Schneider Electric 2.0A, 3.0A, and 6.0A, 5.0A External Power Supply, Function Specification, 15-EN

Page 17

48049-136-05

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units

Rev. 01, 07/2012

Section 1—General Information

 

 

The following will be powered and functional with external power:

All of the above functions which are functional without external power.

Ammeter and bar graph displays are functional with or without current flowing through the circuit breaker. With current flow between 0 and 20% of sensor value, the ammeter may not be accurate.

Trip settings and max. current readings can be accessed on the display be pressing the navigation buttons with or without current flowing through the circuit breaker.

Ground-fault push-to-trip button works for testing ground fault with or without current flowing through the circuit breaker.

Optional Modbus communications are functional, using a separate 24 Vdc power supply for the circuit breaker communications module. This separate 24 Vdc power supply is required to maintain the isolation between the trip unit and communications.

The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or

Full-Function Test Kit is powering the trip unit.

External Power Supply

The trip unit display can be powered by a 24 Vdc external power supply.

ENGLISH

CAUTION

HAZARD OF SHOCK, ARC FLASH OR EQUIPMENT DAMAGE

Trip unit and communication module must use separate power supplies.

Failure to follow this instruction can result in personal injury or equipment damage.

Table 7:

Power Supply Specifications

 

 

 

 

 

 

 

 

 

 

Function

 

Specification

 

 

 

 

 

 

 

 

 

Power for Trip Unit Alone

24 Vdc, 50 mA

 

 

 

 

 

 

 

 

 

Minimum Input-to-Output Isolation

2400 V

 

 

 

 

 

 

 

 

 

Output (Including Max. 1% Ripple)

±5%

 

 

 

 

 

 

 

 

 

 

 

 

Dielectric Withstand (Input/Output)

3 kV rms

 

 

 

 

 

 

 

 

 

 

 

 

Connections UC3

 

 

Connections

 

F1 (-)

 

 

 

 

24 Vdc

 

 

F2 (+)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply is used for graphic scree display when the circuit breaker is open or not carrying current.

© 1999–2012 Schneider Electric All Rights Reserved

15-EN

Image 17
Contents Conserver pour usage ultérieur Page Retain for future use Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip UnitsPlease Note Hazard Categories and Special SymbolsFCC Notice Death or serious injuryTable of Contents List of Registers Rating Plug Removal New Rating Plug InstallationGeneral Information Trip Unit SettingsIntroduction Communications0A Trip Unit Micrologic 2.0A Trip UnitMicrologic 3.0A Trip Unit Micrologic 5.0A Trip Unit Micrologic 6.0A Trip Unit Zone-Selective Interlocking Trips and clears the fault. Circuit breaker 2 does not tripLong-Time Protection Trip Unit SwitchesMicrologic Trip Unit Long-Time Delay Values Short-Time Protection Micrologic Trip Unit Short-Time Delay ValuesInstantaneous Protection Ground-Fault Protection Indicator LightsOverload Indicator Light Micrologic Trip Unit Ground-Fault Pickup ValuesMicrologic Trip Unit Configuration Trip Unit TestingTrip Indicator Lights Control Power15-EN External Power SupplyFunction Specification Ammeter Accessing InformationDisplay Ammeter MeasurementsCurrent Menus Current MenuRev , 07/2012 Ammeter 17-EN18-EN Peak Menu19-EN Switch Settings MenuSwitch settings menu displays Operation Switch Setting AdjustmentExamples Set pickup levelsSet Time Delay Set time delayRev , 07/2012 Operation 21-EN22-EN Set Time DelaysSet time delays ZSI Combinations Zone-Selective Interlocking ZSIUnits 23-ENCommunication Module values Wire circuit breakers for zone-selectiveInterlocking 24-EN25-EN Set communication module valuesTrip Unit Settings Trip Unit Settings CheckTrip Unit Operation Verification ScreenTrip Unit Resetting Equipment Ground-Fault Trip Functions TestingTrip Unit Status Check 27-ENPreparation Trip Unit ReplacementRequired Tools Battery Installation Trip Unit ReplacementRating Plug Removal Trip Unit Removal30-EN Trip Unit InstallationReplacement Circuit Breaker Accessory CoverClose switch cover a 31-EN32-EN Trip Unit Installation CheckTrip Unit Setup Circuit Breaker Reconnection Rating Plug Removal Adjustable Rating Plug ReplacementNew Rating Plug Installation Circuit Breaker Accessory Cover Removal Battery ReplacementBattery Replacement Circuit Breaker Disconnection35-EN Withstand Module ReplacementRev , 07/2012 Battery Replacement List of Registers Appendix A-Register ListRegister List Module Module Name Equation Address Range37-EN Rev , 07/2012 Appendix A-Register ListSchneider Electric