LG Electronics LGxxxA1C-B3 Product Specifications, AC Module, Parameter Section Value, VAC 208VAC

Page 31

6 Product Specifications

6-1 AC Module

DC Input

Parameter

Section

 

Value

 

 

 

 

 

 

Power

Max.

295 W

300 W

305 W

Tolerance

3 %

3 %

3 %

 

Voltage

Open Circuit

39.7 V

39.8 V

40.0 V

 

 

 

 

Max Power Point

31.8 V

32.0 V

32.1 V

 

Current

Short Circuit

9.85 A

9.98 A

10.10 A

 

 

 

 

Max Power Point

9.28 A

9.40 A

9.52 A

 

Efficiency

Relative Reduction

 

< 2.0 %

 

 

 

 

 

Note : Relative efficiency reduction in respect to irradiance.

 

 

 

Note : Rated electrical characteristics are within 10 percent of above figures.

 

 

PV module was measured at STC. (Standard Test Condition: Irradiation 1,000W/m2, Cell temp. 77ºF(25),

1.5AM)

 

 

 

 

 

 

 

 

AC Output

 

 

 

 

 

 

 

 

Parameter

 

Section

240VAC

 

208VAC

 

 

 

 

 

 

 

AC Continuous1)

280W(@DC Module 295W) /

285W(@DC Module 300W) /

Power

 

290W(@DC Module 305W)

 

 

Inverter Rated Continuous

305 W

 

300W

 

 

 

 

 

 

Voltage

 

Rated

240 V (211 ~ 264 V)

 

208 V (187 ~ 229 V)

Current

 

Rated

1.27 A

 

1.44 A

 

 

 

 

 

 

Max Fault Current

 

77 A

 

 

 

Frequency

 

Nominal

60 Hz (59.3 ~ 60.5 Hz)

 

 

 

 

 

 

Extended2)

57.0 Hz ~ 60.5 Hz

 

 

 

Power Factor

 

> 0.95

 

 

 

 

CEC Weighted Efficiency

96.5 %

 

96.0 %

(California Energy Commission)

 

 

 

 

Max. Number of AC Modules3)

12 units

 

11 units

1)AC Continuous = Max Input DC Power x CEC Efficiency.

2)For setting frequency rage, refer to Chapter 4-3. Configuring the Instalation App - Step 5.

3)For details, refer to Chapter 3-10. Connecting AC Module Array to Distribution Panel.

 

Protection

 

 

Ground Fault Detection and Interrupt (GFDI)

Applied

Fuse (Internal of the Micro Inverter)

2A

CAUTION : FOR CONTINUED PROTECTION AGAINST RISK OF FIRE,

REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE.

Over Current Protection Device (OCPD)3)

20A

3)For details, refer to Chapter 3-10. Connecting AC Module Array to Distribution Panel.