshooting Standing Pilot ModelsDirect Ignition Furnaces Including Gas Gun M1B Series see , Page Cad cell is operational, replace the primary control Burner will not start and the LED indicator isOptional Accessories Cad Cell Resistance when Sensing flameControl Module Status Indicator M5S Series Control Module Status Indicators M1M SeriesRed LED Indicator Status Control Module Status Indicator M1BClean or replace the oil fi lter element at the oil tank MaintenanceInstaller Information Additional Oil Furnace MaintenanceManifold Pressure Natural Gas 3.5 w.c Burner Direct Blower TonsM1GB M1MCOrifi ce Size Nat. Gas Equivalent Orifice Sizes for High Altitude InstallationsOrifi ce Size Nat. Gas Orifi ce Size LP Output MbtuhGas Flow Rates Cubic Feet per Hour GAS InformationModels Wiring DiagramsM1GH 077, 090 Models M1GB 056, 070 Models Gas AtmosphericWiring Diagram Steady OFF No power Blinking Wiring Diagram Installation Address Installation / Performance Check List